11-5. TROUBLE JUDGEMENT CRITERIA OF MAIN PARTS
MFZ-KT25VG MFZ-KT35VG MFZ-KT50VG MFZ-KT60VG
RED
YLW
BRN
ORN
GRN
ROTOR
Part name
Figure
Check method and criteria
Indoor fan motor (MF)
Measure the resistance with a tester.
Refer to 11-7. "Test point diagram and voltage", "Indoor electronic control
P.C. board", for the chart of thermistor.
Room temperature
thermistor (RT11)
Indoor coil thermistor
(RT12 (MAIN 1), RT13 (SUB)
RT14 (MAIN 2), RT15 (MAIN 3))
Horizontal vane motor
(MV1) FRONT
Multi-flow vane motor
(MV3)
Measure the resistance between the terminals with a tester.
(Part temperature: 10°C ~ 30°C)
Normal
Measure the resistance between the terminals with a tester.
(Part temperature: 10°C ~ 30°C)
306 Ω ~ 382 Ω
Color of the lead wire
BRN-other one (350 Ω)
Horizontal vane motor
(MV2) BACK
Measure the resistance between the terminals with a tester.
(Part temperature: 10°C ~ 30°C)
Normal
219 Ω ~ 273 Ω
BRN-other one (250 Ω)
Color of the lead wire
Normal
219 Ω ~ 273 Ω
BRN-other one (250 Ω)
Color of the lead wire
Check 11-6.
“Check of indoor fan motor” and “Check of indoor
electronic control P.C. board and indoor fan motor”.
OPERATION INDICATOR
Not lit
Blinking
Lit
Right lamp blink
No.
Symptom
Operation indicator lamp
Condition
Remedy
Abnormal
point
1
MXZ type
Operation
mode
setting
Outdoor unit
operates but
indoor unit
does not
operate.
When the operation mode of the each indoor
unit is differently set to COOL (includes DRY)
and HEAT at the same time, the operation
mode of the indoor unit that has operated
first has the priority.
•
Select the same operation mode
for all the units.
Refer to the outdoor unit
service manual.
2.5-second OFF
OBH843