3
3. Installation diagram
Fig. 3-1
3.1. Outdoor unit (Fig. 3-1)
Ventilation and service space
■
SUZ-KA25VA4
SUZ-KA35VA4
A
100 mm or more
B
350 mm or more
C
Basically open 100 mm or more without any obstruction in front and on both
sides of the unit.
D
00 mm or more (Open two sides of left, right, or rear side.)
■
SUZ-KA50VA4
SUZ-KA60VA4
SUZ-KA71VA4
A
100 mm or more
B
350 mm or more
C
500 mm or more
When the piping is to be attached to a wall containing metals (tin plated) or metal
netting, use a chemically treated wooden piece 0 mm or thicker between the wall
and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.
Note:
When operating the air conditioner in low outside temperature, be sure to fol-
low the instructions described below.
• Never install the outdoor unit in a place where its air inlet/outlet side may be ex-
posed directly to wind.
• To prevent exposure to wind, install the outdoor unit with its air inlet side facing
the wall.
• To prevent exposure to wind, it is recommended to install a baffle board on the
air outlet side of the outdoor unit.
Units should be installed by licensed contractor accordingly to local code re-
quirement.
Air outlet
2-10 mm × 21 mm slot
Air inlet
285
40
344.5
304 - 325
800
500
150
400
44
Drainage hole (
W
42)
(In case of Heater models
W
33)
69
Drain hose
Drain socket
2
1
Fig. 4-1
4. Drain piping for outdoor unit (Fig. 4-1)
4.1. Accessories
Check the following parts before installation.
<Outdoor unit>
1
Drain socket
1
• Provide drain piping before indoor and outdoor piping connection. (It will be hard
to install drain socket
1
if indoor and outdoor piping connection is conducted
prior to drain piping as outdoor unit becomes immovable.)
• Connect the drain hose
(obtainable at a store, inside diameter: 15 mm) as
shown in the figure for drainage.
• Make sure to provide drain piping with a downhill grade for easy drain flow.
Note:
Do not use the drain socket
1
in the cold region. Drain may freeze and it
makes the fan stop.
SUZ-KA25/KA35VA4
(mm)
■
SUZ-KA50VA4
SUZ-KA60VA4
SUZ-KA71VA4
Drainage hole
(
W
42)
Air inlet
Air outlet
417.5
50
360
500
175
Air inlet
330
40
2-10 mm × 21 mm slot
81
840
(mm)
SUZ-KA25VA4
SUZ-KA35VA4
01_RG79Y534H01_EN.indd 3
2013/06/24 (月) 午前 10:55:25