No. Symptom
Indication
Abnormal point / Con-
dition
Condition
Remedy
LED1(Red) LED2(Yellow)
20
Outdoor unit
operates.
Once
Lit
Primary current protec-
tion
The input current exceeds 8 A (
MXZ-2F33VF,
MXZ-2F33VF2, MXZ-2F33VF3
)/ 10 A (
MXZ-
2F42VF, MXZ-2F42VF2, MXZ-2F42VF3, MXZ-
2F53VF/VFH, MXZ-2F53VF2/VFH2, MXZ-
2F53VF3/VFH3
).
These symptoms do not mean any abnormality of
the product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short
cycled.
Secondary current
protection
The current of the compressor exceeds 17 A.
21
Twice
Lit
High pressure protec-
tion
The indoor gas pipe temperature exceeds 45°C dur-
ing heating.
Defrosting in cooling
The indoor gas pipe temperature falls 3°C or below
during cooling.
22
3 times
Lit
Discharge temperature
protection
The discharge temperature exceeds 100°C during
operation.
• Check the refrigerant circuit and the refrigerant
amount.
• Refer to 12-6. "Check of LEV".
• Refer to 12-6. "Check of outdoor thermistors".
23
4 times
Lit
Low discharge
temperature protection
The frequency of the compressor is kept 68 Hz
(
MXZ-2F33VF, MXZ-2F33VF2, MXZ-2F33VF3
)/80
Hz (
MXZ-2F42VF, MXZ-2F42VF2, MXZ-2F42VF3,
MXZ-2F53VF/VFH, MXZ-2F53VF2/VFH2, MXZ-
2F53VF3/VFH3
) or more and the discharge
temperature is kept under 50°C (COOL mode)/40°C
(HEAT mode) for more than 40 minutes.
• Refer to 12-6. "Check of LEV".
• Check the refrigerant circuit and the refrigerant
amount.
24
5 times
Lit
Cooling high pressure
protection
The outdoor heat exchanger temperature exceeds
58°C during operation.
This symptom does not mean any abnormality of
the product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short
cycled.
25
8 times
Lit
Converter protection
A failure is detected in the operation of the converter
during operation.
• Check the voltage of power supply.
• Replace the inverter P.C. board.
26
Outdoor unit
operates
normally.
9 times
Lit
Inverter check mode The connector of compressor is disconnected.
Inverter check mode starts.
-
27
Lit
Lit
Normal
-
-
NOTE 1. The location of LED is illustrated at the right figure. Refer to 12-7.4.
2. LED is lighted during normal operation.
The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the blinking frequency is “2”.
LED1 LED2
Outdoor display P.C. board (Parts side)
Lit
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
OBH790D
Содержание SEZ-M-DA Series
Страница 42: ...42 WIRING DIAGRAM 7 MXZ 2F33VF E1 ET1 MXZ 2F42VF E1 ET1 MXZ 2F53VF E1 ET1 OBH790D ...
Страница 44: ...44 MXZ 2F33VF2 ET1 MXZ 2F42VF2 ET1 MXZ 2F53VF2 ET1 OBH790D ...
Страница 45: ...45 MXZ 2F33VF3 E1 MXZ 2F42VF3 E1 MXZ 2F53VF3 E1 OBH790D ...
Страница 46: ...46 MXZ 2F33VF3 ET1 MXZ 2F42VF3 ET1 MXZ 2F53VF3 ET1 OBH790D ...
Страница 47: ...47 MXZ 2F53VFH E1 OBH790D ...
Страница 49: ...49 MXZ 2F53VFH3 E1 OBH790D ...
Страница 50: ...50 MXZ 3F54VF E1 ET1 E2 ET2 MXZ 3F68VF E1 ET1 E2 ET2 OBH790D ...
Страница 52: ...52 MXZ 3F54VF2 ET1 MXZ 3F68VF2 ET1 OBH790D ...
Страница 53: ...53 MXZ 3F54VF3 E1 MXZ 3F68VF3 E1 OBH790D ...
Страница 54: ...54 MXZ 3F54VF3 ET1 MXZ 3F68VF3 ET1 OBH790D ...
Страница 55: ...55 MXZ 4F72VF E1 ET1 E2 ET2 OBH790D ...
Страница 57: ...57 MXZ 4F72VF2 ET1 MXZ 4F80VF2 ET1 OBH790D ...
Страница 58: ...58 MXZ 4F72VF3 E1 MXZ 4F80VF3 E1 OBH790D ...
Страница 59: ...59 MXZ 4F72VF3 ET1 MXZ 4F80VF3 ET1 OBH790D ...