14
TROUBLESHOOTING
14
- 10
14.3 When CC-Link IE Controller Network Board did not Operate Normally
14.3.2 Checking on Event Viewer screen
14.3.2 Checking on Event Viewer screen
Check the operation of the board with Windows
®
Event Viewer screen.
Event logs related to the CC-Link IE Controller Network board are displayed as "AMnetg"
or "Mccien" in the Source field on the Event Viewer screen.
(1) For error events
When an error occurs in a driver, the error description is displayed in the System Log
field on the Event Viewer screen.
The following table explains actions for each error message.
POINT
When multiple errors occur, check the chronological order (time of occurrence) on
the Event Viewer screen and handle the errors in the order.
Event ID.
Error message
Corrective action
257(0101
H
)
The I/F board was not found.
Check installed status of the CC-Link IE Controller Network
board.
258(0102
H
)
There is no response from the hardware.
The board may be a failure.
Please consult your local Mitsubishi representative.
259(0103
H
)
Too many boards were detected.
Remove the boards by the number exceeding the allowable
number.
262(0106
H
)
Failed to link the device name.
Reinstall the OS.
264(0108
H
)
Failed to register the interrupt.
Reinstall the OS.
268(010C
H
)
An error occurred during the receive
process.
Check the personal computer program or programmable
controller program which requests processing to the
personal computer.
279(0117
H
)
An error occurred while the registry
database is written.
• Restart the personal computer after installing SW1DNC-
MNETG-B, and confirm that no error occurs.
• Increase the system memory and/or disk capacity.
• When the error has occurred at updating Windows
®
8.1 or
upgrading the operating system with the software package
installed, reinstall the software package.
280(0118
H
)
Own station received the request which
was not processable from another station.
Check the personal computer program or programmable
controller program which requests processing to the
personal computer.
When the communication route contains another station of
the MELSEC iQ-R series, check that "Dynamic Routing" is
set to "Disable".
282(011A
H
)
Failed to map the I/O port.
The I/O port is overlapped with that of another resource.
Remove the other option board.
286(011E
H
)
Failed to allocate memory area for driver
start.
Increase the memory.
287(011F
H
)
No parameter or abnormal data
Set a parameter with the CC IE Control utility and reset the
board.
288(0120
H
)
Driver WDT error occurred.
Refer to Driver WDT error. (Section 14.7.2)