7.3 Online Module Change Procedure
7.3.1 When industrial shipment setting is used and initial setting was made with GX Configurator-DA
7
ONLINE MODULE CHANGE
7.3
Online Module Change Procedure
There are the following online module change procedures depending on whether the user
range setting has been made or not, whether the initial setting of GX Configurator-DA has
been made or not, and whether the other system exists or not.
7.3.1
When industrial shipment setting is used and initial setting was
made with GX Configurator-DA
(1) Conversion disable
(a) Take the following steps to disable the conversion:
1) Set D/A conversion enable/disable setting (Un\G0) to All channel conversion
disable (3F
H
).
2) Turn Operating condition setting request (Y9) from off to on to stop the conver-
sion.
3) Operating condition setting completed flag (X9) turns off from on.
4) Check that the conversion is stopped by seeing the actual analog output value.
5) Turn Operating condition setting request (Y9) from on to off.
Range setting
Initial setting
Other system
Reference section
Industrial shipment setting
GX Configurator-DA
-
Industrial shipment setting
Sequence program
-
User range setting
GX Configurator-DA
Present
User range setting
GX Configurator-DA
Absent
User range setting
Sequence program
Present
User range setting
Sequence program
Absent