6
- 2
6.2 For Use in Normal System Configuration
6
PROGRAMMING
6.2
For Use in Normal System Configuration
(1) System configuration
(2) Conditions for the intelligent function module switch setting
(3) Program conditions
(a) CH1 uses the rate control function (Refer to Section 3.2.4.)
• CH1 Increase digital limit value: 100
• CH1 Decrease digital limit value: 30
(b) CH2 uses the warning output function (Refer to Section 3.2.4.)
• CH2 Warning output upper limit value: 10000
• CH2 Warning output lower limit value: 3000
If a warning is output, the status of Warning output flag (Un\G48) is read and pro-
cessing for the warning output is performed.
(c) If an error occurs in writing a digital value, an error code is displayed in binary
coded decimal (BCD) form.
Error code shall be reset after removing of the cause.
Input range setting
HOLD/CLEAR function setting
Normal resolution mode/ High resolution mode
CH1
4 to 20mA
CLEAR
High resolution mode
CH2
0 to 5V
CH3
to
CH6
not used
-
-
CH1: 4 to 20mA output
QX10 (X/Y10 to X/Y1F)
QY10 (X/Y20 to X/Y2F)
Q66DA-G
(X/Y0 to X/YF)
CH2: 0 to 5V output