9-1. CONTROL SPECIFICATIONS AND FUNCTION SETTING
Mode
Setting
Mode (function) No.
Initial setting
23 (123)
Wired remote controller
(RF thermostat)
11 (111)
Heater
control
1st
1st
1st
Enable heater
basic control
Enable heater
comfort mode
Enable heater
economy mode
2nd
2nd
Heater OFF
Inlet air temp. set temp.
Heater ON
Inlet air temp.< set temp. -4.5
°
F(2.5
°
C)
The fan will stop and the heater will turn off when [DEFROST] or [ERROR]
is displayed.
1
Heater OFF
Inlet air temp.
set temp.
Heater ON
Inlet air temp.< set temp. -1.8
°
F(1
°
C)
The fan will stop and the heater will turn off when [DEFROST] is displayed.
2
1
Heater OFF
Inlet air temp.
set temp.
Heater ON
Inlet air temp.< set temp. -2.7
°
F(1.5
°
C)
The fan will stop and the heater will turn off when [DEFROST] is displayed.
Heater OFF
Inlet air temp.
set temp.-1.8
°
F(1
°
C)
Heater ON
Inlet air temp.< set temp. -3.6
°
F(2
°
C)
The fan will stop and the heater will turn off when [DEFROST] is displayed.
2
2
Inlet air temp.
set temp.-1.8
°
F(1
°
C)
Heater ON
Inlet air temp.< set temp. -4.5
°
F(2.5
°
C)
The fan will stop and the heater will turn off when [DEFROST] is displayed.
·
·
·
·
·
1st: Heater output from CN24-1(yellow) on the indoor unit control board
2nd: Heater output from CN24-2(blue) on the indoor unit control board
*Refer to the Installation Manual for function settings
Table 1 shows how the field-installed heater is controlled. Select the desired pattern in the table below, and set the
Function on the indoor units as shown in Table 1.
Table.1 [Function table]
Select unit numbers 01 to 03 or all units (AL [wired remote controller] / 07 [IR wireless remote controller])
·
·
·