background image

11

G

B

Never connect in reverse phases.
Never connect the Power Line L1, L2, and L3 to Terminal N.

-  If the unit is miss wired, when power is supplied, some electrical parts will 

be damaged.

Install the power cable so that tension is not applied to the cable.

-  Tension may cause the cable to break and generate heat and cause a 

Þ

 re.

Install a leak circuit breaker, as required.

-  If a leak circuit breaker is not installed, electric shock may result.

Use power line cables of suf

Þ

 cient current carrying capacity and rating.

-  Cables that are too small may leak, generate heat, and cause a 

Þ

 re.

Use only a circuit breaker and fuse of the speci

Þ

 ed capacity.

-  A fuse or circuit breaker of a larger capacity, or the use of a substitute 

simple steel or copper wire may result in a general unit failure or 

Þ

 re.

Do not wash the air conditioner units.

-  Washing them may cause an electric shock.

Be careful that the installation base is not damaged by long use.

-  If the damage is left uncorrected, the unit may fall and cause personal 

injury or property damage.

Install the drain piping according to this Installation Manual to ensure 
proper drainage. Wrap thermal insulation around the pipes to prevent 
condensation.

-  Improper drain piping may cause water leakage and damage to furniture 

and other possessions.

Be very careful about transporting the product.

-  One person should not carry the product. Its weight is in excess of 20kg.
-  Some products use PP bands for packaging. Do not use any PP bands as 

a means of transportation. It is dangerous.

-  Do not touch the heat exchanger 

Þ

 ns. Doing so may cut your 

Þ

 ngers.

-  When transporting the outdoor unit, support it at the speci

Þ

 ed positions on 

the unit base. Also support the outdoor unit at four points so that it cannot 
slip sideways. 

Safely dispose of the packing materials.

-  Packing materials, such as nails and other metal or wooden parts, may 

cause stabs or other injuries.

-  Tear apart and throw away plastic packaging bags so that children will not 

play with them. If children play with a plastic bag which has not been torn 
apart, they face the risk of suffocation.

1.5.  Before starting the test run

 Caution:

Turn on the power at least 12 hours before starting operation.

-  Starting operation immediately after turning on the main power switch 

can result in irreversible damage to internal parts. Keep the power switch 
turned on during the operational season. Make sure of the phase order of 
power supply and voltage between each phase.

Do not touch the switches with wet 

Þ

 ngers.

-  Touching a switch with wet 

Þ

 ngers can result in an electric shock.

Do not touch the refrigerant pipes during and immediately after 
operation.

-  During and immediately after operation, the refrigerant pipes may be hot 

or cold, depending on the condition of the refrigerant 

ß

 owing through the 

refrigerant piping, compressor, and other refrigerant cycle parts. Your 
hands may suffer burns or frostbite if you touch the refrigerant pipes.

Do not operate the air conditioner with the panels and guards removed.

-  Rotating, hot, or high-voltage parts can cause injuries.

Do not turn off the power immediately after stopping operation.

-  Always wait at least 5 minutes before turning off the power. Otherwise, 

drainage water leakage or mechanical failure of sensitive parts may occur.

Do not touch the surface of the compressor during servicing.

-  If unit is connected to a supply and not running, the crank case heater 

located at the base of the compressor may still be operating.

Use refrigerant piping made of phosphorus deoxidized copper and 
copper alloy seamless pipes and tubes. In addition, be sure that the 
inner and outer surfaces of the pipes are clean and free of hazardous 
sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other 
contaminant.

-  Contaminants on the inside of the refrigerant piping may cause the 

refrigerant oil to deteriorate.

Store the piping to be used during installation indoors and keep both 
ends of the piping sealed until just before brazing. (Store elbows and 
other joints in a plastic bag.)

-  If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and 

compressor failure may result.

Apply a small amount of ester oil, ether oil, or alkyl benzene to 

ß

 ares. 

(for indoor unit)

-  In

Þ

 ltration of a large amount of mineral oil may cause the refrigerant oil to 

deteriorate.

Use liquid refrigerant to 

Þ

 ll the system.

-  If gas refrigerant is used to 

Þ

 ll the system,  the composition of the 

refrigerant in the cylinder will change and performance may drop.

Do not use a refrigerant other than R410A.

-  If another refrigerant (R22, etc.) is mixed with R410A, the chlorine in the 

refrigerant may cause the refrigerant oil to deteriorate.

Use a vacuum pump with a reverse 

ß

 ow check valve.

-  The vacuum pump oil may 

ß

 ow back into the refrigerant cycle and cause 

the refrigerant oil to deteriorate.

Do not use the following tools that are used with conventional 
refrigerants.
(Gauge manifold, charge hose, gas leak detector, reverse 

ß

 ow check 

valve, refrigerant charge base, refrigerant recovery equipment)

-  If the conventional refrigerant and refrigerant oil are mixed in the R410A, 

the refrigerant may deteriorate.

-  If water is mixed in the R410A, the refrigerant oil may deteriorate.
-  Since R410A does not contain any chlorine, gas leak detectors for 

conventional refrigerants will not react to it.

Do not use a charging cylinder.

-  Using a charging cylinder may cause the refrigerant to deteriorate.

Be especially careful when managing the tools.

-  If dust, dirt, or water gets into the refrigerant cycle, the refrigerant may 

deteriorate.

1.3.  Before installation

 Caution:

Do not install the unit where combustible gas may leak.

-  If the gas leaks and accumulates around the unit, an explosion may result.

Do not use the air conditioner where food, pets, plants, precision 
instruments, or artwork are kept.

-  The quality of the food, etc. may deteriorate.

Do not use the air conditioner in special environments.

-  Oil, steam, sulfuric smoke, etc. can signi

Þ

 cantly reduce the performance of 

the air conditioner or damage its parts.

When installing the unit in a hospital, communication station, or similar 
place,  provide suf

Þ

 cient protection against noise.

-  Inverter equipment, private power generator, high-frequency medical 

equipment, or radio communication equipment may cause the air 
conditioner to operate erroneously, or fail to operate. On the other hand, 
the air conditioner may affect such equipment by creating noise that 
disturbs medical treatment or image broadcasting.

Do not install the unit on or over things that are subject to water 
damage.

-  When the room humidity exceeds 80% or when the drain pipe is clogged, 

condensation may drip from the indoor unit. Perform collective drainage 
work together with the outdoor unit, as required.

1.4.  Before installation (relocation) - 

electrical work

 Caution:

Ground the unit.

-  Do not connect the ground wire to gas or water pipes, lightning rods, or 

telephone ground lines. Improper grounding may result in electric shock.

2.  About the product

This unit uses R410A-type refrigerant.

Piping for systems using R410A may be different from that for systems using 
conventional refrigerant because the design pressure in systems using 
R410A is higher. Refer to the Data Book for more information.

Some of the tools and equipment used for installation with systems that use 
other types of refrigerant cannot be used with the systems using R410A. 
Refer to the Data Book for more information.

Do not use the existing piping, as it contains chlorine, which is found in 
conventional refrigerating machine oil and refrigerant. This chlorine will 
deteriorate the refrigerant machine oil in the new equipment. The existing 
piping must not be used as the design pressure in systems using R410A 
is higher than that in the systems using other types of refrigerant and the 
existing pipes may burst. 

 Caution:

Do not vent R410A into the atmosphere.
R410A is a Fluorinated Greenhouse gas, covered by the Kyoto Protocol 
with a Global Warming Potential (GWP) = 1975.


Содержание PURY-EP-YHM-A

Страница 1: ...ALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação a...

Страница 2: ...guide Procured at the site A Front B Must be open C Wall height H 15 15 450 300 A A 100 450 50 50 A A A B B 500 H h h H 240 45 A D C 50 C 1000 30 450 300 C B B C A 100 450 100 B B C C A 450 100 C C B A A A B 450 450 15 C A A A 450 450 900 300 300 B B C C A 1000 900 300 B B C A mm Fig 7 0 1 1 P200 P300 EP200 7 2 P350 P400 EP250 EP300 8m 8m 40 8m 40 8m ...

Страница 3: ...30mm A B C A Fig 8 1 2 A Screws 30mm A D B C D B With detachable leg 9 9 2 Fig 9 2 1 P200 P400 EP200 EP300 P450 P800 EP400 EP600 a C b B c d f D E A e A1 unit1 unit2 A2 A G C E E E D E D E F A NOTE1 B A a b c d A B C E F E E Note1 E B C D g i j h A Outdoor unit B BC controller standard C BC controller main D BC controller sub E Indoor unit 15 80 F Indoor unit 100 250 G Outdoor twinning kit ...

Страница 4: ...el P450 P650 EP400 EP600 P700 P800 Outdoor twinning kit CMY R100VBK CMY R200VBK Å Outdoor model P200 P250 P300 P350 P400 P450 P500 P550 P600 P650 P700 P750 P800 EP200 EP250 EP300 EP400 EP450 EP500 EP550 EP600 ı High pressure side ø15 88 ø19 05 ø19 05 ø19 05 ø22 2 ø22 2 ø22 2 ø28 58 ø28 58 ø28 58 ø28 58 ø28 58 ø28 58 ø15 88 ø19 05 ø19 05 ø22 2 ø22 2 ø22 2 ø28 58 ø28 58 Ç Low pressure side ø19 05 ø2...

Страница 5: ... I A Downward slope B Upward slope C BC controller standard or main D Twinning pipe E Slope of the twinning pipe is at an angle within 15 to the ground F Twinning pipe low pressure side G Twinning pipe high pressure side H On site piping low pressure connecting pipe between outdoor units I On site piping low pressure main pipe to BC controller J On site piping high pressure main pipe to BC control...

Страница 6: ...fer to the instructions included in the kit 2 Connection pipe is not used when the Twinning kit is attached 3 Use a pipe cutter to sever When not attaching a low pressure twinning pipe Fig 10 2 2 ø22 2 ID ø25 4 ID ø22 2 OD ø19 05 ø22 2 ID ø25 4 ID ø28 58 ø28 58 ID ø25 4 ID ø19 05 OD ø19 05 F E C D D A B G H I F C D A Front pipe routing B When not attaching a low pressure twinning pipe CWhen attach...

Страница 7: ... B A B A Inner wall concealed A B D C B Outer wall A Steel wire B Piping C Asphaltic oily mastic or asphalt D Heat insulation material A E Outer covering B A High pressure pipe B Low pressure pipe C Electric wire D Finishing tape E Insulator D F G B D Floor waterproofing E A B C Outer wall exposed F H D B G E Roof pipe shaft I A J 1m 1m F Penetrating portion on fire limit and boundary wall A Sleev...

Страница 8: ...03 RC 155 M1M2 M1M2 S TB7 TB3 CN41 53 OC r3 A B S System controller L3 L 6 L4 L 5 r 2 r 4 r 1 A B A B A B A B BC M1M2S 52 BS M1M2S 55 BC M1M2S 54 TB02 TB02 TB02 OC CN41 CN41 CN40 A Cable strap B Power source cable C Transmission cable 1 When the power supply unit is not connected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE outdoor unit ...

Страница 9: ...N41 B SW2 1 ON 2 Fig 11 3 3 RC IC BC M1M2 S TB5 IC M1M2 S TB5 RP Ground A B A B A B S TB2 A B S TB3 L 15 r 1 r 1 L 18 RC IC M1M2 S TB5 IC M1M2 S TB5 L17 L16 L14 L13 M1M2 S M1 M2 TB3 M1 M2 TB3 M1M2 S TB7 M1M2 S TB7 OC 51 L11 L12 OS 52 CN41 CN41 TB02 Fig 11 4 1 A Switch Breakers for wiring and current leakage B Breakers for current leakage C Outdoor unit D Pull box E Indoor unit F BC controller stan...

Страница 10: ...efrigerant different from the refrigerant speciÞed on the unit If a different refrigerant or air is mixed with the original refrigerant the refrigerant cycle may malfunction and the unit may be damaged If the air conditioner is installed in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety limit if the refrigerant should leak Consult the dealer ...

Страница 11: ... installation indoors and keep both ends of the piping sealed until just before brazing Store elbows and other joints in a plastic bag If dust dirt or water enters the refrigerant cycle deterioration of the oil and compressor failure may result Apply a small amount of ester oil ether oil or alkyl benzene to ßares for indoor unit InÞltration of a large amount of mineral oil may cause the refrigeran...

Страница 12: ...ing mode 5 CDB 43 CDB Heating mode 20 CWB 15 5 CWB Fresh air intake type Cooling mode 21 CDB 43 CDB Heating mode 12 5 CWB 20 CWB Model PURY P550YSHM A PURY P600YSHM A PURY P650YSHM A PURY P700YSHM A PURY P750YSHM A PURY P800YSHM A Noise level 50 60Hz 61dB A 62dB A 62 5dB A 63dB A 63 5dB A 64dB A External static pressure 0 Pa 2 Indoor units Total capacity 50 150 1 Model 15 250 Quantity 2 50 2 50 2 ...

Страница 13: ... refer to item 10 2 1 Connecting pipe ID ø25 4 ID ø22 2 Low pressure side High pressure side 2 Connecting pipe ID ø25 4 OD ø19 05 High pressure side 3 Connecting pipe ID ø25 4 ID ø28 58 Low pressure side 4 Connecting elbow ID ø19 05 OD ø19 05 High pressure side Model P250 1 pc EP250 1 pc 1 pc 1 pc P300 1 pc EP300 1 pc 1 pc 1 pc P350 1 pc 1 pc 1 pc P400 1 pc 1 pc 8 1 Installation Fig 8 1 1 P 3 A Wi...

Страница 14: ...e unit to make an emergency stop Charge the system with an appropriate amount of refrigerant When servicing always check the notes concerning pipe length and amount of additional refrigerant at both locations the refrigerant volume calculation table on the back of the service panel and the additional refrigerant section on the labels for the combined number of indoor units Refer to item 9 2 for de...

Страница 15: ...clude the amount needed for extended piping and additional charging of each refrigerant line will be required on site In order that future servicing may be properly provided always keep a record of the size and length of each refrigerant line and the amount of additional charge by writing it in the space provided on the outdoor unit 10 1 Calculation of additional refrigerant charge Calculate the a...

Страница 16: ...age Take the following steps 1 through 4 to remove the pinched connecting pipe before connecting refrigerant pipes to the outdoor unit 1 Check that the refrigerant service valve is fully closed turned clockwise all the way 2 Connect a charging hose to the service port on the low pressure high pressure refrigerant service valve and extract the gas in the pipe section between the refrigerant service...

Страница 17: ... vacuum pump and leave it for 1 hour Ensure the degree of vacuum has not increased If the degree of vacuum increase is larger than 130 Pa water might have entered Apply pressure to dry nitrogen gas up to 0 05 MPa and vacuum again Finally seal in with the liquid refrigerant through the high pressure pipe and adjust the low pressure piping to obtain an appropriate amount of the refrigerant during op...

Страница 18: ...ground to the grounding terminal In the case of transmission lines for centralized control connect it to the shield terminal S on the terminal block for centralized control TB7 Furthermore in the case of the outdoor units whose power supply connector CN41 is replaced with CN40 short circuit the shield terminal S and the grounding terminal in addition to the above 5 Fix the connected wires securely...

Страница 19: ...onnected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE outdoor unit in the system and connect it to CN40 2 If a system controller is used set SW2 1 on all of the outdoor units to ON Fig 11 3 2 MA Remote Controller P 9 A Change the jumper connector from CN41 to CN40 B SW2 1 ON C Keep the jumper connector on CN41 A Group 1 B Group 3 C Group...

Страница 20: ...ler cable length m1 m2 and m1 m2 m3 m4 200 m 0 3 to 1 25 mm2 3 Transmission booster Fig 11 3 3 P 9 Max transmission cable length M NET cable 1 L11 L12 L13 L14 L16 L17 200 m 1 25 mm2 2 L11 L12 L13 L14 L16 L18 200 m 1 25 mm2 3 L11 L12 L13 L15 200 m 1 25 mm2 4 L17 L16 L14 L15 L15 L14 L16 L18 200 m 1 25 mm2 Remote controller cable length 1 2 10 m 0 3 to 1 25 mm2 If the length exceeds 10 m use 1 25 mm2...

Страница 21: ...r piping temperature at thermostat ON Fan stops during heating operation Defrost display The fan is set to stop during defrosting Fan does not stop while operation has been stopped No lighting The fan is set to run for 1 minute after stopping to exhaust residual heat only in heating No setting of fan while start SW has been turned on Heat ready Ultra low speed operation for 5 minutes after SW ON o...

Страница 22: ...odel EP400 EP450 EP500 Unit combination EP200 EP200 EP250 EP200 EP300 EP200 Refrigerant R410A 10 5kg 10 5kg 11 8kg 10 5kg 11 8kg 10 5kg Allowable pressure Ps HP 4 15 MPa LP 2 21 MPa Net weight 235kg 235kg 265kg 235kg 265kg 235kg Model EP550 EP600 Unit combination EP300 EP250 EP300 EP300 Refrigerant R410A 11 8kg 11 8kg 11 8kg 11 8kg Allowable pressure Ps HP 4 15 MPa LP 2 21 MPa Net weight 265kg 265...

Страница 23: ...e number on this manual before handing it to the customer This product is designed and intended for use in the residential commer cial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Pressure Equipment Directive 97 23 EC ...

Отзывы: