background image

 

Job Name:

 

Drawing Reference:

Schedule No.

 

System No.:

Notes:

OUTDOOR VRF SYSTEM SPECIFICATIONS
Capacity

Cooling……………………………………………..48,000 Btu/h

Heating……………………………………………..54,000 Btu/h

Power

Power Source……………….........208 / 230V, 1-phase, 60Hz

Power Input

  Cooling………………………………………………4.97 kW

  Heating………………………………………………4.88 kW

Current

  Cooling (208 / 230)........................................24.0 / 21.7 A

  Heating (208 / 230) ...................................…23.6 / 21.3 A

Minimum Circuit Ampacity (MCA) (208 / 230)….……..…26 A

Breaker Size for Wiring ........................................….......30 A

………Pre-coated Galvanized-steel Sheets

External Finish

Munsell No. 3Y 7.8 / 1.1

External Dimensions

Inches………………..53-3/16 h x 37-7/16 w x 13 (+1-3/16) d

mm……………………………..1,350 h x 950 w x 330 (+30) d

Net Weight

………………………………….287 lbs. / 130 kg

Fan

Type x Quantity...………...........................…Propeller Fan x 2

Airflow Rate……………………………………...…….3,530 cfm

Motor Output……...…..……………………….0.086 + 0.086 kW

Compressor

Type………………...................………….Inverter-driven Scroll

Motor Output………..…………………………………….2.4 kW

Lubricant

………………..…...………………………….FV50S

Refrigerant

……………..…...…………………………..R410A

Protection Devices

High Pressure Protection………………High Pressure Switch

Compressor…………Discharge Thermo / Overcurrent Detection

Fan…...…………………………..Overheat / Voltage Protection

Piping Diameter

Liquid (High Pressure)………..……………3/8" / 9.52 mm Flare

Gas (Low Pressure)………………………5/8" / 15.88 mm Flare 

Indoor Unit

Total Capacity…..…….50% –130% of Outdoor Unit Capacity

Model / Quantity…………………..…………..….P06-P54 / 1 ~ 8

Sound Level (Cooling / Heating)

………….50 / 52 dB(A) 

Operating Temperature Range

Cooling (Outdoor)……………….23°F ~ 115°F (-5 ° ~ +46°C) DB*

Heating (Outdoor)…………….0°F ~ +60°F (-18 ° ~ +15°C) WB

Anti-corrosion Protection

 

Blue Fin Treatment

 applied to condenser coil protects coil 

from airborne contaminants. 

Options

□ Branch Joint (T-Branch)…………………..…....CMY-Y62-G-E

□ Header - Four-Branch…………………………….CMY-Y64-G-E

□ Header - Eight-Branch……………………………..CMY-Y68-G-E

□ Drain Pan………………………………….….….PAC-SG64DP-E

□ Drain Socket………………………………….….PAC-SG61DS-E

 

Model:

 PUMY-P48NHMU

UTDOOR

O

 VRF  

E

E

EM

Y

S ST

 F ATUR S

 Single-phase outdoor unit 

   with variable refrigerant  

   technology

• Inverter-driven (variable 

   speed) compressor

• Total refrigerant piping 

   length of 394' (120 m)

• Uses CITY MULTI indoor  

   units and Controls Network