66
Active filter module
PUMY-P100VHM
PUMY-P125VHM
PUMY-P140VHM
L1, L2
Connect to the DCL(Reactor)
Connect to the 52C
Connect to
the outdoor
power circuit
board(TABN1)
+
–
I
Not used
N2
Connect to
the outdoor
power circuit
board(TABN2)
N1
Non-connect
P
Connect to the out-
door power circuit
board(TABP2)
DCL
L1
L2
ACTM
P
I
N1
N2
(+)
(- )
Load
+
Connection and internal circuit diagram
Connect to the out-
door power circuit
board(CNAF)
1
: GND
2
-
1
: 15V DC
3
-
1
: Control signal
4
,
5
: Not used
6
-
1
: Control signal
Error condition Normal value (reference)
Symptom when the unit is in trouble
(–) and N1 / N2 / I
open
less than 1
"
1
The unit does not operate (can not be switched ON)
(–) and L2
short
100k
"
~ 1M
"
1
The breaker operates
open
W
1
The unit does not operate (can not be switched ON)
2
4220 Abnormal stop (9-10. No.189 "ACTM error" display)
P and L2
short
100k
"
~ 1M
"
1
The breaker operates
open
W
1
The unit does not operate (can not be switched ON)
2
4220 Abnormal stop (9-10. No.189 "ACTM error" display)
P and N1 / N2 / I
short
100k
"
~ 1M
"
1
The breaker operates
open
W
1
The unit does not operate (can not be switched ON)
2
4220 Abnormal stop (9-10. No.189 "ACTM error" display)
L2 and N1 / N2 / I
short
100k
"
~ 1M
"
1
The breaker operates
open
W
1
The unit does not operate (can not be switched ON)
2
4220 Abnormal stop (9-10. No.189 "ACTM error" display)
Tester check points of Acive
fi
lter module
W
The symptom when the unit is in open error condition is described to determine open error by tester check.