33
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
Plate HEX liquid pipe temperature (TH6)
– 39~88
:
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Water inlet temperature (TH32)
0~100
1
ON
2 3 4 5 6
Condensing temperature (T
63HS
)
– 39~88
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
:
0~150
(When it is 100 Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 105 Hz;
0.5 secs. 0.5 secs. 2 secs.
Hz
:
0~100
Calculated maximum frequency
0~150
1
05
1
ON
2 3 4 5 6
:
Ambient temperature (TH7)
-39~88
-39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
1
ON
2 3 4 5 6
Outdoor heatsink temperature (TH8)
-40~200
:
-40~200
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
(When the thermistor detects 100
:
or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
1
ON
2 3 4 5 6
°C
Discharge superheat (SHd)
0~255
Cooling and Heating: SHd = TH4-T
63HS
0~255
(When the SHd is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
°C
Sub cool (SC)
0~130
Cooling: SC = T
63HS
-TH3
Heating: SC = T
63HS
-TH6
0~130
(When the SC is 100°C or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
1
ON
2 3 4 5 6
0.1 A
Input current of outdoor unit
0~500
0~500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
1
ON
2 3 4 5 6
Содержание PUHZ-W85VHA