Installing the Outdoor Unit
Installing the Outdoor Unit (boiler)
Position the outdoor unit so that the air flows into an open area,
where there are no plants and animals
Install the outdoor unit on a flat, stable surface, the unit needs to
be securely mounted at least 100mm off the ground on rubber feet.
The unit must be bolted down for security using 10mm bolts and
Zebedee’s.
The space around the unit is very important, allow:
300mm to the left-hand side (facing the front of the unit), 600mm to
the right of the unit, you can mount the unit with only 150mm to the
rear and 1500mm to the front of the unit.
The connections on the back of the units are inch male thread
The unit must have adequate drainage away from the unit; it can
produce up to 6 L / hour of condensate. If you are installing the unit
at height you can install a drain pan under the unit but its best to let
the unit drain into the ground. The unit has an optional extra (not
with the unit) drain fitting available called PAC-SG61DSE
Monobloc Dimensions
Models
A (mm)
B (mm)
C (mm)
50
740
850
175
85
943
950
175
112
1350
1020
210
140
1350
1020
210
300 or more
300 or more
1500 or more
600 or more
B
330
+ 3
0
A
C
600
370
Flow from HP
Boiler Flow
Return to HP
Boiler Return
Heating Return
Heating Flow
G3 kit already installed.
It comes with a white
expansion vessel in the kit
Hot water pump and plate
hex. The cylinder has no coil
inside, the potable water is
pumped through the plate by
this pump. There is also a
de-scaler in line.
Primary pump
pumps water to the
outdoor unit and back
Drain Pipe
Extruded Portion
Drain Boss
Rubber Cap
Drain hole of Base