–33–
Communication de-
mand capacity
0 - 255
Abnormal thermistor
display
1 - 3, –
FAN output at abnor-
mal stop
0 - 100
LEV opening angle (/5)
at abnormal stop
0 - 400
Outdoor Condenser/
evaporater temp tem-
perature at abnormal
stop
–39 - 88
Discharge super heat
SHd at abnormal stop
0 - 216
Cooling: Outdoor TH2-
Outdoor TH3
Heating: Outdoor TH2-
Indoor TH3
(average)
Sub cool Sc at abnor-
mal stop
0 - 130
Cooling: Outdoor TH3-
Outdoor TH1
Heating: Indoor TH3
(average) -In-
door TH2 (av-
erage)
0 - 255
When communication demand not set: 100 %
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 100,
every other second
1
←→
100
1 - 3, –
1: Outdoor liquid temp thermistor (TH1)
2: Outdoor discharge temp thermistor (TH2)
3: Outdoor condenser/evaporater temp thermistor (TH3)
–: No abnormal thermistor
0 - 100
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 100,
every other second
–
←→
00
0 - 400
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 200,
every other second
2
←→
00
–39 - 88
(When 0
°
C or lower, “–”and temperature are displayed
alternately.)
<Example> When –10,
every other second
–
←→
–10
0 - 216
(When 100
°
C or higher, 100s digit and 10s and units
digits are displayed alternately.)
<Example> When 150,
every other second
–
←→
50
0 - 130
(When 100
°
C or higher, 100s digit and 10s and units
digits are displayed alternately.)
<Example> When 100,
every other second
1
←→
00
%
–
%
5 pulses
°
C
°
C
°
C
SW2 setting
Display contents
Description of display
Unit
OFF
ON
1 2 3 4 5 6
OFF
ON
1 2 3 4 5 6
OFF
ON
1 2 3 4 5 6
OFF
ON
1 2 3 4 5 6
OFF
ON
1 2 3 4 5 6
OFF
ON
1 2 3 4 5 6
OFF
ON
1 2 3 4 5 6