![Mitsubishi Electric PLFY Series Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/mitsubishi-electric/plfy-series/plfy-series_technical-and-service-manual_1811100018.webp)
18
5
4-WAY AIR FLOW SYSTEM
5-1. PLACEMENT OF THE AIR OUTLETS
• For this grille, the blowout direction comes in 11 patterns.
Also, by setting the remote controller to the appropriate settings, you can adjust the airflow and speed. Select the settings
from Table1 according to the location in which you want to install the unit.
1) Decide on the pattern of the airflow direction.
Blowout direction
pattern
4-direction
<Table 1>
3-direction
2-direction
Note1.
For 3 and 2-direction
settings, please use
the air outlet shutter
plate (option).
Pattern 1 Initial setting
Pattern 4 1 air outlet
fully closed
Pattern 6 2 air outlet
fully closed
Silent
2.5m
2.7m
3.0m
Standard
2.7m
3.0m
3.3m
High ceiling
3.5m
3.5m
3.5m
4 direction
3 direction
2 direction
SWA
SWB
PLFY-P32/40/50/63/80VBM-E.UK
PLFY-P32/40/50/63/80VBM-E
1
.UK
PLFY-P32/40/50/63/80VBM-ER2.UK
PLFY-P32/40/50/63/80VBM-ER3.UK
PLFY-P100/125VBM-E.UK
PLFY-P100/125VBM-ER2.UK
PLFY-P100/125VBM-ER3.UK
Silent
2.7m
3.0m
3.3m
Standard
3.2m
3.6m
4.0m
High ceiling
4.5m
4.5m
4.5m
4 direction
3 direction
2 direction
SWA
SWB
2) According to the number of air outlets and height of the ceiling to install the unit, be sure to set up the switches
(SWA, SWB) on the circuit board to the appropriate setting.
• Correspondence of ceiling heights to numbers of air outlets
SW14
SW11
SW12
1 2 3 4 5 6 7 8 9 10
ON
OFF
SW1
SWC
CN82
CN43
3
2
SWA
1
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
0 1 2
3
4
5
6
78
9A
B
C
D
E
F
(10ths DIGIT)
(1s DIGIT)
. /
.
(BRANCH No.)
2
3
SWB
4
OCH413D