24
<How to operate>
1
Press POWER ON/OFF button.
2
Press the operation MODE button to display DRY.
3
Press the TEMP. button to set the set temperature.
NOTE
: The set temperature changes 1°F when the or
button is pressed one time. Dry 67 to 87°F
<How to operate>
1
Press button.
2
Press [F1] button to display DRY.
3
Press [F2] [F3] button to set the set temperature.
8-2. DRY OPERATION
Control Mode
Control Details
Remarks
1. Temperature
adjustment
function
1-1. Determining temperature adjustment function
(Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermostat signal and the room temperature (TH21).
Dry thermo-ON Room temperature
]
Set tempe 2°F
Dry thermo-OFF Room temperature
[
Set temperature
Room temperature
3 minutes passed since
starting operation
Dry thermo-
ON time
(min)
Dry thermo-
OFF time
(min)
Thermostat signal Room temperature (T1)
Over 64°F
ON
T1
]
83°F
9
3
83°F > T1
]
79°F
7
3
79°F > T1
]
75°F
5
3
75°F > T1
3
3
OFF
Unconditional
3
10
Below 64°F
Dry thermo OFF
1-2. Anti-freeze prevention control
No control function
2. Fan
Indoor fan operation controlled depends on the compressor conditions.
Dry thermo
Fan speed notch
ON
[Low]
OFF
Excluding the following
Stop
Room temp. < 64°F
[Low]
Note: Fan speed change is not allowed during DRY operation.
3. Drain pump
Operates as it would in COOLING operation.
4. Vane
(up/down vane
change)
Settings are the same in DRY operation as they are in COOL operation.
F2
F3
F4
F1
.
OCH611D