![Mitsubishi Electric PLA-P1.6KA Скачать руководство пользователя страница 41](http://html.mh-extra.com/html/mitsubishi-electric/pla-p1-6ka/pla-p1-6ka_technical-and-service-manual_1811076041.webp)
41
Total
Electrical circuit
Refrigerant circuit
Indoor side
Outdoor
side
Service Ref.
SHF
BF
W
kW
V
A
V
A
MPa
MPa
°
C
°
C
°
C
m
°
C
°
C
°
C
°
C
°
C
Mode
Capacity
Input
Indoor unit Service Ref.
Phase,Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase,Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
1,50
240
1/3 , 50
240/415
1,50
240
1/3 , 50
240/415
1,50
240
1/3 , 50
240/415
Cooling
4,400
1.82
0.64
7.36 / 2.49
2.13
0.50
87.1
48.3
12
5
27
19
16.3
35
24
0.80
0.26
Cooling
5,300
2.44
0.65
10.26 / 3.70
2.41
0.50
87.8
53.4
4.5
5
27
19
15.0
35
24
0.74
0.22
Cooling
6,300
2.63
0.61
11.90 / 4.48
2.08
0.50
77.5
48.5
6.3
5
27
19
13.5
35
24
0.75
0.12
(21.2)
(5.1)
(24.6)
(5.1)
(21.7)
(5.1)
(kgf/
F
)
(kgf/
F
)
D.B.
W.B.
D.B.
D.B.
W.B.
PLA-P1.6KA.UK
PLA-P1.6KA
1
.UK
PLA-P2KA.UK
PLA-P2KA
1
.UK
PLA-P2.5KA.UK
PLA-P2.5KA
1
.UK
PLA-P1.6KA.UK
PLA-P1.6KA
1
.UK
PLA-P2KA.UK
PLA-P2KA
1
.UK
PLA-P2.5KA.UK
PLA-P2.5KA
1
.UK
PU-P1.6VGAA.UK
PU-P1.6YGAA.UK
PU-P2VGAA.UK
PU-P2YGAA.UK
PU-P2.5VGAA.UK
PU-P2.5YGAA.UK
4.2. Cooling only type(2)
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/
f
f
)
Standard
High
ceiling
Air flow
Air speed
Coverage range
Air flow
Air speed
Coverage range
m
3
/min
m/sec.
m
m
3
/min
m/sec.
m
16.0
5.6
6.0
17.0
5.9
6.4
PLA-P1.6KA.UK
PLA-P1.6KA
1
.UK
16.0
5.6
6.0
17.0
5.9
6.4
PLA-P2KA.UK
PLA-P2KA
1
.UK
PLA-P2.5KA.UK
PLA-P2.5KA
1
.UK
17.0
5.9
6.4
18.0
6.3
6.8
5. OUTLET AIR SPEED AND COVERAGE RANGE
w
The air coverage range is the value up to the position where the air speed is 0.25m/sec.
When air is blown out horizontally from the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the
furniture inside the room.
OC240-B--2.qxp 04.9.29 3:31 PM Page 41