8
< Process for setting >
[1] To turn off air conditioner and change the remote
controller to "Fixed airfl ow direction mode"
1.Press ON/OFF button to turn off the air conditioner.
2.Press Fan Speed button and Filter button for more than 2
seconds simultaneously and it becomes the fi xed airfl ow direction
mode after a while.
2.Press Filter
button to send the information on remote controller.
3. Wait for 15 seconds . How does the air conditioner run?
Only the air from the selected outlet blows downward.
Go to step[3].
Air from the wrong outlet blows downward.
Repeat 1 and set again.
All outlets are closed.
The numbers of the air conditioner (refrigerant address No.,
Unit No.) are wrong. Refer to How to fi nd air conditioner No..
[3] To fi x air direction
1.Press Mode button (Return button) to blink Up/Down air direction
indicater.
2.Press Set Temperature button until the direction to set is chosen.
3.Press Filter button to send the information on remote controller to
air conditioner.
4.Wait for 15 seconds . How does the air conditioner run?
Airfl ow direction is set in the selected direction.
The fi xed setting completed (Go to step [4].)
Airfl ow direction is set in the wrong direction.
Repeat 2. and set again.
[4] To cancel "Fixed airfl ow direction mode"
1.Press ON/OFF button to cancel "Fixed airfl ow direction mode".
It is also canceled by pressing Fan Speed button and Filter button
for more than 2 seconds simultaneously.
2.Do not operate remote controller for 30 seconds after the "Fixed airfl ow
direction mode" is canceled. It does not accept even if it is operated.
Air blows downward after it becomes
"fixed airflow direction mode"
"Fixed airflow direction mode" display
Note: "0" indicates
all outlets.
Outlet No.
Unit No.
Up/Down air direction Refrigerant addres No.
MITSUBISHI
ELECTRIC
label
Outlet No.4
Outlet No.2
Outlet No.3
Outlet No.1
Air direction changes
This indicates NO FIXED SETTING(canceled)
Up/Down air direction
Unit No.
Outlet No.
Refrigerant addres No.
[2] To select and identify the outlet to set
1.Press Set Temperature button to change number with the outlet No.
blinking. Select outlet No. to set.
5. Operation