6. Electrical work
6.1. Electric wiring
[Fig. 6-1]
Connection can be made without removing the front panel.
1. Open the front grille, remove the screw (2 pieces), and remove the electrical
parts cover.
* Electrical work can be conducted more effectively with the panel removed.
When attaching the panel, check that the hooks
M
at three locations on the air
outlet side are connected securely.
2. Securely connect each wire to the terminal block.
* In consideration of servicing, provide extra length for each of the wires.
* Take care when using strand wires, because beards may cause the wiring to
short out.
3. Install the parts that were removed back to their original condition.
4. Fasten each of the wires with the clamp under the electrical parts box.
A
Electrical box cover
B
Fixing screw
C
Clamp
D
Ground wire connection portion
E
MA remote control terminal block: (1, 2) do not have polarity
F
Transmission terminal block: (M1, M2, S) do not have polarity
G
Power supply terminal block (L, N, ).
H
Terminal screw
I
Ground wire connection portion: Connect the ground wire in the direction illustrated in the
diagram.
J
Remote control cable
K
Transmission cable
L
Power supply cable
M
Hook
N
Band
Caution:
Wiring for remote controller cable shall be apart (5 cm or more) from power
source wiring so that it is not influenced by electric noise from power source
wiring.
6.2. Power supply wiring
• Wiring size must comply with the applicable local and national codes.
• Power supply cable of appliance shall not be lighter than design 60245 IEC 53 or
60227 IEC57, 60245 IEC 53 or 60227 IEC 53.
• Install a ground wire longer than other cables.
• A switch with at least 3 mm, 1/8 inch contact separation in each pole shall be
provided by the air conditioner installation.
[Fig. 6-2]
A
Ground-fault interrupter
B
Local switch/Wiring breaker
C
Indoor unit
D
Pull box
Warning:
Never splice the power cable or the indoor-outdoor connection cable,
otherwise it may result in a smoke, a fire or communication failure.
JKL
C
N
L
K
J
D
G
F
E
A
B
B
L
E
F
I
G
M
Secure with a band
N
at the location shown
in the diagram
Fig. 6-1
Indoor unit side
55 mm
12 mm
~220-240V
~220-240V
RH79A016H01_en.indd 12