background image

11

WIRING DIAGRAM

5

1 2

to the connector       . (Remote controller wire is non-polar.)

TB5

TB2

N

L

TO NEXT 
INDOOR UNIT

PULL 
BOX

FUSE
(15A)

~/N 220V 60Hz

~/N 220-230-240V 50Hz

BREAKER

  (15A)

POWER SUPPLY

GRN/YL

W

ORN

ORN

PKFY-P20VAM

Models

OFF

ON

Models

SW2

<

w

1>

SW2

PKFY-P25VAM

4

3

2

1

4

3

2

1

OFF

ON

Mark

LED1

LED2

Meaning

Main power supply

Function

Power supply for

MA-Remote controller

LED on indoor board for service

Main power supply(Indoor unit:220-240V)

power on      lamp is lit

Power supply for MA-Remote controller

on      lamp is lit

3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)

In case of connecting MA-remote controller, please connect MA remote controller cable in an accessorie

2.

CN35P

MICON
BOARD

(BLU)

CN53P

MICON
BOARD

(RED)

(BLU)

(RED)

POWER BOARD

POWER BOARD

CN53M

CN35M

CN43

ADDRESS

(RED)

(RED)

ADDRESS

CN82

SW5

220V

240V

3RD
DIGIT

2ND
DIGIT

1ST
DIGIT

CONNECTION
NO.

See fig: 

w

1

(WHT)

CENTRALLY
CONTROL

(GRN)

REMOTE
INDICATION

(RED)

ADDRESS

(RED)

ADDRESS

(BLU)

CN20

INTAKE

(RED)

(BLU)

(GRN)

(RED)

BLU

RED

BLK

RED

WHT

BLU

BLU

M-NET REMOTE CONTROLLER

TO OUTDOOR UNIT

BC CONTROLLER

CONTROLLER

TO MA-REMOTE

LIQUID
(WHT)

(BLK)

GAS

(GRN)

PNK

YLW

ORN

BLU

RED

SWITCH

(WHT)

(WHT)

(WHT)

RED

WHT

YLW

ORN

BLU

BRN

6.

5.

4.

1.

Note

The setting of the SW2 dip switches differs in the capacity. For the detail, refer to the fig: 

w

1.

Symbols used in wiring diagram above are,    : terminal block,        : connecter.

At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.

Please set the switch SW5 according to the power supply voltage.
Set SW5 to 240V side when the power supply is 230 and 240 volts.
When the power supply is 220 volts, set SW5 to 220V side.

block

Terminal

Switch

Circuit board

Power supply

Transmission

Address board

Mode selection

Address setting 1st digit

Connection No.

Address setting 2nd digit

Name

Voltage selection

Vane motor

MV

Fan motor

(0

:

/15

T

,25

:

/5.4

T

)

TB5

TB2

SW14<A.B>

SW12<A.B>

SW11<A.B>

SW1<A.B>

A.B

Pipe temperature,detection/Gas

Capacitor(fan motor)

C1

MF

TH23

Thermistor

SW3

SW2

Switch

CN52

CN51

CN41

CN32

Indoor controller board

Name

Symbol

M.B

Legend

Connector

Remote switch

HA terminal-A

Centrally control

Remote indication

Mode selection

Capacity code

P.B

Indoor power board

Symbol

Name

Symbol

ZNR

Varistor

Fuse (6.3A)

FUSE

Fan phase control

F.C

(0

:

/15

T

,25

:

/5.4

T

)

Pipe temperature,detection/liquid

(0

:

/15

T

,25

:

/5.4

T

)

Room temperature,detection

Thermistor

TH21

TH22

Linear expansion valve

LEV

SW5<A.B>

CN5V

(BLU)

CN41

HA

REMOTE

CN32

CN34 CN29

LEV

CN60

CN3A

CN81

CN42

CN52

CN51

123456789

1

0

SW3

0FF

0N

1234

SW2

LED2

M.B

CN21

CN2M

M-NET

FAN

CND

C1

FUSE
250V
6.3A

8

4

ON

OFF

1 2 3 4 5 6 7 8 910

SW1

SW12 SW11

SW14

A.B

0

0

0

LED1

TH22

TH23

TH21

5

MF

M1 M2

DC24-30V

DC8.7-13V

{

P.B

ZNR

F.C

MV

{

2

1

LEV

6

6

5

4

3

2

1

1 2 3 4 5

4

3

2

1

1 2 3

1 2 3

1

2

2

1

3

2

1

4 5

3

2

1

4 5

4

1 2 3

6

1 2 3 4 5

7 8

3

1

1 2

1

3

2

4 5

1 2 3

1

2

3

4

5

6

7

8

1

2

3

4

5
4

2

3

1

3

2

1

1 2

1

4

6

1

3

1

2

3

4

5

6

1
2
3
4
5

PKFY-P20VAM-E
PKFY-P25VAM-E

OC309A---1.qxp  06.7.7 3:47 PM  Page 11

Содержание PKFY-P20VAM-E

Страница 1: ...l names Service Ref PKFY P20VAM E PKFY P20VAM E PKFY P25VAM E PKFY P25VAM E No OC309 REVISED EDITION A Wall Mounted Series PKFY INDOOR UNIT SPLIT TYPE HEAT PUMP AIR CONDITIONERS R407C R22 R410A Note This manual describes only service data of the indoor units RoHS compliant products have G mark on the spec name plate For servicing of RoHS com pliant products refer to the RoHS Parts List Revision Ro...

Страница 2: ...low residual oil piping If there is a large amount of residual oil hydraulic oil etc inside the piping and joints deterioration of the lubricant will result Use ESTR ETHER or HAB as the lubricant to coat flares and flange connection parts If large amount of mineral oil enter that can cause deterioration of refrigerant oil etc Use liquid refrigerant to seal the system If gas refrigerant is used to ...

Страница 3: ...16 Use high tension side pressure of 3 43MPa G or over 2 Charge hose Only for R407C Use pressure performance of 5 10MPa G or over 3 Electronic scale 4 Gas leak detector Use the detector for R134a or R407C 5 Adapter for reverse flow check Attach on vacuum pump 6 Refrigerant charge base 7 Refrigerant cylinder For R407C Top of cylinder Brown Cylinder with syphon 8 Refrigerant recovery equipment ...

Страница 4: ...ols with care If dirt dust or moisture enter into refrigerant cycle that can cause deterioration of refrigerant oil or malfunction of com pressor Do not use a charging cylinder If a charging cylinder is used the composition of refrigera nt will change and the efficiency will be lowered Flare tool Electronic refrigerant charging scale Vacuum pump adaptor Size adjustment gauge Gauge manifold Torque ...

Страница 5: ...rmed with the cylinder of syphon stood vertically Refrigerant is charged from liquid phase Gravimeter Unit 3 Service tools Use the below service tools as exclusive tools for R410A refrigerant No Specifications 1 Gauge manifold Only for R410A Use the existing fitting specifications UNF1 2 Use high tension side pressure of 5 3MPa G or over 2 Charge hose Only for R410A Use pressure performance of 5 0...

Страница 6: ...ton Monitor Set button Mode button Return button Set Time buttons Back Ahead Timer On Off button Set Day button Opening the door ON OFF button Fan Speed button Filter button Enter button Test Run button Check button Clear button Airflow Up Down button Louver button Operation button To preceding operation number Ventilation button Operation button To next operation number On the controls are set th...

Страница 7: ...ponding timer is set Up Down Air Direction indica tor The indicator shows the direc tion of the outcoming airflow One Hour Only indicator Displayed if the airflow is set to weak and downward during COOL or DRY mode Operation varies according to model The indicator goes off after one hour at which time the airflow di rection also changes Room Temperature display Shows the room temperature Louver di...

Страница 8: ...Cooling Heating Height Width Depth Gas side Liquid side PKFY P20VAM E 2 2 2 5 PKFY P25VAM E 2 8 3 2 0 04 0 04 0 20 0 20 Plastic munsell 2 60Y 8 66 0 69 295 815 158 Cross fin Lineflow fan 1 5 9 5 6 5 2 4 9 0 0 017 Polyethylene sheet PP honey comb 12 7 1 2 6 35 1 4 PVC pipe VP 16 connectable I D 16 36 35 33 32 8 5 Electric characteristic Single phase 220 230 240V 50Hz Single phase 220V 60Hz Note 1 R...

Страница 9: ...3k 25 5 4k 30 4 3k 40 3 0k 250V 6 3A 4 Pole Output 17W PS4V17 1 5µF 440V MSFBC20A76 DC12V L N 250V 20A M1 M2 250V 10A Liquid pipe thermistor Gas pipe thermistor Fan motor capacitor Linear expansion valve PKFY P20VAM E PKFY P25VAM E Room temperature thermistor Fuse Indoor controller board Fan motor with thermal fuse Vane motor with limit switch Power supply terminal block Transmission terminal bloc...

Страница 10: ... E PKFY P25VAM E A 159 407 5 328 328 298 235 235 205 205 175 175 170 170 10 10 0 298 407 5 168 135 125 110 35 10 27 5 40 53 65 87 113 128 0 295 260 260 225 225 190 190 180 159 155 155 120 120 85 85 30 30 45 4 4 5 0 0 133 122 5 97 5 85 60 47 5 22 5 15 90 102 5 124 4 4 5 35 4 4 5 40 4 4 5 37 4 11 20 8 4 3 0 72 5 Air intake dimension Air intake Installation plate Knock out hole Installation space 100...

Страница 11: ...necter At servicing for outdoor unit always follow the wiring diagram of outdoor unit Please set the switch SW5 according to the power supply voltage Set SW5 to 240V side when the power supply is 230 and 240 volts When the power supply is 220 volts set SW5 to 220V side block Terminal Switch Circuit board Power supply Transmission Address board Mode selection Address setting 1st digit Connection No...

Страница 12: ...rmal 1 5 White Red 2 6 Yellow Brown 3 5 Orange Red 4 6 Blue Brown Open or short Measure the resistance between the terminals using a tester Surrounding temperature 25 Normal Normal 200 7 Abnormal 1 2 Red Pink 1 3 Red Blue 1 4 Red Orange 1 5 Red Yellow Open or short 1 Measure the resistance between the terminals using a tester Surrounding temperature 20 2 Without disassembling the parts measure the...

Страница 13: ...rmistor R0 15k 3 Fixed number of B 3480K 2 Rt 15exp 3480 0 15k 10 9 6k 20 6 3k 25 5 4k 30 4 3k 40 3 0k Thermistor for lower temperature Linear expansion valve Operation summary of the linear expansion valve Linear expansion valve open close through stepping motor after receiving the pulse signal from the indoor controller board Valve position can be changed in proportion to the number of pulse sig...

Страница 14: ...ot closed all the way It is not necessary to exchange the linear expansion valve if the leakage is small and not making any trouble Thermistor Linear expansion valve Motor will idle and make ticking noise when motor is operated while the linear expansion valve is locked This ticking sound is the sign of the abnormality Check the color of lead wire and missing terminal of the con nector Exchange th...

Страница 15: ...ntal angle Down B C Effective Not effective Heater 4 degreed up Not effective Effective Target Superheat setting temperature 9 degreed 6 degreed Target Subcool setting temperature 15 degreed 10 degreed ON OFF 1 2 3 4 5 6 7 8 9 10 ON OFF 1 2 3 4 5 6 7 8 9 10 ON OFF 1 2 3 4 ON OFF 1 2 3 4 PKFY P20VAM E MODEL SW2 PKFY P25VAM E Address board At delivery Indoor controller board Indoor controller board ...

Страница 16: ... SW12 2nd digit address setting Rotary switch SW14 Connection No Setting SW5 Voltage selection Rotary switch Address setting should be done when M NET remote controller is being used This is the switch to be used when the indoor unit is operated with R2 series outdoor unit as a set If the unit is used at the 230V or 240V area set the voltage to 240V If the unit is used at the 220V set the voltage ...

Страница 17: ...ion valve output LEV SW3 Mode selection CN51 Centrally control SW2 Capacity setting CN52 Remote indication CN6V Vane moter output MV CN20 Room temperature thermistor TH21 CN53M Connect to the indoor power board CN53P Between 1 1 to 2 2 24 30V DC non polat Between 3 3 to 5 5 12 5 13 7V DC Pin3 3 Between 4 4 to 5 5 11 5 12 7V DC Pin4 4 CN35M Connect to the indoor power board CN35P LED2 Power supply ...

Страница 18: ...ween 3 3 to 5 5 12 5 13 7V DC Pin3 3 Between 4 4 to 5 5 11 5 12 7V DC Pin4 4 LED1 Main power supply Indoor unit 220 240V CN35P Connect to the indoor controller board CN35M CN2M Connect to the terminal block TB5 M NET transmission connecting wire 24 30V DC non polar FAN Fan motor output MF CND Power supply for indoor controller board Between 1 1 to 3 3 220 240V AC ...

Страница 19: ...sh Down Be careful not to damage the airflow adjustment plate with the screw driver PKFY P20VAM E PKFY P25VAM E Be careful on removing heavy parts Figure 1 Figure 2 2 REMOVING THE FRONT PANEL Before removing the front panel leave the open space at upper side of air flow adjustment plate approximately 2 to 3 cm 1 Remove the screw caps then remove the set screws Refer to the photo 1 2 Remove the lef...

Страница 20: ...photo 3 Photo 2 Electrical box cover Screw cap Electrical box Photo 3 Indoor micro controller board Indoor power board Indoor power board 4 REMOVING THE ELECTRICAL BOX 1 Remove the front panel Refer to 2 2 Remove the electrical box cover 3 Pull the nozzle assembly toward you as opening the catch of the nozzle assembly 4 Disconnect the indoor outdoor connector 5 Disconnect the following connector o...

Страница 21: ...o 6 7 Pull the left hand side of the heat exchanger toward you See the photo 7 8 Remove the line flow fan Photo 6 Heat exchanger Fan motor Photo 7 Heat exchanger 7 REMOVING THE VANE MOTOR 1 Remove the front panel 2 Remove the screw of the electrical parts box cover and remove the cover 3 Remove the screw of the vane motor and remove the motor from the shaft 4 Disconnect the vane motor connector CN...

Страница 22: ... BOX BACK PLATE BRAND LABEL No Parts No Parts Name Specifications PKFY P20VAM E PKFY P25VAM E Remarks Drawing No Wiring Diagram Symbol Recom mended Q ty Unit Amount Q ty set Price 1 1 1 1 1 1 1 1 1 1 3PCS SET DT25C174H03 BC79R798H02 R01 22A 635 R01 22A 651 R01 22A 500 R01 22A 691 R01 22A 096 R01 22A 054 T7W A00 658 R01 22A 808 Part number that is circled is not shown in the figure ...

Страница 23: ...M1 M2 3P L N GAS LIQUID PS4V17 KA PAR 21MAA No Parts No Parts Name Specifications PKFY P25VAM E PKFY P20VAM E Remarks Drawing No Wiring Diagram Symbol Recom mended Q ty Unit Amount Q ty set Price MV FUSE TH21 A B TB5 TB2 P B M B TH23 TH22 MF R B 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 BG00J285G24 T7W B00 675 R01 22A 530 R01 22A 223 R01 22A 00...

Страница 24: ... HEAT EXCHANGER CONNECT PIPE LINEAR EXPANSION VALVE No Parts No Parts Name Specifications PKFY P20VAM E PKFY P25VAM E Remarks Drawing No Wiring Diagram Symbol Recom mended Q ty Unit Amount Q ty set Price R01 H58 480 R01 H59 480 R01 E03 470 R01 E63 401 1 1 1 1 1 1 LEV 1 3 2 ...

Страница 25: ...ND LABEL No G G G G G G G G G G RoHS Parts No Parts Name Specifications PKFY P20VAM E PKFY P25VAM E Remarks Drawing No Wiring Diagram Symbol Recom mended Q ty Unit Amount Q ty set Price 1 1 1 1 1 1 1 1 1 1 3PCS SET DT25C174H03 BC79R798H02 R01 23A 635 R01 23A 651 R01 23A 500 R01 23A 691 R01 23A 096 R01 23A 054 T7W A01 658 R01 23A 808 Part number that is circled is not shown in the figure ...

Страница 26: ...D PS4V17 KA PAR 21MAA No G G G G G G G G G G G G G G G G G G G G G G G G Parts No Parts Name Specifications PKFY P25VAM E PKFY P20VAM E Remarks Drawing No Wiring Diagram Symbol Recom mended Q ty Unit Amount Q ty set Price MV FUSE TH21 A B TB5 TB2 P B M B TH23 TH22 MF R B 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 BG00J285G24 T7W 23A 675 R01 23A ...

Страница 27: ...EXCHANGER CONNECT PIPE LINEAR EXPANSION VALVE No G G G G RoHS Parts No Parts Name Specifications PKFY P20VAM E PKFY P25VAM E Remarks Drawing No Wiring Diagram Symbol Recom mended Q ty Unit Amount Q ty set Price R01 J37 480 R01 J38 480 R01 E04 470 R01 H05 401 1 1 1 1 1 1 LEV 1 3 2 ...

Страница 28: ...0 8310 JAPAN cCopyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO LTD Distributed in Jul 2006 No OC309 REVISED EDITION A PDF 8 Distributed in Apr 2004 No OC309 PDF 9 Made in Japan New publication effective Jul 2006 Specifications subject to change without notice ...

Отзывы: