[3] Self-diagnosis
Self check result display <Error history> (For the contents of the error code, refer to 13. Troubleshooting, error code list.)
Error history reset
The error history is displayed in
Self check results display.
5
Self check reset
There are the following two ways of resetting self check.
Press the
H
[CHECK] button twice successively within three seconds
→
Resets self check and returns to the state before self check.
Press the
I
[
ON/OFF] button
→
Self check resets and indoor units stop.
(When operation is prohibited, this operation is ineffective.)
Retrieve the error history of each unit using the remote controller.
Self check address or self check refrigerant address
Appro
Switch to the self check mode.
When the
H
F
[CHECK] button is pressed twice successively
within three seconds , the display shown below appears.
Set the address or refrigerant address No. you want to self check.
When the
[
TEMP. (
) and (
)] buttons are pressed,
the address decreases and increases between 01 and 50 or
00 and 15. Set it to the address No. or refrigerant address No.
you want to self check.
ximately three seconds after the change operation,
the self check refrig erant address changes from flashing
to a steady light and self check begins.
Address 3 digits or unit address No. 2 digits
<When opposite side does not exist>
<When there is no error histor y>
ERROR CODE
ERROR CODE
ERROR CODE
ERROR CODE
ERROR CODE
ERROR CODE
When the
D
[
MENU] button is pressed twice successively
within three seconds , the self check address or refrigerant
address flashes.
When the error history was reset, the display shown below appears.
When error history reset failed, the error contents are displayed again.
Error code 4 digits or error code 2 digits
3
2
4
3
1
- 29 -