Indoor unit speci

fi

 cations

Indoor power supply terminal kit (option)

Required

Indoor unit electrical box connector con-
nection change

Required

Label af

fi

 xed near each wiring diagram for 

the indoor and outdoor units

Required

Outdoor unit DIP switch settings (when us-
ing separate indoor unit/outdoor unit power 
supplies only)

6.2.  Remote controller (Fig. 6-2)
For wired remote controller

1)  Two remote controller setting

If two remote controllers are connected, set one to “Main” and the other to “Sub”. For setting procedures, refer to “Function selection of remote controller” in the operation 
manual for the indoor unit.

6. Electrical work

*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. Max. 120 m
 

For PUHZ-RP100/125/140 YHA application, use shield wires. The shield part must be grounded with the indoor unit OR the outdoor unit, NOT with both.

*3. The 10 m wire is attached in the remote controller accessory. Max. 500 m
*4. The 

fi

 gures are NOT always against the ground.

Notes:  1.  Wiring size must comply with the applicable local and national code.
 2. 

Power supply cords and indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed 

fl

 exible cord. (Design 60245 IEC 

57)

 

3.  Install an earth longer than other cables.

If the indoor and outdoor units have separate power supplies, refer to the table at the 
below. If the optional wiring replacement kit is used, change the indoor unit electrical 
box wiring refering to the 

fi

 gure in the right and the DIP switch settings of the outdoor 

unit control board.

ON
OFF

1

2

(SW8)

3

Electric heater
(For models with 
heater)

Connectors (connections when shipped 
from the factory are for indoor unit power 
supplied from outdoor unit)

Indoor unit power supplied from outdoor unit 
(when shipped from factory)

If the indoor and 
outdoor units have 
separate power 
supplies, change the 
connections of the 
connectors as shown 
in the following 

fi

 gure.

Connectors

Indoor unit 

control board

Separate indoor unit/outdoor unit power 
supplies

Electric heater
(For models with 
heater)

Indoor unit 

control board

*  There are three types of labels (labels A, B, and C). Af

fi

 x the appropriate labels to 

the units according to the wiring method.

Indoor unit model

PCA

Indoor unit power supply

~/N (single), 50 Hz, 230 V

Indoor unit input capacity 
Main switch (Breaker)

*1

16 A

Indoor unit power supply 

×

 Min. 1.5

Indoor unit power supply earth

×

 Min. 1.5

Indoor unit-Outdoor unit

*2

×

 Min. 0.3

Indoor unit-Outdoor unit earth

Remote controller-Indoor unit

*3

×

 0.3 (Non-polar)

Indoor unit L-N

*4

AC 230 V

Indoor unit-Outdoor unit S1-S2

*4

Indoor unit-Outdoor unit S2-S3

*4

DC 24 V

Remote controller-Indoor unit

*4

DC 12 V

Circuit 

rating

Wiring

Wire No. 

×

 size 

(mm

2

)

Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a 

fi

 re or communication failure.

 Warning:

Содержание PCA-RP HAQ

Страница 1: ...re il condizionatore d aria leggere attentamente il presente manua le ed il manuale d installazione dell unità esterna PER L INSTALLATORE Español MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado PARA EL INSTALADOR Português MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente est...

Страница 2: ... as the seaside the performance can be significantly reduced and the internal parts can be damaged Do not install the unit where combustible gases may leak be produced flow or accumulate If combustible gas accumulates around the unit fire or explo sion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as...

Страница 3: ...ion bolts or use angle stock braces or square timbers for bolt installation Fig 3 4 3 Selection of suspension bolts and tubing positions Fig 3 3 Using the pattern paper provided for installation select proper positions for suspen sion bolts and tubing and prepare relative holes 3 2 Preparation for installation Fig 3 2 1 Suspension bolt installing spacing mm Models A B RP71 1180 1136 RP125 1564 152...

Страница 4: ...g When installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pres sure in the refrigerant line and may result in an explosion and other hazards The use of any ...

Страница 5: ...re to only use the flare nuts that came with the unit A Flare cutting dimensions Copper pipe O D mm Flare dimensions øA dimensions mm ø6 35 8 6 9 0 ø9 52 12 6 13 0 ø12 7 15 8 16 2 ø15 88 19 0 19 4 ø19 05 22 9 23 3 B Flare nut tightening torque Copper pipe O D mm Tightening torque N m Tightening angle Guideline ø6 35 14 18 60 90 ø9 52 35 42 60 90 ø12 7 50 58 30 60 ø15 88 75 80 30 60 ø19 05 100 140 ...

Страница 6: ...cedures 1 Remove the independent piece 2 screws of the indoor unit 2 Attach the band 6 supplied with the unit to the drain hose 5 3 Connect the drain hose 5 to the drain hole of the unit 4 Connect the field drain tubing VP 25 O D ø32 PVC TUBE to the drain hose 5 5 Tighten the band 6 in 2 places 6 Wrap the drain tubing cover 7 supplied with the unit 7 Install the independent piece 8 Check for corre...

Страница 7: ...the remote controller accessory Max 500 m 4 The figures are NOT always against the ground S3 terminal has DC 24 V against S2 terminal However between S3 and S1 these terminals are not electrically insulated by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be li...

Страница 8: ...longer than other cables If the indoor and outdoor units have separate power supplies refer to the table at the below If the optional wiring replacement kit is used change the indoor unit electrical box wiring refering to the figure in the right and the DIP switch settings of the outdoor unit control board ON OFF 1 2 SW8 3 Electric heater For models with heater Connectors connections when shipped ...

Страница 9: ...te Make the above settings on Mr Slim units as necessary Table 1 summarizes the setting options for each mode number Refer to the indoor unit Installation Manual for the detailed information about initial settings mode numbers and setting numbers for the indoor units Be sure to write down the settings for all functions if any of the initial settings has been changed after the completion of install...

Страница 10: ... controller After the power is turned on PLEASE WAIT will be displayed for approximately 2 minutes Indoor controller board LED 1 will be lit up LED 2 will be lit up if the address is 0 or off if the address is not 0 and LED 3 will blink Outdoor controller board LED 1 green and LED 2 red will be lit up After the startup mode of the system finishes LED 2 will be turned off If the outdoor controller ...

Страница 11: ...ot a problem Step 5 Stop the test run 1 Press the ON OFF button to stop the test run The Test run menu will appear Note If an error is displayed on the remote controller see the table below LCD Description of malfunction LCD Description of malfunction LCD Description of malfunction P1 Intake sensor error P9 Pipe sensor error dual wall pipe E0 E5 Communication error between the remote controller an...

Страница 12: ...emperature of heat sink U8 Outdoor unit fan safeguard stop U6 Compressor overcurrent interruption Abnormal of power module U7 Abnormality of super heat due to low discharge temperature U9 UH Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit Current sensor error Others Other errors Refer to the technical manual for the outdoor unit 7 Test run On wir...

Страница 13: ...P frequency A Hz Hr times Hr Ref address Cool Ref address Cool Ref address Cool Sub cool OU TH4 temp OU TH6 temp OU TH7 temp IU air temp IU HEX temp IU filter time 1 2 3 Select Service from the Main menu and press the SELECT button Select Check with the F1 or F2 button and press the SELECT button Select smooth maintenance with the F1 or F2 button and press the SELECT button Select each item Select...

Страница 14: ...берег моря может привести к значительному снижению эффективности работы прибора или повреждению его внутренних частей Не устанавливайте прибор в местах где возможна утечка возникновение приток или накопление горючих газов Если горючий газ будет накапливаться вокруг прибора это может привести к возникновению пожара или взрыву Не держите пищевые продукты растения домашних животных в клетках произвед...

Страница 15: ...ты W3 8 или М10 размера Fig 3 4 мм 2 1 Наружные размеры прибора Внутренний прибор Fig 2 1 Выберите такое место для установки которое обеспечивало бы следующие зазоры необходимые для установки и техобслуживания мм Mодель W D H A B C E RP71 1136 650 296 Мин 100 Мин 100 Мин 500 Макс 250 RP125 1520 650 296 Мин 100 Мин 100 Мин 500 Макс 250 Предупреждение Укрепите внутренний прибор на стене которая явля...

Страница 16: ...есей окислителей грязи мусора масел или влаги Храните предназначенные для установки трубы в помещении герметически закрытыми с обоих концов до припайки Используйте в качестве масла охлаждения масло сложного или простого эфира или алкинбензол небольшое количество для покрытия раструбов и фланцевых соединений Используйте для заполнения системы жидкий хладагент Не используйте другие хладагенты кроме ...

Страница 17: ...щей жидкости до запуска компрессора 4 Прокладка труб хладагента Порядок установки 1 Наденьте поставленный кожух трубы 2 на трубу газа до тех пор пока он не будет плотно прижат к листовому металлу внутри прибора 2 Наденьте поставленный кожух трубы 3 на трубу жидкости до тех пор пока он не будет плотно прижат к листовому металлу внутри прибора 3 Закрепите кожухи труб 2 и 3 с обоих концов 15 20 мм по...

Страница 18: ...ветствующими клеммами 4 Установите на место крышку блока терминалов 5 Зафиксируйте электропровода местным проводным зажимом расположенным с правой стороны соединительной коробки Предупреждение Никогда не подсоединяйте внахлест силовой кабель или соединитель ный кабель внешнего питания Это может привести к задымлению воз горанию или неисправности A Крышка блока терминалов B Установочные винты C Кле...

Страница 19: ...а не должны быть легче экранированного гибкого провода из полихлоропрена модель 60245 IEC 57 3 Длина устанавливаемого кабеля заземления должна превышать длину других кабелей A Источник электропитания наружного прибора B Прерыватель утечки на землю C Прерыватель проводной цепи или изолирующий выключатель D Наружный прибор E Соединительные провода внутреннего прибора наружного прибора F Пульт дистан...

Страница 20: ...245 IEC 57 3 Длина устанавливаемого кабеля заземления должна превышать длину других кабелей Электрический обогреватель Для моделей с обогревателем Разъемы соединения при поставке с предприятия изготовителя таковы что источник электропитания на внутренний прибор подается от наружного прибора Источник электропитания на внутренний прибор подается от наружного прибора при поставке с предприятия изгото...

Страница 21: ...ока Эти настройки относятся ко всем подключенным внутренним блокам Включено После восстановления питания требуется четыре минуты ожидания 2 02 Выбор термистора измерение температуры в помещении Усредненное значение показаний температуры включенных внутренних блоков 1 Термистор на внутреннем блоке к которому подключен контроллер дистанционного управления неизменяемое значение 2 Встроенный датчик на...

Страница 22: ...ения дождитесь удаления с дисплея сообщения PLEASE WAIT Ждите Сообщение PLEASE WAIT Ждите отображается в течение приблизительно 2 минут после включения питания Плата управления внутреннего блока индикатор 1 загорается индикатор 2 загорается если адрес равен 0 или гаснет если адрес не равен 0 индикатор 3 мигает Плата управления наружного блока индикатор 1 зеленый и индикатор 2 красный загораются По...

Страница 23: ...пытания Шаг 5 Остановка пробного пуска 1 Для остановки пробного пуска нажмите кнопку ВКЛ ВЫКЛ Отображается меню Пробного пуска Примечание Если на дисплее отображается код ошибки см таблицу ниже ЖК дисп лей Описание сбоя ЖК дисплей Описание сбоя ЖК дисп лей Описание сбоя P1 Ошибка датчика впуска P9 Ошибка датчика трубопровода двойной трубопровод E0 E5 Ошибка связи между пультом дистанционного управ...

Страница 24: ...лизительно 2 минут после включения питания ПослезагоранияСИД1 2 СИД2выключается горит только СИД 1 Правильная работа В течение приблизительно 2 минут после включения питания работа пульта дистанционного управления невозможна вследствие запуска системы Правильная работа PLEASE WAIT Код ошибки По истечении приблизительно 2 минут после включения питания Горит только СИД 1 СИД 1 2 мигают Не подсоедине...

Страница 25: ... Нормальный Нажмите кнопку ВЫБОР начнется работа в выбранном режиме Работа в режиме Stable mode Стабильный режим займет прим 20 минут Отобразятся рабочие данные Для параметра общего времени работы компрессора COMP run КОМП раб используется единица 10 часов а для параметра количества включений компрессора COMP On Off КОМП Вкл Выкл используется единица 100 раз дробные значения исключены Навигация по...

Страница 26: ... do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Sollentuna Sweden Hammarbacken 14 P O Box 750 SE 19127 Sollentuna Sweden UK Branch UK Branc...

Отзывы: