Mitsubishi Electric PAC-YG63MCA Скачать руководство пользователя страница 3

2

• Confirm that the box contains the following parts.

* In addition to the parts mentioned above, other parts need to be procured locally in order to operate this device. Furthermore, other Mitsubishi optional 

parts may be required depending on how the device is to be used. 
For details, refer to "6 Installation Method".

4-1. Product Specifications

*1: Supply electric power from a power supply unit for the transmission line or an outdoor unit. Furthermore, the power consumption factor of the M-NET 

circuitry of this unit is "1/4" (equivalent to one ME Remote Controller).

*2: Configure the dip switch settings for the analog input method to use while referring to "9 Switch List".
*3: The measurement error for the system includes the measurement error for this unit, sensor, and wiring.
*4: Settings for the interlock function are performed from the maintenance tool. For details, refer to the instruction manual for the Maintenance Tool.

4-2. External View

3

Confirmation of Parts

Number

Part Name

Quantity

1

AI controller

1

2

Installation/instruction manual (this document)

1

4

Specifications

Item

Description

Power Supply

24 VDC±10%: 5 W

Screw terminal 

block (M3)

Interface

M-NET communication

17 to 30 VDC (*1)

Screw terminal 

block (M3)

Input

Ch

Sensor

Measurement 

target

Measurement 

range

Measurement error

External connection 

method

Ch1

Pt100 

(3-wire system)

Temperature

-30 to 60°C

[-22 to 140°F]

±0.3%FS ±0.1°C (0.18°F) (*3)

[at 25°C (77°F)]

Screwless terminal 

block (3 poles)

Analog

4 to 20 mADC

Temperature/

humidity

(Set by system 

controller)

±0.5%FS ±0.1°C (0.18°F) (*3)

±0.5%FS ±0.1%RH

[at 25°C (77°F)]

Screwless terminal 

block (2 poles)

1 to 5 VDC

0 to 10 VDC

Ch2

Analog

4 to 20 mADC

Temperature/

humidity

(Set by system 

controller)

±0.5%FS ±0.1°C (0.18°F) (*3)

±0.5%FS ±0.1%RH

[at 25°C (77°F)]

Screwless terminal 

block (2 poles)

1 to 5 VDC

(*2)

0 to 10 VDC

Output

Upper/lower limit 

alarm output 

(non-voltage contact)

Applied load

MAX: 24 VDC, 5 W

MIN: 5 VDC, 2 mW

* AC loads cannot be connected.

Screw terminal 

block (M3.5)

Interlock 

Function

Interlock M-NET devices according to measurement data values. (*4)

Environment 

Conditions

Temperature

Operating temperature range

0 to 40°C [32°F to 104°F]

Storage temperature range

-20 to 60°C [-4°F to 140°F]

Humidity

30 to 90%RH (no condensation)

Dimensions

200 (W) × 120 (H) × 45 (D) mm / 7

7

/

8

 (W) × 4

3

/

4

 (H) × 1

25

/

32

 (D) in

Weight

0.6 kg / 1 3/8 lb

Current Time  

Power Failure 

Backup

If the power is cut, an internal capacitor will normally keep counting the current time for approximately one week. 

(The internal capacitor takes approximately a day to charge. Replacement of a battery is not necessary.)

Installation 

Environment

Inside a control panel (indoors)

* Use this product in a hotel, a business office environment or similar environment.

[ 24 VDC Power Supply]

N623

Al controller

PAC-YG63MCA

MODEL

SERVICE REF. PAC-
INPUT
WEIGHT
SERIAL No.

MADE    IN    JAPAN

YG60MCA-J

 VOLTAGE

 DC24V;0.2A

0.6 kg  / 1 /

3 8

lb

Al controller

PAC-YG63MCA

[ Output LEDs ] 

Alarm

Alarm

Ch2

Ch1

[ OUTPUT ] Non-voltage Contact Output

Alarm

Alarm

Ch2

Ch1

[ INPUT ]

Pt100

4 to 20 mA / 1 to 5 V / 0 to 10 V

4 to 20 mA / 1 to 5 V / 0 to 10 V

Ch1

Ch2

harmful interference, and (2)this device must accept any interference
received, including interference that may cause undesired operation.

subject to the following two conditions: (1)this device may not cause

This device complies with Part15 of the FCC Rules.Operation is

200

 (

7

7

/

8

)

46

 (

1

13

/

16

)

26

 

(

1

1

/

32

)

45

 (

1

25

/

32

)

9

 (

3

/

8

)

15

 (

19

/

32

)

11

0

 (

4

11

/

32

)

26 

(

1

1

/

32

)

120

 (

4

3

/

4

)

150

 (

5

29

/

32

)

26

 (

1

1

/

32

)

83.5

 (

3

5

/

16

)

27

 (

1

3

/

32

)

4.5

(

3

/

16

)

Unit: mm (in)

Содержание PAC-YG63MCA

Страница 1: ...2 4 Specifications 2 4 1 Product Specifications 2 4 2 External View 2 5 Example of System Configuration 3 6 Installation Method 3 6 1 Parts to be Procured Locally 3 6 2 Installation Procedure 4 7 Wiring Method 5 7 1 Names of Parts 5 7 2 Connecting the Power Line and M NET Transmission Line 6 7 3 Connecting the Sensors 6 1 Channel 1 Pt100 Input 6 2 Channel 1 Channel 2 Analog Input 7 7 4 Connecting ...

Страница 2: ... in an unusual environment If the device is installed where a large amount of oil including machine oil steam or sulfidizing gas is present this environment may lead the device to a remarkable drop in performance or damage its parts Do not install the device where a large amount of steam rises such as in the bathroom or kitchen Avoid installing this device where dew condensation occurs If the devi...

Страница 3: ... 4 to 20 mADC Temperature humidity Set by system controller 0 5 FS 0 1 C 0 18 F 3 0 5 FS 0 1 RH at 25 C 77 F Screwless terminal block 2 poles 1 to 5 VDC 2 0 to 10 VDC Output Upper lower limit alarm output non voltage contact Applied load MAX 24 VDC 5 W MIN 5 VDC 2 mW AC loads cannot be connected Screw terminal block M3 5 Interlock Function Interlock M NET devices according to measurement data valu...

Страница 4: ...or etc AI controller 24 VDC Power Supply 24 VDC Power Supply 6 Installation Method Required Part Specification Unit fixing screws M4 screw 4 Power supply for this unit Power source 24 VDC 10 0 2 A Minimum loading SELV circuit power line with grounding terminal Ripple noise Lower than 200 mVp p Compatible specification Authorized or CE marked products Subject to regulations IEC60950 or EN60950 CISP...

Страница 5: ... all four of the screws 2 To remove the cover as shown in the figure remove the two screws for fixing the cover in place and then remove the cover by unhooking the upper hook section from the lower case To attach the cover hook the upper hook section on the lower case and then fix the cover in place with the two screws that were removed Note The space shown above does not include space for periphe...

Страница 6: ...erform wiring so that the terminal block is not strained If strained use a wire guide or junction terminal to alleviate the stress on the terminal block Do not connect the wires directly from the top of the control panel to the terminal block Moisture may enter this device along the wiring and cause electric shock or fire 24 VDC Power source Relay Junction terminal block 7 Wiring Method CN01 CN03 ...

Страница 7: ... 24 VDC power supply 1 Varistor 2 Arrester 3 Noise filter 4 Fuse It is important to pay attention to the polarity when connecting to the 24 VDC power supply terminal block Connecting the positive and negative in the reverse order will cause a failure Fix the power line and M NET transmission line in place on the outside to ensure that the terminal block is not affected by any external force Not se...

Страница 8: ... circuiting the plates cover lower case or neighboring wires Perform wiring so that the terminal block is not strained If strained use a wire guide or junction terminal to alleviate the stress on the terminal block CN03 Ch1 Ch2 X1 Caution To use X1 relay obtain one that satisfies the following specifications Operating coil Applied load MAX 24 VDC 5 W Built in diode MIN 5 VDC 2 mW Built in diode 1 ...

Страница 9: ... Procedure Ch Setting Setting Switch Pt100 To not use Ch1 Pt100 used 1 SW01 1 2 SW01 3 ON ON OFF OFF Ch Setting Setting Switch 4 to 20 mADC 1 to 5 VDC 0 to 10 VDC To not use Ch1 Setting of sensor to use 1 SW11 1 2 SW11 2 3 SW01 1 4 SW01 2 5 SW01 3 ON ON ON OFF OFF OFF ON ON OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF OFF Ch2 Setting of sensor to use 1 SW12 1 2 SW12 2 3 SW02 1 4 SW02 2 ON ON ON OFF O...

Страница 10: ...emperature Measurement range setting Set the upper limit and lower limit values Set a range from 30 C 22 F to 60 C 140 F Measurement correction Input the measurement temperature correction value offset value Ch Setting Setting with G B 50A or TG 2000A Ch1 Measurement category setting Select the temperature humidity Measurement range setting Set the upper limit and lower limit values Measurement co...

Страница 11: ... of upper lower limit alarm interlock output use No Yes Specify whether to use channel 2 upper lower limit alarm interlock output 6 Selection of the system to judge upper lower limit alarm interlock output Self judgment System controller Select whether this device itself or the system controller performs the output judgment of the upper lower limit alarm interlock 7 Unused Set to OFF 8 Unused Set ...

Страница 12: ...2 Output LEDs Error status 1 1 4 digit error code LED12 13 14 15 Status display LEDs Refer to 10 2 Error Status Display Output Method Ch1 Ch2 LED 03 LED 02 Level Output Alarm output Alarm stop Alarm output Alarm stop LED11 LED12 LED13 LED14 LED15 Function Remark Common Error code display Binary number indication 23 8 22 4 21 2 20 1 STEP1 ErrorStatusDisplay Starting Point Indication LEDs 12 to 15 f...

Страница 13: ...surement accuracy of the sensor used results in extreme differences in the measurement values use the measurement correction value offset value input function of the system controller to correct the measurement values 3 When upper lower limit alarm interlock is to be used input a value that exceeds the set alarm level and confirm whether the alarm is displayed on the controller Furthermore confirm...

Страница 14: ......

Страница 15: ......

Страница 16: ... if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the use is encouraged to try to correct the int...

Отзывы: