Special function

(a) 

Low-level sound priority mode

 (Local wiring)

Unit enters into Low-level sound priority mode by external signal input setting.

Inputting external signals to the outdoor unit decreases the outdoor unit operation sound 3 to 4 dB lower than that of usual. 

Adding a commercial timer or on-off switch contactor setting to the CNDM connector which is optional contactor for demand

input located on the outdoor controller board enables to control compressor operation frequency.

W

The performance depends on the load of conditioned outdoor temperature.

How to wire

1) Make the circuit as shown above with Adaptor for external signal input(PAC-SC36NA).

2) Turn SW1 to on for Low-level sound priority mode.

Turn SW1 to off to release Low-level sound priority mode and normal operation.

(b) 

Demand control

ON/OFF Operation

 

(Local wiring)

Demand control is available by external input. In this mode, power consumption is decreased within the range of usual

0~100%.

Connect SW 1 which is procured locally between Orange and Red(1 and 3) of the Adaptor (PAC-SC36NA), for external signal 

input and insulate the tip of the brown lead wire.

It is possible to set it to the following power consumption (compared with ratings) by setting the SW7-1, 2.

SW7-1

SW7-2

OFF

0% (Operation stop)

75%

50%

OFF

ON

OFF
OFF

ON

Power consumption 

(with SW1 on)

CNDM

X

SW1

~

X

Max. 10 m[33ft] including local wiring

SW1 : Switch 

X : Relay (Contact spec. : DC1mA)

Relay

supply

Red 3

Brown 2

Orange 1

Purchased locally

Adaptor for external 

signal input

(PAC-SC36NA)

Outdoor unit 

controller board

3
2
1

Insulate this point securely as 

this is not used.

<Low-level sound priority mode circuit>

OCH429--3.qxp  07.11.20 9:19 AM  Page 73

How to wire

CNDM

X

SW1

~

X

Max. 10 m[33ft] including local wiring

SW1 : Switch 

X : Relay (Contact spec. : DC1mA)

Relay

supply

Red 3

Brown 2

Orange 1

Purchased locally

Adaptor for external 

signal input

(PAC-SC36NA)

Outdoor unit 

controller board

3
2
1

Insulate this point securely as 

this is not used.

<Power consumption/operation ON/OFF mode circuit>

Note:

When SW7-1 and SW7-2 is s set to the OFF position and SW1 is closed, operation will stop (compressor and condensing

fan stops operation) the indoor fan will continue operation base on user settings of fan speed.

This function does not prohibit the functions of the wired controller.