background image

4. Locally Procured Parts

All parts other than the Multiple Remote Controller Adapter are procured locally.

The items required will depend on the connection method. Refer to the example of use shown below.

(Example)

1

Switch .................. Single pole, single action switch.

CAUTION

Select a part with contacts for extremely low amperage.  

5 or 12 VDC is used at the contact points for the switch so there is a load of only approximately 1 mA.  

Improper switch selection could cause improper operation.

2

Relay ................... Use relays that meet the following specifications.

Operation coil

Rated voltage: 12 VDC

Power consumption: 0.9 W or less

* Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.

3

Transit relay ......... When the wiring work as described in 

6. Wiring Restrictions

 is required, this relay is used.

4

Control cable ....... The length of the electrical wiring for the PAC-SA88HA-E is 2 meters (6-1/2 ft).

To extend this length, use sheathed 2-core cable. Don’t extend the cable more than 10 meters (32 ft).

Control cable type: CVV, CVS, CPEV or equivalent

Cable size: 0.5 mm

2

 ~ 1.25 mm

2

 (16 to 22 AWG)

CAUTION

1. Wiring should be covered by insulation tube with supplementary insulation.

2. Use relays or switches with IEC or equivalent standard.

3. The electric strength between accessible parts and control circuit should have 2750 V or more.

5. Locally Procured Wiring

Basic connection methods for following models are shown below as examples.

For details, refer to the CITY MULTI DATA BOOK, Electrical Wiring Diagram etc.

Indoor unit “-E” type input/output connector (CITY MULTI series)

Polarity (output terminal)

No.

Color

CN51

CN52

1

Brown

+

2

Red

-

3

Orange

+

-

4

Yellow

-

-

5

Green

-

1

 Input (CN51)

CN51

X

Y

Z

L

1

L

2

SW

X

1

2

3

4
5

Y

Z

Distant control board

Indoor unit 

control board

Relay circuit

Adapter

SW: Distant ON/OFF switch

L1: Status lamp

L2: Error lamp

X: Relay (a point of contact, fixed DC1 mA)

Y, Z: Relay   Contact rating voltage ≥ 15 VDC

 

Contact rating current ≥ 0.1 A

 

Minimum applicable load ≤ DC1 mA

Power 

supply of 

relay

Maximum cable length is 10 m (32 ft.)

*  Every time the SW is pushed (the pulse 

is inputted), it reacts against ON/OFF.

• ON/OFF (Pulse) input specification

Item

Description

Input signal

Pulse sign (Normally open)

Standard of pulse

200 ms 

 

or more

200 ms 

 

or more

2

 Input (CN52)

3

 Output (CN52)

SW1

X

CN52

5

1

2

3

4

X

Distant control board

Indoor unit 

control board

Relay circuit

Adapter

Since this is not used, be sure to completely wrap 

with insulation tape.

 SW1: Demand switch

 X: Relay (coil ≤ 0.9 W, 12 VDC)

SW1 Indoor unit
ON

Forced thermo-OFF

OFF Normal running

Power 

supply of 

relay

Maximum cable length is 

10 m (32 ft.)

L

1

L

2

L

3

Z

CN52

1

2
3
4
5

Y

X

X

Z

Y

Distant control board

Indoor unit 

control board

Relay circuit

Adapter

Since this is not used, be sure to completely wrap 

with insulation tape.

 L1: St atus lamp

 

Fan motor output (SW1-5 OFF) 

Thermostat ON (SW1-5 ON)

 L2: Cooling/Dry status lamp

 L3: Heating status lamp

 X, Y, Z:  Relay (Coil with fixed 12 VDC, a power consumption of 0.9 W or less)

Power 

supply of 

relay

Maximum cable length is  

10 m (32 ft.)

6. Wiring Restrictions

Keep the length of the cable connecting to the circuit board of the indoor unit shorter than 10 meters (32 ft).

Longer than 10 meters (32 ft) could cause improper operation.

Use a transit relay when extending wiring such as remote wiring.

When using a polarized relay (such as a relay with a diode), connect the relay in the correct polarity to avoid damage to the indoor unit circuit 

board.

WT02522X04

HEAD OFFICE:

 TOKYO BLDG. , 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

Authorized representative in EU:

  MITSUBISHI ELECTRIC EUROPE B.V. 

HARMAN HOUSE, 1 GEORGE STREET, UXBRIDGE, MIDDLESEX UB8 1QQ, U.K.

Отзывы: