Function code and Data address

6.3 Holding Register

Read using function code 03 and write using function code 06/ 16.

Function code 06 is single holding register, and function code 16 is multiple holding register.

Broadcast request is available ONLY when function code is 06/16.

Function 

Code

Address Modicon 

Address

Register 

Name

Details

System No.*

1

1-4,6 5,7

Read:03

Write: 06/ 16

0

40001

Capacity 

request

(from Local 

controller)

OFF, Step1-Step11, Auto 

step mode

• Auto step mode is 

Read only

0(0x0000)=OFF

1(0x0001)=Step1 (Min.)

2(0x0002)=Step2

~~~~

11(0x000B)=Step11 (Max.)

12(0x000C)=Auto step mode (Auto)

• If the interface unit receives other data, received data will be 

cancelled.

• OFF=DriveOFF / Others=DriveON

• When reading and the intelligent multiple outdoor unit control is 

used, response of the sub interface unit becomes "12 (0x000C)", 

because capacity request is only for the main interface unit.

N/A

1

40002

Drive Mode

1 (0x0001) = Heating mode, 3 (0x0003) = Cooling mode,

7(0x0007) = Fan mode, 8 (0x0008) = Auto change over

• If the interface unit receives other data, received data will be cancelled.

2

40003 Temperature 

Setpoint

Cooling: 12~30°C

Heating: 17~28°C

Auto change over: 17~28°C

(by 1°C)

0(0x0000)=0°C

10(0x000A)=1.0°C

20(0x0014)=2.0°C Actual set point × 10 = Communication data

~~~~

300(0x012C)=30.0°C

• If the interface unit receives other data, received data will be 

cancelled.

• When the interface unit receives decimal value, value will be 

round down.

N/A

3

40004

Drive ON/OFF

0=OFF / 1=ON

• If the interface unit receives other data, received data will be cancelled.

N/A

4

40005

Error Code 

(hex)

[READ ONLY]

0x8000=No error

0x8000≠Error Code 

*2

5

40006

Error Code 

(decimal)

[READ ONLY]

8000=No error

8000≠Error Code 

*2

6

40007 Step status

[READ ONLY]

OFF,Step1-Step11,Auto 

step mode

0(0x0000)=OFF

1(0x0001)=Step1 (Min.)

2(0x0002)=Step2

~~~~

11(0x000B)=Step11 (Max.)

12(0x000C)=Auto step mode (Auto)

• When the intelligent multiple outdoor unit control is used, step 

status shows devided capacity step of each interface unit.

7

40008

Ref.address

[READ ONLY]

0x0000=address0

0x0001=address1

~~~~

0x000F=address15

8

40009

Modbus 

Comms 

Counter

[READ ONLY]

Value or a counter which increments upon every valid Modbus command received.

0=0count

1=1count

~~

65535=65535count

• When the counter becomes more than 65535, it΄s cleared.

*1. Refer to the section 1 "System". "

" means available, and "N/A" means NOT available.

*2. Meanings of error codes, please see Table 6.

< Table 6 : Error codes >

Error code

(Modbus)

Error code

(Remote controller)

Discription

5101

P1

Refer to the 
installation manual.

5102

P2

1503

P6 (Freezing)

1504

P6 (Overheating)

5103

P9

6831
6834

"E0" or "E4"

6201

E1

6202

E2

Error code

(Modbus)

Error code

(Remote controller)

Discription

6832
6833

"E3" or "E5"

Refer to the 
installation manual.

6840
6843

E6

6842

E7

0404

Fb

1514

PL

5111

PU

7130

EE

< Continued from the previous page. >

Содержание PAC-IF013B-E

Страница 1: ...unction code and Data address 5 7 System Design Responsibility 7 8 Laws and Regulations 7 September 2015 Model Name PAC IF013B E PAC SIF013B E Related document Refer to the following manual PAC IF013B E PAC SIF013B E INSTALLATION MANUAL This manual describes the Modbus communication only For safety precautions make sure to read installation manual of PAC IF013B E PAC SIF013B E ...

Страница 2: ... interface unit Do NOT send temperature set point or Drive ON OFF DIP SW 1 1 to 1 3 and SW6 are as follows Regarding other settings refer to the section 2 and the installation manual Input type SW1 1 SW1 2 SW1 3 SW6 1 SW6 2 Modbus ON ON ON OFF OFF 2 Auto step mode by Modbus AHU local controller can send Drive ON OFF operation mode and temperature set point by Modbus communication to the interface ...

Страница 3: ...en none Set by DIP SW on the interface controller board SW4 6 SW4 7 Details OFF OFF Odd ON OFF Even OFF ON None ON ON N A Stop bit Slectable from 1bit 2bit OFF ON SW 4 8 1 bit 2 bit 3 Communication timing 3 1 Message sending interval Data sending interval of Master Request from Master query Request from Master query Response from Slave Response Note Please send a query or a operation command every...

Страница 4: ...FG terminal Fig 4 1 PAC S IF013B E A 120Ω A B B SG SG FG Shield Shield Shield Master device 120Ω A A B B SG SG PAC S IF013B E Master device 120Ω FG FG A B SG FG PAC S IF013B E 120Ω Table 4 1 Cable specifications Item Description Cable type Shielded cable Number of pairs 2P Conductor resistance 20 C 88 0 Ω km or less Insulation resistance 10000MΩ km or more Dielectric withstand voltage 500VDC 1 min...

Страница 5: ...99 9 C 0xFFFF 0 1 C 0x0000 0 0 C 0x0001 0 1 C 0x012C 30 0 C When thermistor is open or short Open 0xFC19 Short 0x03E7 1 30002 TH1 Target air temp 39 C 88 5 C by 0 5 C 2 30003 TH5 2 Phase temp 39 C 88 5 C by 0 5 C 3 30004 TH2 Ref liquid temp 39 C 88 5 C by 0 5 C 4 30005 TH7 Outdoor temp 15 C 46 C by 1 C Actual thermistor temp 10 Communication data 0xFC19 99 9 C 0xFFFF 0 1 C 0x0000 0 0 C 0x0001 0 1 ...

Страница 6: ...nit receives other data received data will be cancelled When the interface unit receives decimal value value will be round down N A 3 40004 Drive ON OFF 0 OFF 1 ON If the interface unit receives other data received data will be cancelled N A 4 40005 Error Code hex READ ONLY 0x8000 No error 0x8000 Error Code 2 5 40006 Error Code decimal READ ONLY 8000 No error 8000 Error Code 2 6 40007 Step status ...

Страница 7: ... The description of exception codes in exception response is shown in the table below Code Name Description 01h ILLEGAL FUNCTION The function code received in the query is not an allowable action for the slave the interface unit 02h ILLEGAL DATA ADDRESS The data address received in the query is not allowable address for the slave the interface unit 03h ILLEGAL DATA VALUE A value contained in the q...

Страница 8: ...DA KU TOKYO 100 8310 JAPAN Authorised representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K This product is designed and intended for use in the residential commercial and light industrial environment ...

Страница 9: ...Related Links Model Number PAC SIF013B E PAC S IF013B E Modbus Manual PAC S IF013B E Parts Catalogue PAC IF013B E AHU Design Guideline RG79F087H03 PAC IF013B E Installation Operation Manual RG79F030H04 ...

Отзывы: