3-3. Attach the drain socket

As shown in Fig. 3-5, insert the drain socket into the U-shaped cutout.

Fig. 3-5

4. Wiring

1. Passing the pump wires (Fig. 4-1)

(a) Route the 2 wires so that they pass through the raised part when the 

maintenance cover is installed.

Fig. 4-1

2. Connecting the pump wires to the control box of the indoor unit (Fig. 4-2)

(a) 

Insert the white connector into CN31 on the indoor P.C. board.

 

Since a connector has been inserted into both CNP and CN31 before 

shipment, they must be removed.

(b) When wiring is complete, fasten the remaining cords with the band 

3

.

Fig. 4-2

When fastening lead wires

Power wires and low-voltage wires are separated inside the control box to prevent noise. Lead wires from the Drain Water Lift-

Up Kit also need to be separated, so fasten them to the lead wires located inside the control box as described below.

•  Since the yellow wire is used for power, its remaining portion must be fastened to the lead wires from the power terminal block.

•  Since the clear wire is used for low voltage, its remaining portion must be fastened to the pipe sensor lead wire.

<Outside unit>

PTT screw 

4

<Inside unit>

Drain socket

Frame

From drain pump

Yellow wire

Clear wire

From drain sensor

Raised part

CNP

Blue

White

CN31

from drain pump

Yellow wire

Indoor P.C. 

board

Clear wire

from drain sensor

Содержание PAC-DRP10DP-E

Страница 1: ...y the user may result in water leakage electric shock or fire Install the unit according to this Installation Manual If the unit is installed improperly water leakage electric shock or fire may result Have all electric work performed by a properly licensed electrician Electric work should be performed in strict adherence to procedures to this Installation Manual Always provide a dedicated power su...

Страница 2: ... conditioner with the panel or guard removed The hand could come in contact with rotating hot or high pressure components They could cause electrical shock or entanglement Never operate the air conditioner with the air filter removed Particles will enter into the air conditioner and cause damage Never turn off the power supply immediately after stopping the unit Wait five minutes or more before tu...

Страница 3: ...ng screws 2 locations shown in Fig 3 3 and remove the Drain socket hole cover These screws will be reused to fix the drain socket Keep them in a safe place Fig 3 3 3 2 Attach the drain pump 1 Attach the drain pump assy 1 and drain socket as shown in Fig 3 4 using four PTT screws 4 When attaching the drain socket make sure that drain hose is straight 2 Attach the Rubber Plug 2 Fig 3 4 Control box c...

Страница 4: ...ith the band 3 Fig 4 2 When fastening lead wires Power wires and low voltage wires are separated inside the control box to prevent noise Lead wires from the Drain Water Lift Up Kit also need to be separated so fasten them to the lead wires located inside the control box as described below Since the yellow wire is used for power its remaining portion must be fastened to the lead wires from the powe...

Страница 5: ...se elbows to make it at least height according to the site Fig 5 3 9 Be sure to use the supplied drain hose Accessory Connect each connection with vinyl chloride adhesive But never use any adhesive over the indoor unit discharge port Otherwise the Drain Water Lift Up Kit cannot be serviced later Also the end connection may be eroded by resin and so cracked Note If the rise portion is long there wi...

Страница 6: ...nt water overflowing from the drain pan Fig 6 1 3 Turn on the main power of the indoor unit The drain pump will be forced to operate even if no remote controller operation is performed Check the transparent drain socket to make sure that drain is discharged 4 When it is confirmed that drain is discharged properly turn off the main power and turn off the SWE on the control board If the SWE remains ...

Страница 7: ...7 ...

Страница 8: ...VN79D552H02 ...

Отзывы: