Mitsubishi Electric PAC-DRP10DP-E Скачать руководство пользователя страница 1

1

Air Conditioning For Building Application

Drain Water Lift-Up Kit  PAC-DRP10DP-E

Installation Manual

This installation manual contains only the description of how to install the Drain water Lift-Up Kit PAC-DRP10DP-E. For information 
about how to wire and how to install air conditioning units, see the installation manual for them.
For your safety, first be sure to read section 1. "Safety Precautions" below thoroughly and then install the Drain water Lift-Up Kit 
PAC-DRP10DP-E correctly.

1. Safety precautions

•   The following two symbols are used to denote dangers that may be caused by incorrect use and their degree:

WARNING

This symbol denotes what could lead to serious injury or death if you misuse the PAC-DRP10DP-E.

CAUTION

This symbol denotes what could lead to a personal injury or damage to your property if you misuse the  

PAC-DRP10DP-E.

•  After reading this installation manual, keep it in a place where the final user can see it anytime he or she wants to it.

 

When someone moves, repairs, or uses the PAC-DRP10DP-E, make sure that this manual is forwarded to the final user.

WARNING

Always have the unit installed by Authorized Mitsubishi 

Representative or similar professional.

Improper installation by the user could result in problems such as 

water leakage, electric shock or fire. 

Always use the designated cables and connect them properly.  

When connecting the terminals, make sure that external forces 

from the cable is not being conveyed to the terminal and then 

tighten it securely.

Improper or loose connections could cause excessive heat or fire.

Only use Mitsubishi-approved accessories, such as an air 

cleaner, humidifier or electric heater.

Always have such accessories installed by an Authorized Mitsubishi 

Representative or similar professional. Improper installation by the 

user may result in water leakage, electric shock or fire.

Install the unit according to this Installation Manual.

If the unit is installed improperly, water leakage, electric shock or fire 

may result.

Have all electric work performed by a properly licensed 

electrician. Electric work should be performed in strict adherence 

to procedures to this Installation Manual. Always provide a 

dedicated power supply.

If the capacity of the power supply is inadequate, it could result in 

problems such as electric shock or fire.

Never modify the unit and always have repairs performed by an 

Authorized Mitsubishi Representative.

Improper repair could result in problems such as water leakage, 

electric shock or fire.

CAUTION

PRECAUTIONS BEFORE INSTALLATION

Never use for special applications such as storing food, plants, 

precision equipment or art.

The quality of these items may deteriorate.

Never use the unit in special environments.

Special environments with high concentrations of oil, steam or sulfuric 

gases will reduce the performance of the air condition and cause its 

parts to deteriorate.

Never install the unit where run-off could result in damage.

If the humidity in the room exceeds 80% or if the drain becomes 

clogged, water may drain off of the indoor unit. When the unit is used 

for heating, there may be drainage from the outdoor unit. If required, 

provide collector drain for the outdoor unit.

Always provide adequate signal noise protection when installing 

in facilities such as hospitals and communication stations.

Equipment at these facilities, such as inverters, in-house generators, 

high-frequency medical equipment, two-way communication 

equipment, may cause the air conditioner to operate improperly.  

Conversely, the signal noise from the air conditioner may affect 

the operation of medical equipment and two-way communication 

equipment and this could interfere with the medical treatment being 

given a patient or cause disturbances or interference in video 

broadcasting equipment.

Содержание PAC-DRP10DP-E

Страница 1: ...y the user may result in water leakage electric shock or fire Install the unit according to this Installation Manual If the unit is installed improperly water leakage electric shock or fire may result Have all electric work performed by a properly licensed electrician Electric work should be performed in strict adherence to procedures to this Installation Manual Always provide a dedicated power su...

Страница 2: ... conditioner with the panel or guard removed The hand could come in contact with rotating hot or high pressure components They could cause electrical shock or entanglement Never operate the air conditioner with the air filter removed Particles will enter into the air conditioner and cause damage Never turn off the power supply immediately after stopping the unit Wait five minutes or more before tu...

Страница 3: ...ng screws 2 locations shown in Fig 3 3 and remove the Drain socket hole cover These screws will be reused to fix the drain socket Keep them in a safe place Fig 3 3 3 2 Attach the drain pump 1 Attach the drain pump assy 1 and drain socket as shown in Fig 3 4 using four PTT screws 4 When attaching the drain socket make sure that drain hose is straight 2 Attach the Rubber Plug 2 Fig 3 4 Control box c...

Страница 4: ...ith the band 3 Fig 4 2 When fastening lead wires Power wires and low voltage wires are separated inside the control box to prevent noise Lead wires from the Drain Water Lift Up Kit also need to be separated so fasten them to the lead wires located inside the control box as described below Since the yellow wire is used for power its remaining portion must be fastened to the lead wires from the powe...

Страница 5: ...se elbows to make it at least height according to the site Fig 5 3 9 Be sure to use the supplied drain hose Accessory Connect each connection with vinyl chloride adhesive But never use any adhesive over the indoor unit discharge port Otherwise the Drain Water Lift Up Kit cannot be serviced later Also the end connection may be eroded by resin and so cracked Note If the rise portion is long there wi...

Страница 6: ...nt water overflowing from the drain pan Fig 6 1 3 Turn on the main power of the indoor unit The drain pump will be forced to operate even if no remote controller operation is performed Check the transparent drain socket to make sure that drain is discharged 4 When it is confirmed that drain is discharged properly turn off the main power and turn off the SWE on the control board If the SWE remains ...

Страница 7: ...7 ...

Страница 8: ...VN79D552H02 ...