9. Reassembly
Reinstall the parts in the reverse order in which they were removed.
10. Confirmation of proper operation
Checking the base heater for normal operation
(1) Use a tester to check that the heater wire is not broken for proper operation.
(2) Check the output voltage for proper circuit operation.
• Base heater energizing conditions*1: Heating mode, outside temperature of 4°C or below, and the compressor is in operation
*1 To meet the above conditions, cool the outdoor temperature sensor (TH7) using a cold spray. When cooling the sensor, make
sure to close the control box panel and Relay Box panel to keep the cold spray from getting on the board inside of the control
box or inside of the Relay Box.