Items
Outdoor unit
PUHY-P600
Ambient temp.
Indoor
DB/WB
Outdoor
Quantity
Set
Indoor unit
Quantity in operation
Condition
Model
–
Main pipe
Piping
Branch pipe
m
Total piping length
Indoor unit fan notch
–
Refrigerant volume
kg
Outdoor
Total current
A
unit
Volts
V
LEV
Indoor unit
Pulse
opening
SC (LEV1)
Pressure
High pressure(after O/S)
/Low pressure(before accumulator)
MPa
Discharge (TH11/TH12)
Heat exchanger outlet (TH5)
Accumulator
Inlet
Outdoor
Outlet
Sectional
unit
Suction (Compressor)
˚C
temp.
Shell bottom (Compressor)
SCC outlet (TH7)
Bypass outlet (TH8)
Indoor
LEV inlet
unit
Heat exchanger outlet
27.0/19.0
35.0/24.0
5
5
200
5
10
55
Hi
28.3
Compressor frequency (No.1/No.2)
Hz
29.6/27.1
380/415
324
324
387
362
222
388
324
387
362
222
246
2.93/0.84
84/86
41
15
15
19/17
47/43
24
8
24
12
PUHY-P650
27.0/19.0
35.0/24.0
5
5
5
10
55
Hi
29.3
33.1/30.3
380/415
266
3.03/0.83
86/86
43
14
14
18/15
53/49
26
7
24
12
200
125
50
25
250
200
125
50
25
50Hz : 104/50
60Hz : 98/60
50Hz : 112/50
60Hz : 107/60
- 90 -