8 FUNCTIONS
8.2 Output HOLD/CLEAR Setting Function
8.2
Output HOLD/CLEAR Setting Function
When the I/O module is disconnected from data link, or the CPU module operating status is STOP, whether to hold or clear
the last output value can be set by this function.
Output HOLD/CLEAR setting and its operation
When HOLD or CLEAR is set for an output, the output is turned on or off as follows.
If a moderate or major error has occurred in the I/O module, output turns off regardless of the output HOLD/CLEAR setting.
Setting method
1.
Set HOLD or CLEAR using the function setting switch 4 of I/O module.
The setting status of output HOLD/CLEAR setting can be checked by bit3 of detailed module information (upper).
For details, refer to the following.
Page 105 Detailed module information (upper)
Operating status
Output HOLD/CLEAR setting
HOLD
Output HOLD/CLEAR setting
CLEAR
Last output status
OFF
Last output status
ON
Last output status
OFF
Last output status
ON
Data link in operation
CPU module in RUN
OFF
ON
OFF
ON
CPU module in STOP
OFF
ON
OFF
OFF
CPU module in PAUSE
OFF
ON
OFF
ON
CPU module in RESET
OFF
ON
OFF
OFF
CPU module suspended by
error
OFF
ON
OFF
OFF
During disconnection/cyclic stop
OFF
ON
OFF
OFF
Function setting switch 4
Output HOLD/CLEAR setting
4
OFF
CLEAR (default)
ON
HOLD
Содержание NZ2MFB1-32D
Страница 2: ......
Страница 14: ...12 1 PRODUCT LINEUP 1 3 I O Combined Module MEMO ...
Страница 16: ...14 2 PART NAMES MEMO ...
Страница 43: ...4 PROCEDURES BEFORE OPERATION 41 4 MEMO ...
Страница 45: ...5 SYSTEM CONFIGURATION 43 5 MEMO ...
Страница 76: ...74 9 PROGRAMMING 9 2 Program Example Program example ...
Страница 78: ...76 10 MAINTENANCE AND INSPECTION MEMO ...
Страница 119: ...APPX Appendix 8 External Dimensions 117 A MEMO ...
Страница 121: ...I 119 MEMO ...
Страница 125: ......