22
3 SPECIFICATIONS
3.2 Performance Specifications
Output module
NZ2MFB2-16R contact output module
*1 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
to a terminal. Connecting two or more wires may cause a poor contact.
*2 It is recommended to use the bar solderless terminal for wiring.
Item
NZ2MFB2-16R
Station type
Slave station
Number of output points
16 points
Rated switching voltage/current
24VDC 2A (resistance load)/point, 8A/common
240VAC 2A (COS
= 1)/point, 8A/common
Minimum switching load
5VDC 1mA
Maximum switching load
264VAC 125VDC
Output response time
OFF
ON
10ms or less
ON
OFF
12ms or less
Life
Mechanical
20 million times or more
Electrical
Rated switching voltage/current load 100 thousand times or more
Page 46 Relay life (contact switching life)
Maximum switching frequency
3600 times/hour
Surge suppressor
None
Fuse
None
Withstand voltage
2300VACrms for 1 minute between all AC external terminals and the ground
510VACrms for 1 minute between all DC external terminals and the ground
Insulation resistance
10M
or higher between all AC external terminals and the ground, all DC external terminals and the
ground (500VDC insulation resistance tester)
Noise immunity
Noise voltage: 1500Vp-p (AC type), 500Vp-p (DC type), noise width 1
s, noise frequency 25 to 60Hz
(noise simulator condition)
Protection degree
IP1X
Wiring method for common
16 points/common (2-wire, screw terminal block type)
External interface
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (Two-piece spring clamp terminal block (push-in
type))
I/O part
34-point one-piece terminal block
Tightening torque range for terminal screw (M3
5.2 screw): 0.59 to 0.88N
m
Applicable DIN rail
TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715)
Applicable wire size
For power supply
Stranded wire: 0.3 to 1.5
(22 to 16 AWG), terminal slot size: 2.8mm
2.0mm
For I/O
Core: 0.3 to 2.0
(22 to 14 AWG)
Applicable solderless
terminal
Terminal block for module
power supply and FG
Page 59 Applicable solderless terminal
Terminal block for output
Page 62 Applicable solderless terminal
Number of occupied stations
One station
Reference response time
1ms
Communication cable
An Ethernet cable that meets the 100BASE-TX standard
For details, refer to the following.
CC-Link IE Field Network Basic Reference Manual
Module power supply
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
153mA or less (24VDC, all points ON)
Weight
0.35kg
Содержание NZ2MFB1-32D
Страница 2: ......
Страница 14: ...12 1 PRODUCT LINEUP 1 3 I O Combined Module MEMO ...
Страница 16: ...14 2 PART NAMES MEMO ...
Страница 43: ...4 PROCEDURES BEFORE OPERATION 41 4 MEMO ...
Страница 45: ...5 SYSTEM CONFIGURATION 43 5 MEMO ...
Страница 76: ...74 9 PROGRAMMING 9 2 Program Example Program example ...
Страница 78: ...76 10 MAINTENANCE AND INSPECTION MEMO ...
Страница 119: ...APPX Appendix 8 External Dimensions 117 A MEMO ...
Страница 121: ...I 119 MEMO ...
Страница 125: ......