APPX
Appendix 3 Setting IP Addresses and Subnet Masks
101
A
Appendix 3
Setting IP Addresses and Subnet Masks
This section describes the setting procedure of IP addresses and subnet masks.
This setting is required when changing IP addresses and subnet masks to specific values. This setting is not required if these
values need not be changed.
Setting procedure
1.
Record the MAC address for I/O module.
2.
Set the IP address setting switch to 0.
3.
Connect the master station and I/O module, and power them on.
4.
Display the network configuration setting window from GX Works3/GX Works2 connected with the master station.
For how to display the network configuration setting window, refer to the following.
CC-Link IE Field Network Basic Reference Manual
5.
Execute the automatic detection of connected device.
[Network Configuration Settings]
[Detect Now]
6.
Select the target I/O module using the MAC address recorded in the step 1, and set an IP address and subnet mask.
7.
Right-click the I/O module in which the setting is reflected, and select "Communication Setting Reflection of Slave
Station".
[Online]
[Communication Setting Reflection of Slave Station]
8.
I/O module restarts, and starts operation with the preset IP address and subnet mask.
9.
Write the set parameter to the CPU module of the master station and reset the CPU module, or turn off and on the power
supply.
[Online]
[Write to PLC]
Содержание NZ2MFB1-32D
Страница 2: ......
Страница 14: ...12 1 PRODUCT LINEUP 1 3 I O Combined Module MEMO ...
Страница 16: ...14 2 PART NAMES MEMO ...
Страница 43: ...4 PROCEDURES BEFORE OPERATION 41 4 MEMO ...
Страница 45: ...5 SYSTEM CONFIGURATION 43 5 MEMO ...
Страница 76: ...74 9 PROGRAMMING 9 2 Program Example Program example ...
Страница 78: ...76 10 MAINTENANCE AND INSPECTION MEMO ...
Страница 119: ...APPX Appendix 8 External Dimensions 117 A MEMO ...
Страница 121: ...I 119 MEMO ...
Страница 125: ......