202
(5) Simultaneous temperature rise AT
PID constants and the simultaneous temperature rise parameter are calculated. The waveform upon execution is
the same as that for the auto tuning function.
For details on the auto tuning function, refer to the following.
(a) How to execute the simultaneous temperature rise AT function
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "1: AT for simultaneous temperature rise" under "CH
Simultaneous temperature rise AT
mode selection".
3.
Turn off and on CH
Auto tuning instruction (RY20 to RY23).
4.
When the operating status is changed from stop to run, simultaneous temperature rise AT starts.
(b) Operation with the simultaneous temperature rise AT function
After the procedure described on
Page 202, Section 8.3.17 (5) (a) is executed, the temperature control
module operates as following.
Operation of the temperature control module
1
CH
Auto tuning status (RX20 to RX23) is turned on. Then normal auto tuning is performed and the simultaneous temperature
rise parameter is calculated.
2
The calculated value is stored in the remote buffer memory when the simultaneous temperature rise parameter is normally
calculated. In addition, CH
AT simultaneous temperature rise parameter calculation completion (b0, b4, b8, b12 of RWr3) is
turned 1 (ON). After auto tuning is completed, CH
Auto tuning status (RX20 to RX23) is turned off and the module is shifted to
the PID control.
OFF
OFF
OFF
ON
ON
ON
0
Control status
Controlled by the program
PID control
Auto tuning
PID control
Calculated
value
CH□ Simultaneous temperature rise gradient data
(address: 2D1H, 2D5H, 2D9H, 2DDH)
and
CH□ Simultaneous temperature rise dead time
(address: 2D2H, 2D6H, 2DAH, 2DEH)
CH□ AT simultaneous temperature rise parameter
calculation completion (b0, b4, b8, b12 of RWr3)
CH□ Auto tuning status
(RX20 to RX23)
CH□ Auto tuning instruction
(RY20 to RY23)
Controlled by the temperature control module
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......