(3) Alert with standby
Even if the temperature process value (PV) or deviation (E) is in a condition to be in an alert status when the
operating status is changed from run to stop, the alert does not occur. The alert function can be disabled until the
temperature process value (PV) or deviation (E) strays out of the condition to be in an alert status.
Ex.
When the alert mode is set to "10: Lower limit deviation alert with wait"
The alert function is inactive until the deviation (E) exceeds the alert set value. (right figure below)
*1
Depending on the alert mode, this value becomes "set value (SV) monitor" or "set value (SV) setting". (
When the system goes into the non-alert status even once after an alert judgment started following the setting of the alert
mode, the alert with standby will be inactive even if the mode is changed to the one with standby.
(a) Setting method
Select one of the following alert modes.
Lower limit deviation alert (
Page 171, Section 8.3.11 (2) (c))
Lower limit deviation alert with standby
Alert mode setting (
Page 176, Section 8.3.11 (6) (a))
Setting value
Alert mode name
7
Upper limit input alert with standby
8
Lower limit input alert with standby
9
Upper limit deviation alert with standby
10
Lower limit deviation alert with standby
11
Upper lower limit deviation alert with standby
19
Upper limit deviation alert with standby (using the set value (SV))
20
Lower limit deviation alert with standby (using the set value (SV))
21
Upper lower limit deviation alert with standby (using the set value (SV))
0
Non-alert status
Alert status
Time
Alert status
Alert set value
Deviation (E)
(= Temperature process value (PV) - Set value (SV)
*1
)
Non-alert status
Alert status
Time
Alert status
Alert set value
Deviation (E)
(= Temperature process value (PV) - Set value (SV)
*1
)
0
Wait operation
region
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......