44
3.5
SLMP
The Ethernet adapter module's devices can be read or written with command messages in the predefined format from
an external device.
For details on SLMP, refer to the following.
SLMP Reference Manual
3.5.1
Available command list
The following table lists the commands that can be executed from an external device to the Ethernet adapter module.
The
part in the Subcommand column varies depending on the specified device. (
SLMP Reference Manual)
Item
Command
Subcommand
Description
Type
Operation
Device
Read
0401
00
1
Reads values in 1-point units from bit devices (consecutive device numbers).
00
0
• Reads values in 16-point units from bit devices (consecutive device numbers).
• Reads values in 1-word units from word devices (consecutive device numbers).
Write
1401
00
1
Writes values to bit devices (consecutive device numbers) in 1-point units.
00
0
• Writes values to bit devices (consecutive device numbers) in 16-point units.
• Writes values to word devices (consecutive device numbers) in 1-word units.
Read Random
0403
00
0
Specifies a device number to read the device value. Discrete device numbers can be
used.
• Reads bit devices in 16- or 32-point units.
• Reads word devices in 1- or 2-word units.
Write Random
1402
00
1
Writes values in 1-point units to bit devices by specifying the device numbers. Discrete
device numbers can be used.
00
0
• Specifies a device number in 16- or 32-point units to write a value to a bit device.
Discrete device numbers can be used for specification.
• Specifies a device number in word units to write a value to a word device. Discrete
device numbers can be used for specification.
Entry Monitor Device
0801
00
0
Registers a device to be read by Execute Monitor (command: 0802).
Execute Monitor
0802
0000
Reads the value of the device registered by Entry Monitor Device (command: 0801).
Read Block
0406
00
0
Specifies n points (1 point: 16 bits) of word or bit devices as one block, and reads
multiple blocks of data. Discrete device numbers can be used for specification.
Write Block
1406
00
0
Specifies n points (1 point: 16 bits) of word or bit devices as one block, and writes
multiple blocks of data. Discrete device numbers can be used for specification.
Memory
Read
0613
0000
Reads buffer memory data of the Ethernet adapter module.
Write
1613
0000
Writes data to the buffer memory of the Ethernet adapter module.
Remote
Control
Remote Run
1001
0000
Executes remote RUN to the Ethernet adapter module.
Remote Stop
1002
0000
Executes remote STOP to the Ethernet adapter module.
Remote Reset
1006
0000
Executes remote RESET to the Ethernet adapter module.
Read Type Name
0101
0000
Reads the model name and code of the Ethernet adapter module.
Clear Error
1617
0000
Turns off the COM.ERR. LED on the Ethernet adapter module.
Ondemand
2101
0000
Issues a send request from the CPU module to the Ethernet adapter module and sends
data to the external device.
Содержание NZ2GF-ETB
Страница 1: ...CC Link IE Field Network Ethernet Adapter Module User s Manual NZ2GF ETB ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURE BEFORE THE OPERATION 4 4 1 Start Up Procedure Memo ...
Страница 82: ...80 10 The following dialog box is displayed 11 Set the switch on the Ethernet adapter module to RUN Click ...
Страница 198: ...196 a Detail Setting ...
Страница 246: ...244 Memo ...
Страница 253: ......