CHAPTER 11 TROUBLESHOOTING
11
11.
2 Er
ror Code
List
11.2
Error Code List
This section describes error codes.
Error codes are classified by error number as follows.
11.2.1
Main D/A converter module
(1) Error code list (0000H to 0FFFH, 1F00H to 1F40H, D529H, D52BH)
The errors are classified into the following three types:
If any of these errors occurs, check that the D LINK LED lights up, and take the corrective actions corresponding
to the error code with the list below.
Error code
Classification
Reference
0000H to 0FFFH, 1F00H to 1F40H, D529H,
D52BH
Errors relating to the main D/A converter module
1000H to 1FFFH
Errors relating to the extension D/A converter
module
D000H to DFFFH (D529H and D52BH excluded)
Errors relating to the CC-Link IE Field Network
(communication error)
Classification
Description
Major error
This error is a sign that recovery is impossible, with the RUN LED turning off.
Moderate error
This error is a sign that the module cannot continue to operate, with the ERR. LED turning on.
Minor error
This error is a sign that the module can continue to operate, with the ERR. LED flashing.
Error code
(hexadecimal)
Classification
Error name
Description and cause
Action
0010H
Major error
Hardware failure
Module hardware error
Turn off and on the module power supply.
If this error persists, the failure of the module is a
possible cause. Please consult your local
Mitsubishi representative.
010
H
Moderate error
Range setting out-
of-range
The value set in Range setting (address:
0103H) is out of the range.
indicates the number of the channel that has
been incorrectly set.
Set the value of Range setting (address: 0103H)
within the allowable range.
0110H
Moderate error
Non-volatile
memory data error
(module working
information)
The non-volatile memory data are abnormal.
• To set the module operation information of the
non-volatile memory back to its default, change
Module operation information initialization
command (address: 1004H) as follows: Not
commanded (0)
Commanded (1)
Not
commanded (0).
• Take anti-noise measures including the use of
shielded cables for connection.
• If this error persists, the failure of the module is
a possible cause. Please consult your local
Mitsubishi representative.
0120H
Moderate error
User range data
damaged (The
channel cannot be
identified.)
The value set in the offset/gain setting is
invalid.
The channel where the error has occurred
cannot be identified.
Start over the offset/gain setting of all channels
where the user range setting is used.
If an error occurs, please consult your local
Mitsubishi representative.