![Mitsubishi Electric NZ2EX2B-60AD4 Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/mitsubishi-electric/nz2ex2b-60ad4/nz2ex2b-60ad4_user-manual_1811811028.webp)
26
*1
For details on the I/O conversion characteristics, refer to the following:
• I/O Conversion Characteristics of A/D Conversion (
*2
Except for the conditions under noise influence.
*3
This current value is an instantaneous value at which no breakdown occurs in the internal resistance of the module. The
maximum input current value for constant application is 24mA.
*4
Do not connect two or more cables to the terminal.
*5
The sampling period varies depending on whether an extension analog module is connected or not. For details, refer to
the following:
• Conversion Speed and Sampling Period (
Applicable
solderless
terminal
Terminal block for
module power
supply and FG
TE 0.5-10 (NICHIFU Co., Ltd.) [Applicable wire size: 0.5
]
TE 0.75-10 (NICHIFU Co., Ltd.) [Applicable wire size: 0.75
]
TE 1.0-10 (NICHIFU Co., Ltd.) [Applicable wire size: 0.9 to 1.0
]
TE 1.5-10 (NICHIFU Co., Ltd.) [Applicable wire size: 1.25 to 1.5
]
AI 0.5-10WH (Phoenix Contact Co., Ltd.) [Applicable wire size: 0.5
]
AI 0.75-10GY (Phoenix Contact Co., Ltd.) [Applicable wire size: 0.75
]
AI 1-10RD (Phoenix Contact Co., Ltd.) [Applicable wire size: 1.0
]
AI 1.5-10BK (Phoenix Contact Co., Ltd.) [Applicable wire size: 1.5
]
Terminal block for
analog input
signals
RAV1.25-3 (compliant with JIS C 2805) [Applicable wire size: 0.3 to 1.25
]
V2-MS3 (JST Mfg. Co., Ltd) [Applicable wire size: 1.25 to 2.0
]
RAP2-3SL (Nippon Tanshi Co., Ltd.) [Applicable wire size: 1.25 to 2.0
]
TGV2-3N (NICHIFU Co., Ltd.) [Applicable wire size: 1.25 to 2.0
]
Cyclic
transmission
RX/RY points
32 16 points
×
Number of extension modules
RWr/RWw points
16 Points of each extension module
Communication cable
An Ethernet cable that meets the 1000BASE-T standard:
Category 5e or higher (double shielded, STP), straight cable
Applicability of extension module
Connectable (Max. one module)
External power supply
24VDC (20.4 to 28.8VDC)
Inrush current: 36.5A, 1ms or lower
Current consumption: 210mA
Weight
0.30kg
Item
Description
Содержание NZ2EX2B-60AD4
Страница 1: ...CC Link IE Field Network Analog Digital Converter Module User s Manual NZ2GF2BN 60AD4 NZ2EX2B 60AD4 ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Страница 156: ...154 3 In the dialog box that appears shown below click button ...
Страница 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Страница 253: ......