Mitsubishi Electric MXZ-4F80VGD Скачать руководство пользователя страница 4

3

3. 

Obstacles in front (blowing) only

When there is an obstacle in front of the 

unit  as  shown  in  the  figure,  open  space 

above, behind, and on the sides of the unit 
is required.

2. 

Front (blowing) side open

As long as space indicated in the 

figure is provided, it is allowed to 

install the unit where obstacles 
are behind and on the sides of 
the unit. (No obstacle above 

the unit)

FREE SPACE REQUIRED AROUND OUTDOOR UNIT

500 or more

200 or more

350 or more

100 or more

1. 

Obstacles above

When there is no obstacle in front and on 
the sides of the unit, it is allowed to install 
the unit where an obstacle is above the 

unit only if the space shown in the figure 

is provided.

100 or more

500 or more

100 or more

Service space

350 or more 

350 or more

6. 

Service space

Provide space for service and maintenance as shown in the figure.

500 or more

100 or more

•  When installing the unit in an area that is enclosed with walls such as a 

verandah, be sure to have enough space as shown below. 

  In this case, the air conditioning capacity and power consumption might 

deteriorate.

•  When there is a lack of airflow or there is a possibility of becoming short 

cycle, install an outlet guide and make sure there is enough space behind 
of the unit.

•  When installing two or more units, do not install the units in front or behind 

each other.

100 or more

200 or more

350 or more

500 or more

500 or more

(Unit: mm)

5. 

Obstacles in front, behind and on side(s)

4. 

Obstacles in front and behind

The unit can be used by attach-
ing an optional outdoor blowing 

guide (PAC-SH96SG-E) (but 

both sides and top are open).

500 or more

100 or more

Blowing guide (PAC-SH96SG-E)

Height of the obstacle is 1200 or less

• 

R32 is heavier than air—as well as other refrigerants—so tends to accumulate at the base (in the vicinity of the floor). If R32 accumulates around base, it may reach 

a flammable concentration in case room is small. To avoid ignition, maintaining a safe work environment is required by ensuring appropriate ventilation. If a refriger

-

ant leak is confirmed in a room or an area where there is insufficient ventilation, refrain from using of flames until the work environment can be improved by ensuring 

appropriate ventilation.

•   Refrigerant pipes connection shall be accessible for maintenance purposes.

•   Install outdoor units in a place where at least one of the four sides is open, and in a sufficiently large space without depressions. 

OK

OK

OK

NG

WG79A820H01_2nd.indd   3

2020/04/08   13:36:19

Содержание MXZ-4F80VGD

Страница 1: ...D MXZ 5F100VGD English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit WG79A820H01_2nd indd 1 2020 04 08 13 36 19 ...

Страница 2: ...nt to securing product safety n Do not discharge the refrigerant into the atmosphere If refrigerant leaks during installation ventilate the room Check that the refrigerant does not leak after installation has been completed If refrigerant leaks and comes in contact with fire or heating part of such a fan heater kerosene heater or cooking stove it will create harmful gas Provide ventilation in acco...

Страница 3: ...the pipe during pipe bending 6 Refrigerant pipe bending radius must be 100 mm or more 7 Insulation material Heat resisting foam plastic 0 045 specific gravity 8 Be sure to use the insulation of specified thickness Excessive thickness may cause incorrect installation of the indoor unit and insufficient thickness may cause dew drippage 9 At least 2 indoor units must be connected when using indoor un...

Страница 4: ...coming short cycle install an outlet guide and make sure there is enough space behind of the unit When installing two or more units do not install the units in front or behind each other 100 or more 200 or more 350 or more 500 or more 500 or more Unit mm 5 Obstacles in front behind and on side s 4 Obstacles in front and behind The unit can be used by attach ing an optional outdoor blowing guide PA...

Страница 5: ...t C Create an appropriate ventilation open area Make sure that the width of the open area is 0 9 m or more and the height of the open area is 0 15 m or more However the height from the bottom of the installation space to the bottom edge of the open area should be 0 125 m or less Open area should be 75 or more opening B Install in a space with a depression height of 0 125 m M kg Amin m 1 0 12 1 5 1...

Страница 6: ... the bottom of the indoor unit is h0 for wall mounted 1 8 m or more for ceiling suspended cassette and ceiling concealed 2 2 m or more When installing floor standing refer to indoor unit Installation manual There are restrictions in installation height for each model so read the installation manual for the particular unit For wall mounted ceiling suspended cassette and concealed Only for MFXZ M kg...

Страница 7: ...or piping connection 3 Attach the drain socket to one of the several drain holes Fix the drain socket into the drain hole of the base using the catches to secure it in place 4 Connect the soft PVC hose I D 15 mm as shown in the illustration 5 Make sure to provide drain piping with a downhill grade for easy drain flow 6 Glue the drain caps to close all the other unnecessary holes with the glue Prep...

Страница 8: ...A and indoor outdoor unit connecting wire B be sure to fix both cable and wire with cable clamps Connecting order Connect the terminal block in following order 5F100VGD Terminal block for power supply Service panel Screws Cable cover Cable clamp MXZ 5F100VGD A B C D E P DR MXZ 4F80VGD A B C D P DR DR DR DR DR Power supply Terminal block for indoor outdoor unit Terminal block for DRED interface Wir...

Страница 9: ... then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety Pipe size mm ø6 35 ø9 52 ø12 7 ø15 88 ø19 05 ø22 2 ø...

Страница 10: ...port make sure that the valve core is in closed position and then tighten part A Do not tighten part A or turn the body when valve core is in open position 4 PURGING PROCEDURES LEAK TEST AND TEST RUN Service port cap Torque 13 7 to 17 7 N m 140 to 180 kgf cm Stop valve cap Torque 19 6 to 29 4 N m 200 to 300 kgf cm Make sure to replace the cap after the operation R32 4 2 GAS CHARGE Perform gas char...

Страница 11: ...tion mode in COOL DRY mode set the 4 of SW1 on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner SW1 ON 1 2 3 4 5 6 SW1 ON 1 2 3 4 5 6 LED SW1 SW871 SW2 4 5 HOW TO SET LOW STANDBY POWER MODE Use of the low standby power mode is recommended when none of the indoor units listed in Table 1 is connected to ...

Страница 12: ...e result is Not completed press the piping wiring correction switch SW871 again to cancel this function Then confirm the wiring and piping combination in a conventional manner by operating the indoor units one by one The operation is done while the power is supplied Make sure not to contact parts other than the switch including the P C board This may cause electric shock or burn by hot parts and l...

Страница 13: ...manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 0 05 MPa Gauge approx 0 0 5 kgf cm2 or the protec tion function may operate due to the pressure increase in the high pressure refrigerant circuit If this occurs use a refrigerant collecting device to collect all of the refrigerant in the system and ...

Страница 14: ......

Страница 15: ......

Страница 16: ...WG79A820H01 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN WG79A820H01_2nd indd 13 2020 04 08 13 36 23 ...

Отзывы: