Mitsubishi Electric MXZ-4D83 Скачать руководство пользователя страница 6

En-5

4-1. PURGING PROCEDURES AND LEAK TEST

Fig. 

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

3.  FLARING WORK AND PIPE CONNECTION

3-1. FLARING WORK

Pipe diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch 

type tool  

for R40A

Clutch 

type tool  

for R22

Wing nut 

type tool  

for R22

N•m

kgf•cm

ø6.35 (/4”)

7

0 to 0.5 .0 to .5

.5 to 2.0

3.7 to 7.7 40 to 80

ø9.52 (3/8”)

22

34.3 to 4.2 350 to 420

ø2.7 (/2”)

26

2.0 to 2.5

49.0 to 56.4 500 to 575

ø5.88 (5/8”)

29

73.5 to 78.4 750 to 800

Tilted Uneven Burred

Good

No good

Burr Copper pipe

Spare reamer

Pipe cutter

Smooth all 

around

Even length 

all around

Inside is shin-

ing without any 

scratches.

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

3-2. PIPE CONNECTION

1) Apply a thin coat of refrigeration oil (G) to the flared ends of the pipes 

and the pipe connections of the outdoor unit. Do not apply refrigeration 

oil on screw threads. Excessive tightening torque will result in damage 

on the screw.

2) Align the center of the pipe with that of the pipe connections of the out-

door unit, then hand tighten the flare nut 3 to 4 turns.

3) Tighten the flare nut with a torque wrench as specified in the table.

• Over-tightening may cause damage to the flare nut, resulting in refrig

-

erant leakage.

• Be sure to wrap insulation around the piping. Direct contact with the 

bare piping may result in burns or frostbite.

3-3. INSULATION AND TAPING

) Cover piping joints with pipe cover.

2) For outdoor unit side, surely insulate every piping including valves.

3) Using  piping  tape  (E),  apply  taping  starting  from  the  entry  of  outdoor 

unit.

•  Stop  the  end  of  piping  tape  (E)  with  tape  (with  adhesive  agent  at-

tached).

•  When  piping  have  to  be  arranged  through  above  ceiling,  closet  or 

where the temperature and humidity are high, wind additional commer-

cially sold insulation to prevent condensation.

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Copper 

pipe

) Cut the copper pipe correctly with pipe cutter. (Fig. , 2)

2) Completely remove all burrs from the cut cross section of pipe. (Fig. 3)

•  Aim  the  copper  pipe  downward  while  removing  burrs  to  prevent 

burrs from dropping in the pipe.

3) Remove flare nuts attached to indoor and outdoor units, then put them 

on pipe having completed burr removal. (Not possible to put them on 

after flaring work.) 

4) Flaring  work  (Fig.  4,  5).  Firmly  hold  copper  pipe  in  the  dimension 

shown in the table. Select A mm from the table according to the tool 

selected.

5) Check 

•  Compare the flared work with Fig. 6.

•  If flare is noted to be defective, cut off the flared section and do flar

-

ing work again.

) Remove service port cap of stop valve on the side of the outdoor unit 

gas pipe. (The stop valves are fully closed and covered in caps in their 

initial state.)

2) Connect  gauge  manifold  valve  and  vacuum  pump  to  service  port  of 

stop valve on the gas pipe side of the outdoor unit.

3) Run the vacuum pump. (Vacuumize for more than 5 minutes.)

4) Check the vacuum with gauge manifold valve, then close gauge mani-

fold valve, and stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure the pointer of gauge 

manifold  valve  remains  in  the  same  position.  Confirm  that  pressure 

gauge shows -0.0 MPa [Gauge] (-760 mmHg).

6) Remove gauge manifold valve quickly from service port of stop valve.

7) Fully open all stop valves on the gas pipe and the liquid pipe. Operat-

ing without fully opening lowers the performance and this causes trou-

ble.

8) Refer  to  -2.,  and  charge  the  prescribed  amount  of  refrigerant  if 

needed.  Be  sure  to  charge  slowly  with  liquid  refrigerant.  Otherwise, 

composition of the refrigerant in the system may be changed and af-

fect performance of the air conditioner.

9) Tighten cap of service port to obtain the initial status.

0) Leak test

 

WARNING

When installing  the  unit,  securely 

connect the refrigerant pipes before 

starting the compressor.

 

CAUTION

When  there  are  the  ports  which are 

not  used,  make  sure  their  nuts  are 

tightened securely.

Service port cap

(Torque 3.7 to 

7.7 N•m, 40 to 

80 kgf•cm)

Stop valve 

for GAS

Stop valve cap

(Torque 9.6 to 

29.4 N•m, 200 

to 300 kgf•cm)

Gauge manifold 

valve (for R40A)

Compound pressure 

gauge (for R40A)

–0.0MPa  

(–760 mmHg)

Handle 

Low

Handle High

Vacuum pump

(for R40A)

Charge hose 

(for R40A)

*Close

*Open

Hexagonal wrench

*4 to 5 turns

Stop valve 

for LIQUID

Pressure gauge

(for R40A)

Precautions when using 

the control valve

When attaching the control valve to 

the service port, valve core may de-

form or loosen if excess pressure is 

applied. This may cause gas leak.

Service port

Charge hose 

(for R40A)

Body

Close

Open

Control 

valve

A

When attaching the control valve to 

the service port, make sure that the 

valve core is in closed position, and 

then  tighten  part A.  Do  not  tighten 

part A or turn the body when valve 

core is in open position.

JG79A662H01_en.indd   5

2012/09/24 (月)   午後 7:00:11

Содержание MXZ-4D83

Страница 1: ...ς μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidade interior consulte o manual de instalação da unidade interior Installationshåndbog Til INSTALLATØREN Denne håndbog beskriver kun hvordan udendørsenheden installeres Ve...

Страница 2: ...entilation in accord ance with EN378 1 n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri...

Страница 3: ...ility of becoming short cycle install an outlet guide and make sure there is enough space behind of the unit When installing two or more units do not install the units in front or behind each other 100 or more 200 or more 350 or more 500 or more 500 or more Unit mm 5 Obstacles in front behind and on side s 4 Obstacles in front and behind The unit can be used by at taching an optional outdoor blowi...

Страница 4: ...00 mm 2 U shape notched holes Base bolt M10 320 mm 2 12 mm 36 mm oval holes Base bolt M10 355 mm 387 mm After the leak test apply insulat ing material tightly so that there is no gap When the piping is to be at tached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation viny...

Страница 5: ...cting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening Af ter tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 Fix indoor outdoor unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 2 PIPE CONN...

Страница 6: ...y hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section and do flar ing work again 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe The stop valves are fully closed and covered in caps in their initial state...

Страница 7: ...ler board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please note that the cooling and heating capacity may lower if this function is activated ...

Страница 8: ...board damage To prevent electronic control P C board damage make sure to perform static elimi nation before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED1 Red LED2 Yellow LED3 Green Lighted Lighted Once Result of piping wiring correction function LED1 Red LED2 Yellow LED3 Green Result Lighted Not lighted Ligh...

Страница 9: ...Z 5D102VA MXZ D VA Parts Catalogue OBB626G MXZ 2D 5DVA Service Manual OBH626E MXZ 4D83 and MXZ 5D102 Installation Manual JG79A662H01 MXZ 4D83 and MXZ 5D102 Declaration of Conformity MXZ 4D83 and MXZ 5D102 Declaration of Conformity ...

Отзывы: