background image

En-5

4-1. PURGING PROCEDURES AND LEAK TEST

Fig. 

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

3.  FLARING WORK AND PIPE CONNECTION

3-1. FLARING WORK

Pipe diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch 

type tool  

for R40A

Clutch 

type tool  

for R22

Wing nut 

type tool  

for R22

N•m

kgf•cm

ø6.35 (/4”)

7

0 to 0.5

.0 to .5

.5 to 2.0

3.7 to 7.7 40 to 80

ø9.52 (3/8”)

22

34.3 to 4.2 350 to 420

ø2.7 (/2”)

26

2.0 to 2.5

49.0 to 56.4 500 to 575

ø5.88 (5/8”)

29

73.5 to 78.4 750 to 800

Tilted Uneven Burred

Good

No good

Burr

Copper pipe

Spare reamer

Pipe cutter

Smooth all 
around

Even length 
all around

Inside is shin-
ing without any 
scratches.

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

3-2. PIPE CONNECTION

1) Apply a thin coat of refrigeration oil (G) to the flared ends of the pipes 

and the pipe connections of the outdoor unit. Do not apply refrigeration 
oil  on  screw  threads.  Excessive  tightening  torque  will  result  in  damage 
on the screw.

2) Align the center of the pipe with that of the pipe connections of the out-

door unit, then hand tighten the flare nut 3 to 4 turns.

3) Tighten the flare nut with a torque wrench as specified in the table.

• Over-tightening may cause damage to the flare nut, resulting in refrig

-

erant leakage.

•  Be  sure  to  wrap  insulation  around  the  piping.  Direct  contact  with  the 

bare piping may result in burns or frostbite.

3-3. INSULATION AND TAPING

) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3) Using  piping  tape  (E),  apply  taping  starting  from  the  entry  of  outdoor 

unit.
•  Stop  the  end  of  piping  tape  (E)  with  tape  (with  adhesive  agent  at-

tached).

•  When  piping  have  to  be  arranged  through  above  ceiling,  closet  or 

where the temperature and humidity are high, wind additional commer-
cially sold insulation to prevent condensation.

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Copper 
pipe

) Cut the copper pipe correctly with pipe cutter. (Fig. , 2)
2) Completely remove all burrs from the cut cross section of pipe. (Fig. 3)

•  Aim  the  copper  pipe  downward  while  removing  burrs  to  prevent 

burrs from dropping in the pipe.

3) Remove flare nuts attached to indoor and outdoor units, then put them 

on pipe having completed burr removal. (Not possible to put them on 

after flaring work.) 

4) Flaring  work  (Fig.  4,  5).  Firmly  hold  copper  pipe  in  the  dimension 

shown  in  the  table.  Select  A  mm  from  the  table  according  to  the  tool 
selected.

5) Check 

•  Compare the flared work with Fig. 6.

•  If flare is noted to be defective, cut off the flared section and do flar

-

ing work again.

) Remove service port cap of stop valve on the side of the outdoor unit 

gas pipe. (The stop valves are fully closed and covered in caps in their 
initial state.)

2) Connect  gauge  manifold  valve  and  vacuum  pump  to  service  port  of 

stop valve on the gas pipe side of the outdoor unit.

3) Run the vacuum pump. (Vacuumize for more than 5 minutes.)
4) Check the vacuum with gauge manifold valve, then close gauge mani-

fold valve, and stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure the pointer of gauge 

manifold  valve  remains  in  the  same  position.  Confirm  that  pressure 

gauge shows -0.0 MPa [Gauge] (-760 mmHg).

6) Remove gauge manifold valve quickly from service port of stop valve.
7) Fully open all stop valves on the gas pipe and the liquid pipe. Operat-

ing without fully opening lowers the performance and this causes trou-
ble.

8) Refer  to  -2.,  and  charge  the  prescribed  amount  of  refrigerant  if 

needed.  Be  sure  to  charge  slowly  with  liquid  refrigerant.  Otherwise, 
composition of the refrigerant in the system may be changed and af-
fect performance of the air conditioner.

9) Tighten cap of service port to obtain the initial status.
0) Leak test

 

WARNING

When  installing  the  unit,  securely 
connect  the  refrigerant  pipes  before 
starting the compressor.

 

CAUTION

When  there  are  the  ports  which  are 
not  used,  make  sure  their  nuts  are 
tightened securely.

Service port cap
(Torque 3.7 to 
7.7 N•m, 40 to 
80 kgf•cm)

Stop valve 
for GAS

Stop valve cap
(Torque 9.6 to 
29.4 N•m, 200 
to 300 kgf•cm)

Gauge manifold 
valve (for R40A)

Compound pressure 
gauge (for R40A)

–0.0MPa  
(–760 mmHg)

Handle 
Low

Handle High

Vacuum pump
(for R40A)

Charge hose 
(for R40A)

*Close

*Open

Hexagonal wrench

*4 to 5 turns

Stop valve 
for LIQUID

Pressure gauge
(for R40A)

Precautions when using 
the control valve

When attaching the control valve to 
the service port, valve core may de-
form or loosen if excess pressure is 
applied. This may cause gas leak.

Service port

Charge hose 
(for R40A)

Body

Close

Open

Control 
valve

A

When attaching the control valve to 
the service port, make sure that the 
valve core is in closed position, and 
then  tighten  part A.  Do  not  tighten 
part A  or  turn  the  body  when  valve 
core is in open position.

BH79A024H01_en.indd   5

2014/01/21   13:46:50

Содержание MXZ-4D80VA

Страница 1: ...nual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit Split type Air Conditioner MXZ 4D80VA MXZ 5D100VA English ...

Страница 2: ...nerated n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or materials and inc...

Страница 3: ...ow or there is a possibility of becoming short cycle install an outlet guide and make sure there is enough space behind of the unit When installing two or more units do not install the units in front or behind each other 100 or more 200 or more 350 or more 500 or more 500 or more Unit mm 5 Obstacles in front behind and on side s 4 Obstacles in front and behind The unit can be used by at taching an...

Страница 4: ...7 mm After the leak test apply insulat ing material tightly so that there is no gap When the piping is to be at tached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down...

Страница 5: ...s conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening Af ter tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 Fix indoor outdoor unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make ...

Страница 6: ...ring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section and do flar ing work again 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe The stop valves are fully closed and covered in caps...

Страница 7: ... on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please note that the cooling and heating capacity may lower if this...

Страница 8: ...vent electronic control P C board damage make sure to perform static elimi nation before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED1 Red LED2 Yellow LED3 Green Lighted Lighted Once Result of piping wiring correction function LED1 Red LED2 Yellow LED3 Green Result Lighted Not lighted Lighted Completed Probl...

Отзывы: