<Heating>
Design Condition
Outdoor Design Wet Bulb Temperature
35.6ºF (2.0ºC)
Total Heating Load
34.4 kBTU/h
Room1
Indoor Design Dry Bulb Temperature
69.8ºF (21.0ºC)
Heating Load
16.3 kBTU/h
Room2
Indoor Design Dry Bulb Temperature
73.4ºF (23.0ºC)
Heating Load
18.1 kBTU/h
<Other> Indoor/Outdoor Equivalent Piping Length
230 ft
2. Heating Calculation
(1) Temporary Selection of Indoor Units
Room1
MSZ-FH15
18.0 kBUT/h (Rated)
20.3 kBUT/h (Rated)
Room2
MSZ-FH18
(2) Total Indoor Units Capacity
15 + 18 = 33
(3) Selection of Outdoor Unit
The P36 outdoor unit is selected as total indoor units capacity is P33
MXZ-4C36
45.0 kBUT/h
(4) Total Indoor Units Capacity Correction Calculation
Room1
Indoor Design Dry Bulb Temperature Correction (69.8ºF)
1.00 (Refer to Figure 4)
Room2
Indoor Design Dry Bulb Temperature Correction (73.4ºF)
0.92 (Refer to Figure 4)
CT
L Ȉ,QGRRU8QLW5DWLQJî,QGRRU'HVLJQ7HPSHUDWXUH&RUUHFWLRQ
îî
N%78K
(5) Outdoor Unit Correction Calculation
Outdoor Design Wet Bulb Temperature Correction (35.6ºF)
1.0 (Refer to Figure 5)
Piping Length Correction (230 ft)
Defrost Correction
0.96 (Refer to Figure 6)
0.89 (Refer to Table 1)
7RWDO2XWGRRU8QLW&DSDFLW\&7R
7RWDO,QGRRU8QLWV&DSDFLW\&7L
CTo = Outdoor
8
nit Rating
î
Outdoor Design Temperature Correction
î
Piping Length
Correction
î
Defrost Correction
îîî
N%78K
(6) Determination of Maximum System Capacity
&RPSDULVRQRI&DSDFLW\EHWZHHQ7RWDO,QGRRU8QLWV&DSDFLW\&7LDQG7RWDO2XWGRRU8QLW&DSDFLW\&7R
CTi = 36.7 < CTo = 38.4, thus, select CTi.
&7[ &7L N%78K
(7) Comparison with Essential Load
Against the essential load 34.4 kBTU/h, the maximum system capacity is 36.7 kBTU/h: Proper outdoor units have been selected.
(8) Calculation of Maximum Indoor Unit Capacity of Each Room
CTx = CTi, thus, calculate by the calculation below
Room1
0D[LPXP&DSDFLW\î5RRP&DSDFLW\DIWHUWKH7HPSHUDWXUH&RUUHFWLRQ5RRP7RWDO&DSDFLW\DIWHUWKH7HPSHUDWXUH&RUUHFWLRQ
îîî
+
î
N%78K
OK: fulfills the load 16.3 kBTU/h
Room2
0D[LPXP&DSDFLW\î5RRP&DSDFLW\DIWHUWKH7HPSHUDWXUH&RUUHFWLRQ5RRP7RWDO&DSDFLW\DIWHUWKH7HPSHUDWXUH&RUUHFWLRQ
=
îîî
+
î
=
N%78K
OK: fulfills the load 18.1 kBTU/h
Completed selecting units since the selected units fulfill the heating loads of Room 1, 2.
Figure 4
Indoor unit temperature correction
To be used to correct indoor unit only
Figure 5
Outdoor unit temperature correction
To be used to correct outdoor unit only
Figure 6
Correction of refrigerant piping length
-4
5
14
23
32
41
50
59
-25
-20
-15
-10
-5
0
5
10
15
0.4
0.5
0.6
0.7
0.8
0.9
0.8
0.5
0.6
0.7
1.0
1.1
1.2
1.0
1.1
1.3
1.4
Ratio of heating capacity
Outdoor Temperature [°C W.B.]
70.0°F (21.1°C) D.B
15
16
17
18
19
20
21
22
23
24
25
26
27
59 60.8 62.6 64.4 66.2 68 69.8 71.6 73.4 75.2 77 78.8 80.6
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Ratio of heating capacity
Indoor Temperature
[°C D.B.]
[°F W.B.]
[°C D.B.]
[°F W.B.]
Indoor
Temperature
0
20
40
60
80
100
120
140
160
180
200
220
240
260
0.70
0.75
0.80
0.85
0.90
0.95
1.00
Total capacity of indoor unit
Capacity ratio
Piping equivalent length (ft)
7DEOH7DEOHRIFRUUHFWLRQIDFWRUDWIURVWDQGGHIURVW
2XWGRRU,QWDNHWHPSHUDWXUH:%)&!
í
í
í
í
í
í
íí íí
&RUUHFWLRQIDFWRU
Capacity of indoor unit
0RGHO1XPEHUIRULQGRRU
XQLW
0RGHO
0RGHO
0RGHO
0RGHO
0RGHO
0RGHO
0RGHO
0RGHO
0VHULHV
0RGHO&DSDFLW\>.%WXK@
ņ
ņ
3VHULHV
ņ
ņ
ņ
6(=
ņ
ņ
ņ
ņ
6/=
ņ
ņ
ņ
ņ
ņ
09=
ņ
ņ
ņ
)RU06=)+)(1$
)RU06=*(*/1$
)RUWKHPRGHOVRWKHUWKDQ
DQG
DERYH
OCH573E
Содержание MXZ-4C36NAHZ
Страница 42: ... MXZ 4C36NAHZ U1 MXZ 5C42NAHZ U1 MXZ 8C48NAHZ U1 OCH573E ...
Страница 43: ... MXZ 8C48NA U1 OCH573E ...
Страница 44: ... MXZ 8C60NA U1 OCH573E ...
Страница 45: ... 6 2 BRANCH BOX PAC MKA50BC PAC MKA30BC 10ths DIGIT OCH573E ...
Страница 163: ... OCH573E ...