2

 CAUTION

(Could lead to serious injury in particular environments when operated incorrectly.)

n

  Install an earth leakage breaker depending on the installation place.

 

If an earth leakage breaker is not installed, it could cause electric shock.

n

  Perform the drainage/piping work securely according to the installation 

manual.

  If there is defect in the drainage/piping work, water could drop from the unit, 

soaking and damaging household goods.

n

  Do not touch the air inlet or the aluminum fins of the outdoor unit.

  This could cause injury. 

n

  Do not install the outdoor unit where small animals may live.

 

If small animals enter and touch the electric parts inside the unit, it could cause a 

malfunction, smoke emission, or fire. Also, advise user to keep the area around 

the unit clean. 

Do not operate the air conditioner during interior construction and finish

-

ing work, or while waxing the floor. 

 

Before operating the air conditioner, ventilate the room well after such work is 
performed. Otherwise, it may cause volatile elements to adhere inside the air 
conditioner, resulting in water leakage or scattering of dew.

1-2. SPECIFICATIONS

1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS

If the diameter of connection pipe does not match the port size of outdoor unit, use optional different-diameter joints according to the following table.

(Unit: mm (inch))

Port size of outdoor unit

Optional different-diameter joints 

(port size of outdoor unit → diameter of connection pipe)

MXZ-2F52VGD

MXZ-3F54VGD

MXZ-4F71VGD

Liquid / Gas

6.35 (1/4) → 9.52 (3/8) : PAC-493PI

9.52 (3/8) → 12.7 (1/2) : MAC-A454JP-E

9.52 (3/8) → 15.88 (5/8) : PAC-SG76RJ-E

12.7 (1/2) → 9.52 (3/8) : MAC-A455JP-E

12.7 (1/2) → 15.88 (5/8) : MAC-A456JP-E

Refer to the installation manual of indoor unit for the diameter of connec-
tion pipe of indoor unit.

A UNIT

6.35 (1/4) / 12.7 (1/2)

A - B UNIT

A - C UNIT

B - D UNIT

6.35 (1/4) / 9.52 (3/8)

*1  Connect to the power switch which has a gap of 3 mm or more when open to interrupt the 

source power phase. (When the power switch is shut off, it must interrupt all phases.)

*2  Use wires in conformity with design 60245 IEC 57. Use the indoor/outdoor connecting wire 

in conformity with the wire specifications specified in the installation manual of the indoor 

unit.

*3  Never use pipes with thickness less than specified. The pressure resistance will be insuf

-

ficient.

*4  Use a copper pipe or a copper-alloy seamless pipe.
*5  Be careful not to crush or bend the pipe during pipe bending.
*6  Refrigerant pipe bending radius must be 100 mm or more.

*7  Insulation material : Heat resisting foam plastic 0.045 specific gravity

*8  Be sure to use the insulation of specified thickness. Excessive thickness may cause incor

-

rect installation of the indoor unit and insufficient thickness may cause dew drippage.

*9  If the outdoor unit is installed higher than the indoor unit, max. height difference is reduced 

to 10 m.

1-4. SELECTING THE INSTALLATION LOCATION

•  Where it is not exposed to strong wind.

•  Where airflow is good and dustless.

•  Where rain or direct sunshine can be avoided as much as possible.
•  Where neighbours are not annoyed by operation sound or hot air.
•  Where rigid wall or support is available to prevent the increase of opera-

tion sound or vibration.

•  Where there is no risk of combustible gas leakage.
•  When installing the unit, be sure to secure the unit legs.
•  Where it is at least 3 m away from the antenna of TV set or radio. Opera-

tion of the air conditioner may interfere with radio or TV reception in areas 

where reception is weak. An amplifier may be required for the affected 

device.

•  Install the unit horizontally.

•  Please install it in an area not affected by snowfall or blowing snow. In 

areas with heavy snow, please install a canopy, a pedestal and/or some 

baffle boards.

Note:

It is advisable to make a piping loop near outdoor unit so as to reduce 
vibration transmitted from there.

Model

Power supply *1

Wire specifications *2

Pipe length and height difference 

*3, *4, *5, *6, *7, *8

Rated 

Voltage

Frequency

Breaker 

capacity

Power 
supply

Indoor/outdoor 

connecting wire

Max. pipe length 

per indoor unit / for 

multi-system

Max. height 

difference *9

Max. no. of bends 

per indoor unit / for 

multi system

MXZ-2F52VGD

220 V - 60 Hz
230 V - 50 Hz

15 A

3-core

 2.5 mm

2

4-core 

1.0/1.5 mm

2

20 m / 40 m

15 m

20 / 40

MXZ-3F54VGD

20 A

25 m / 50 m

25 / 50

MXZ-4F71VGD

25 m / 60 m

25 / 60

Model

Maximum amount of 

refrigerant charge

Factory-charged 

refrigerant amount

MXZ-2F52VGD
MXZ-3F54VGD
MXZ-4F71VGD

2.4 kg

2.4 kg

Note: 

When operating the air conditioner in low outside temperature, be sure 
to follow the instructions described below.
•  Never install the outdoor unit in a place where its air inlet/outlet side 

may be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet 

side facing the wall.

• 

To prevent exposure to wind, it is recommended to install a baffle 

board on the air outlet side of the outdoor unit.

Avoid the following places for installation where air conditioner trouble 
is liable to occur.

•  Where flammable gas could leak.

•  Where there is much machine oil.

•  Where oil is splashed or where the area is filled with oily smoke 

(such as cooking areas and factories, in which the properties of 

plastic could be changed and damaged).

•  Salty places such as the seaside.

•  Where sulfide gas is generated such as a hot spring.

•  Where there is high-frequency or wireless equipment.
•   Where there is emission of high levels of VOCs, including phthalate 

compounds, formaldehyde, etc., which may cause chemical cracking.

•  The appliance shall be stored so as to prevent mechanical damage 

from occurring.

VG79Y194H01_3rd.indd   2

2020/04/08   13:44:30

Содержание MXZ-2F52VGD

Страница 1: ...3F54VGD MXZ 4F71VGD English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit VG79Y194H01_3rd indd 1 2020 04 08 13 44 29 ...

Страница 2: ...gerant does not leak after installation has been completed If refrigerant leaks and comes in contact with fire or heating part of such a fan heater kerosene heater or cooking stove it will create harmful gas Provide ventilation in accordance with EN378 1 n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with...

Страница 3: ... and insufficient thickness may cause dew drippage 9 If the outdoor unit is installed higher than the indoor unit max height difference is reduced to 10 m 1 4 SELECTING THE INSTALLATION LOCATION Where it is not exposed to strong wind Where airflow is good and dustless Where rain or direct sunshine can be avoided as much as possible Where neighbours are not annoyed by operation sound or hot air Whe...

Страница 4: ...RED AROUND OUTDOOR UNIT 500 or more 200 or more 350 or more 100 or more 1 Obstacles above When there is no obstacle in front and on the sides of the unit it is allowed to install the unit where an obstacle is above the unit only if the space shown in the figure is provided 500 or more 100 or more 4 Obstacles in front and behind The unit can be used by at taching an optional outdoor blowing guide M...

Страница 5: ...t C Create an appropriate ventilation open area Make sure that the width of the open area is 0 9 m or more and the height of the open area is 0 15 m or more However the height from the bottom of the installation space to the bottom edge of the open area should be 0 125 m or less Open area should be 75 or more opening B Install in a space with a depression height of 0 125 m M kg Amin m 1 0 12 1 5 1...

Страница 6: ...e are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 3 1 5 4 5 2 0 6 2 5 7 5 3 0 9 3 5 12 4 0 15 5 4 5 20 5 0 24 5 5 29 6 0 35 6 5 41 7 0 47 7 5 54 For wall mounted ceiling suspended cassette and concealed Only for MFXZ M kg Amin m 1 00 No requirements 1 10 1 20 1 30 1 40 1 50 1 60 1 70 1 80 1 84 3 63 1 90 3 75 2 00 3 95 2...

Страница 7: ...t connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the left table is quantity to be used per indoor unit WARNING To avoid risk of fire embed or protect the refrigerant piping External damage on the refrigerant piping can be cause of fire When the piping is to be attached to a wall containing metals tin plated or metal netting use a chemica...

Страница 8: ...mly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 Connect the demand control transmission cable to the terminal block for DRED Interface 7 Fix indoor outdoor unit connecting wire B and power supply cord A with the cable clamps 8 Fix the demand...

Страница 9: ...3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section...

Страница 10: ...owers the performance and this causes trouble 8 Refer to 1 2 and charge the prescribed amount of refrigerant if needed Be sure to charge slowly with liquid refrigerant 9 Tighten cap of service port to obtain the initial status 10 Leak test Union Stop valve Liquid pipe Indoor unit Stop valve with service port Gas pipe Refrigerant gas cylinder operating valve for R32 R410A Gauge manifold valve for R...

Страница 11: ...ain power for the air conditioner HEAT COOL DRY LED SW1 SW871 SW2 SW1 ON 1 2 3 4 5 6 SW1 ON 1 2 3 4 5 6 4 5 HOW TO SET LOW STANDBY POWER MODE Use of the low standby power mode is recommended when none of the indoor units listed in Table 1 is connected to the outdoor unit The low standby power mode can be set with the dip switch SW1 and the jumper connector SC751 Before turning on the breaker at fi...

Страница 12: ...se the remote controller how to remove the air filters how to remove or put the remote controller in the remote controller holder how to clean precautions for operation etc Recommend the user to read the OPERATING INSTRUCTIONS carefully Procedure Press the piping wiring correction switch SW871 1 minute or more after turning on the power supply Correction completes in 10 to 15 minutes When the corr...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...VG79Y194H01 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VG79Y194H01_3rd indd 12 2020 04 08 13 44 33 ...

Отзывы: