Mitsubishi Electric MXZ-2F52VF Скачать руководство пользователя страница 9

8

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

3-2. FLARING WORK

Pipe 

diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch 

type tool  

for R32, 

R410A

Clutch 

type tool  

for R22

Wing nut 

type tool  

for R22

N•m

kgf•cm

ø6.35 

(1/4”)

17

0 to 0.5

1.0 to 1.5

1.5 to 2.0

13.7 to 17.7 140 to 180

ø9.52 

(3/8”)

22

34.3 to 41.2 350 to 420

ø12.7 

(1/2”)

26

2.0 to 2.5

49.0 to 56.4 500 to 575

ø15.88 

(5/8”)

29

73.5 to 78.4 750 to 800

Tilted Uneven Burred

Good

No good

Burr

Copper pipe

Spare reamer

Pipe cutter

Smooth all 
around

Even length 
all around

Inside is shin-
ing without any 
scratches.

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

Copper 
pipe

1) Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)
2) Completely remove all burrs from the cut cross section of pipe. (Fig. 3)

•  Aim the copper pipe downward while removing burrs to prevent burrs 

from dropping in the pipe.

3) Remove flare nuts attached to indoor and outdoor units, then put them on 

pipe having completed burr removal. (Not possible to put them on after 

flaring work.) 

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown 

in the table. Select A mm from the table according to the tool selected.

5) Check 

•  Compare the flared work with Fig. 6.

•  If flare is noted to be defective, cut off the flared section and do flaring 

work again.

3-3. PIPE CONNECTION

•  The connected pipe size differs depending the models and the capacities 

of indoor units.

Indoor unit capacity

15 ~ 42

50

Liquid pipe size

ø6.35

ø6.35

Gas pipe size

Indoor unit: MSZ

ø9.52

ø9.52 *1

Indoor unit: other

ø9.52

ø12.7

*1 Use a joint pipe if the connection of the indoor unit differs.

•  Use tightening torque table above as a guideline for indoor unit side union 

joint section, and tighten using two wrenches. Excessive tightening dam-

ages the flare section.

1) Apply a thin coat of refrigeration oil (G) to the flared ends of the pipes and 

the pipe connections of the outdoor unit.

2) For connection, first align the center, then tighten the first 3 to 4 turns of 

flare nut, by hand.

3) Tighten the flare nut with a torque wrench as specified in the table.

•  Over-tightening may cause damage to the flare nut, resulting in refrigerant 

leakage.

•  Be sure to wrap insulation around the piping. Direct contact with the bare 

piping may result in burns or frostbite.

3-4. INSULATION AND TAPING

1) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3) Using piping tape (E), apply taping starting from the entry of outdoor unit.

•  Stop the end of piping tape (E) with tape (with adhesive agent attached).
•  When piping have to be arranged through above ceiling, closet or where 

the temperature and humidity are high, wind additional commercially sold 
insulation to prevent condensation.

 WARNING

When installing the unit, securely connect the refrigerant pipes 
before starting the compressor.

 CAUTION

When there are the ports which are not used, make sure their 
nuts are tightened securely.

 WARNING

To avoid risk of fire, flare connection should be installed out

-

doors. Reusable mechanical connectors and flared joints are 

not allowed indoors. 
When connecting the refrigerant piping by brazing, rether than 

using flare connections, complete all brazing prior to connecting 

indoor unit to outdoor unit. 

VG79Y196H02.indd   8

2020/05/27   11:45:09

Содержание MXZ-2F52VF

Страница 1: ...XZ 2F52VF English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit VG79Y196H02 indd 1 2020 05 27 11 45 06 ...

Страница 2: ...l cover of the indoor unit and or the service panel of the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc n When installing relocating or servicing the unit make sure that no substance other than the specified refrigerant R32 enters the refrigerant circuit Any presence of foreign substance such as air can cause abnormal pres sure rise an...

Страница 3: ...alloy seamless pipe 5 Be careful not to crush or bend the pipe during pipe bending 6 Refrigerant pipe bending radius must be 100 mm or more 7 Insulation material Heat resisting foam plastic 0 045 specific gravity 8 Be sure to use the insulation of specified thickness Excessive thickness may cause incorrect installation of the indoor unit and insufficient thickness may cause dew drippage 9 If the o...

Страница 4: ... in a sufficiently large space without depressions 1 4 1 Minimum installation area for Outdoor units If you unavoidably install a unit in a space where all four sides are blocked or there are depressions confirm that one of these situations A B or C is satisfied Note These countermeasures are for keeping safety not for specification guarantee A Secure sufficient installation space minimum installa...

Страница 5: ... the height from the floor to the bottom of the indoor unit is h0 for wall mounted 1 8 m or more for ceiling suspended cassette and ceiling concealed 2 2 m or more for floor standing refer to indoor unit Installation manual There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 3 1 5 4 5 2 0 6 2 5 7 5 3 0 9 3 5 12 4 0 15...

Страница 6: ... M kg Amin m 1 00 No requirements 1 10 1 20 1 30 1 40 1 50 1 60 1 70 1 80 1 84 3 63 1 90 3 75 2 00 3 95 2 10 4 15 2 20 4 34 2 30 4 54 2 40 4 74 h0 Refer to indoor unit installation manual Floor standing VG79Y196H02 indd 5 2020 05 27 11 45 07 ...

Страница 7: ...When the piping is to be attached to a wall containing metals tin plated or metal netting use a chemically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according to the dimension for ...

Страница 8: ...SE R32 REFRIGERANT Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thicknesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contaminants...

Страница 9: ... Use a joint pipe if the connection of the indoor unit differs Use tightening torque table above as a guideline for indoor unit side union joint section and tighten using two wrenches Excessive tightening dam ages the flare section 1 Apply a thin coat of refrigeration oil G to the flared ends of the pipes and the pipe connections of the outdoor unit 2 For connection first align the center then tig...

Страница 10: ...ure is applied This may cause gas leak Service port Charge hose for R32 R410A Body Close Open Control valve A When attaching the control valve to the service port make sure that the valve core is in closed position and then tighten part A Do not tighten part A or turn the body when valve core is in open position Service port cap Torque 13 7 to 17 7 N m 140 to 180 kgf cm Charge hose for R32 R410A 4...

Страница 11: ...e Make sure that the following is done Power is supplied to the unit Stop valves are open About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner When relocating or disposing of the air conditioner pump down the system following the procedure below so that no refrigerant ...

Страница 12: ...VG79Y196H02 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VG79Y196H02 indd 11 2020 05 27 11 45 09 ...

Отзывы: