136
No.
Symptom
Indication
Abnormal point / Con-
dition
Condition
Remedy
LED1(Red) LED2(Yellow)
21 'Outdoor unit
stops and
restarts
3 minutes
later' is
repeated.
13 times
Not lighted
Outdoor fan motor
A failure occurs 3 consecutive times within 30
seconds after the fan gets started.
• Refer to 11-6. "Check of outdoor fan motor".
22
Lighted
8 times
Current sensor protec-
tion
A short or open circuit is detected in the current
sensor during compressor operating.
• Replace the outdoor power P.C. board.
23
Lighted
11 times
Communication
between P.C. boards
protection
Communication error occurs between the outdoor
control P.C. board and outdoor power P.C. board
for more than 10 seconds.
• Check the connecting wire between outdoor con-
trol P.C. board and outdoor power P.C. board.
24
Lighted
12 times
Zero cross detecting
circuit (outdoor power
P.C. board)
Zero cross signal cannot be detected while the
compressor is operating.
• Replace the outdoor power P.C. board.
25 Outdoor unit
operates.
Once
Lighted
Primary current protec-
tion
The input current exceeds 15 A.
These symptoms do not mean any abnormality of
the product, but check the following points.
• Check if indoor
fi
lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short
cycled.
26
Twice
Lighted
High-pressure protec-
tion
The indoor gas pipe temperature exceeds 45°C
during heating.
Defrosting in cooling
The indoor gas pipe temperature falls 3°C or below
during cooling.
27
3 times
Lighted
Discharge temperature
protection
The frequency of the compressor is kept 80 Hz or
more and the discharge temperature is kept under
50°C(COOL mode)/40°C(HEAT mode) for more
than 40 minutes.
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-6. "Check of LEV".
• Refer to 11-6. "Check of outdoor thermistors".
28
4 times
Lighted
Low discharge
temperature protection
The frequency of the compressor is kept 80 Hz or
more and the discharge temperature is kept under
39°C for more than 20 minutes.
• Refer to 11-6. "Check of LEV".
• Check refrigerant circuit and refrigerant amount.
29
5 times
Lighted
Cooling high-pressure
protection
The outdoor heat exchanger temperature exceeds
58°C during operation.
This symptom does not mean any abnormality of
the product, but check the following points.
• Check if indoor
fi
lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short
cycled.
30
7 times
Lighted
High Low
Pressure bypass
valve
Cooling evaporating
temperature drop
prevention control
During cooling operation, the temperature of indoor
heat exchanger becomes 3°C or less within 1 hour
after the compressor starts running, or it becomes
less than 12°C - 16°C* later than that.
* It depends on the difference between the set
temperature and the room temperature.
This symptom does not mean any abnormality of
the product, but check the following points.
• Check the indoor
fi
lters are not clogged.
• Check there is suf
fi
cient refrigerant.
• Check the indoor/outdoor unit air circulation is not
short cycled.
31 Outdoor
unit
operates
normally.
7 times
Lighted
High Low
pressure bypass valve
High pressure protec-
tion control at start-up
of heating operation
The room temperature is 24°C or more when 1 or
2 unit(s) start(s) the heating operation.
This symptom does not mean any abnormality of
the product.
32
High Low
pressure bypass valve
Compressor oil temper-
ing control at start-up of
heating operation
Both the following are true:
• The outside temperature is -2°C or less when the
heating operation is started.
• [(Discharge temperature) - (Indoor heat exchang-
er temperature)] < 5°C
33
8 times
Lighted
Cooling evaporating
temperature
protection
During cooling operation, the temperature of
indoor heat exchanger becomes 7°C - 11°C*
or less within 1 hour after the compressor
starts running, or it becomes 9°C - 17°C* or
less later than that.
* It depends on the indoor unit type/model or the
difference between the set temperature and the
room temperature.
34
Lighted
Lighted
Normal
—
—
NOTE 1. The location of LED is illustrated at the right figure. Refer to 11-7.2.
2. LED is lighted during normal operation.
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
LED1 LED2
Lighted
Outdoor control P.C. board
(Parts side)
OBH626K
Содержание MXZ-2D33VA
Страница 25: ...25 WIRING DIAGRAM 6 MXZ 2D33VA E1 MXZ 2D40VA E1 MXZ 2D53VA E1 OUTDOOR DISPLAY P C BOARD OBH626K ...
Страница 26: ...26 MXZ 2D33VA E2 MXZ 2D42VA E2 MXZ 2D53VA E2 OBH626K ...
Страница 27: ...27 MXZ 2D33VA E3 MXZ 2D42VA E3 MXZ 2D53VA E3 OBH626K ...
Страница 28: ...28 MXZ 2D33VA ER2 MXZ 2D40VA ER2 MXZ 2D53VA ER2 OBH626K ...
Страница 29: ...29 MXZ 2D33VA ER3 MXZ 2D42VA ER3 MXZ 2D53VA ER3 OBH626K ...
Страница 30: ...30 MXZ 2D33VA ET2 MXZ 2D42VA ET2 MXZ 2D53VA ET2 OBH626K ...
Страница 31: ...31 MXZ 2D33VA ET3 MXZ 2D42VA ET3 MXZ 2D53VA ET3 OBH626K ...
Страница 33: ...33 MXZ 2D53VAH E1 OUTDOOR DISPLAY P C BOARD OBH626K ...
Страница 34: ...34 MXZ 2D53VAH E2 OBH626K ...
Страница 35: ...35 MXZ 2D53VAH E3 OBH626K ...
Страница 36: ...36 MXZ 2D53VAH ER2 OBH626K ...
Страница 37: ...37 MXZ 2D53VAH ER3 OBH626K ...
Страница 39: ...39 MXZ 3D54VA E1 OBH626K ...
Страница 40: ...40 MXZ 3D54VA2 E2 OBH626K ...
Страница 41: ...41 MXZ 3D54VA2 E3 OBH626K ...
Страница 42: ...42 MXZ 3D54VA2 ER2 OBH626K ...
Страница 43: ...43 MXZ 3D54VA2 ER3 OBH626K ...
Страница 44: ...44 MXZ 3D54VA2 ET2 OBH626K ...
Страница 45: ...45 MXZ 3D54VA2 ET3 OBH626K ...
Страница 46: ...46 MXZ 3D68VA E1 OBH626K ...
Страница 47: ...47 MXZ 3D68VA E2 OBH626K ...
Страница 48: ...48 MXZ 3D68VA E3 OBH626K ...
Страница 49: ...49 MXZ 3D68VA ER2 OBH626K ...
Страница 50: ...50 MXZ 3D68VA ER3 OBH626K ...
Страница 51: ...51 MXZ 3D68VA ET2 OBH626K ...
Страница 52: ...52 MXZ 3D68VA ET3 OBH626K ...
Страница 53: ...53 MXZ 4D72VA E1 OBH626K ...
Страница 54: ...54 MXZ 4D72VA E2 OBH626K ...
Страница 55: ...55 MXZ 4D72VA E3 OBH626K ...
Страница 56: ...56 MXZ 4D72VA ER2 OBH626K ...
Страница 57: ...57 MXZ 4D72VA ER3 OBH626K ...
Страница 58: ...58 MXZ 4D72VA ET2 OBH626K ...
Страница 59: ...59 MXZ 4D72VA ET3 OBH626K ...
Страница 60: ...60 MXZ 4D83VA E1 OBH626K ...
Страница 61: ...61 MXZ 4D83VA E2 OBH626K ...
Страница 62: ...62 MXZ 4D83VA ER1 OBH626K ...
Страница 63: ...63 MXZ 4D83VA ER2 OBH626K ...
Страница 64: ...64 MXZ 4D83VA ET2 OBH626K ...
Страница 65: ...65 MXZ 5D102VA E1 OBH626K ...
Страница 66: ...66 MXZ 5D102VA E2 OBH626K ...
Страница 67: ...67 MXZ 5D102VA ER1 OBH626K ...
Страница 68: ...68 MXZ 5D102VA ER2 OBH626K ...
Страница 69: ...69 MXZ 5D102VA ET2 OBH626K ...