Check of R.V. coil
The cooling operation or heating operation does not operate.
No
Yes
No
Yes
No
Yes
No
Yes
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY
OPERATION in COOL mode.
Is there voltage of 208/230 V AC between pin1
and pin2 at connector CN712?
Turn OFF the power supply.
Disconnect the connector CNAC2.
Replace the 4-way valve.
Replace the outdoor
control P.C. board.
Replace the R.V. coil.
Is there voltage 208/230 V AC
between the pin1 and pin3 at
connector CNAC?
Replace the outdoor
power P.C. board.
Is there normal resistance
to R.V. coil? (Refer to 11-5.)
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY
OPERATION in HEAT mode.
Is there voltage of 208/230 V AC between pin1
and pin2 at connector CN712?
Replace the 4-way valve.
Replace the outdoor control P.C. board.
:KHQFRROLQJRSHUDWLRQGRHVQRWZRUN
:KHQKHDWLQJRSHUDWLRQGRHVQRWZRUN
CNAC
CN712
Outdoor control
P.C. board
CNAC2
Outdoor power
P.C. board
OBH702E
Содержание MXZ-2C20NAHZ
Страница 17: ...17 MXZ 4C36NA MXZ 4C36NA2 Unit inch mm Lock nut Conduit plates Conduit connector OBH702E ...
Страница 19: ...19 MXZ 2C20NAHZ MXZ 2C20NAHZ2 Unit inch mm Lock nut Conduit connector Conduit plate OBH702E ...
Страница 21: ...21 MXZ 3C24NA MXZ 3C30NA WIRING DIAGRAM 6 OBH702E ...
Страница 22: ...22 MXZ 3C24NA2 MXZ 3C30NA2 OBH702E ...
Страница 23: ...23 MXZ 4C36NA OBH702E ...
Страница 24: ...24 MXZ 4C36NA2 OBH702E ...
Страница 26: ...26 MXZ 5C42NA2 OBH702E ...
Страница 27: ...27 MXZ 2C20NAHZ OBH702E ...
Страница 28: ...28 MXZ 2C20NAHZ2 OBH702E ...
Страница 29: ...29 MXZ 3C24NAHZ MXZ 3C30NAHZ OBH702E ...
Страница 30: ...30 MXZ 3C24NAHZ2 MXZ 3C30NAHZ2 OBH702E ...