background image

6

4. Flaring work

 

 Perform 

fl

 aring  work  using 

fl

 aring tool as shown in the 

right.

Outside 

diameter

A (mm)

Flare tool for 

R410A clutch type

Conventional 

fl

 are tool

Clutch type

Wing nut type

ø6.35 mm

0 to 0.5

1.0 to 1.5

1.5 to 2.0

ø9.52 mm

0 to 0.5

1.0 to 1.5

1.5 to 2.0

Firmly hold copper pipe in a die in the dimension shown in 
the table above.

5. Check

 

 Compare the 

fl

 ared work with the 

fi

 gure below.

 

 If 

fl

 are is noted to be defective, cut off the 

fl

 ared section 

and perform 

fl

 aring work again.

5-3 PIPE CONNECTION

Note:
Fasten a 

fl

 are nut with a torque wrench as speci

fi

 ed in the table below.

When fastened too tight, a 

fl

 are nut may be broken after a long period and cause a leakage of refrigerant.

1.  Indoor unit connection

 

  Connect both liquid pipe and gas pipe to indoor unit.

 

  - Apply a thin coat of refrigeration oil to the seat surface of pipe.

 

  - For connection, align the center of both pipe and union, then tighten the 

fi

 rst 3 to 4 turns in 

fl

 are nut by 

hand.

 

  - For tightening the union part of the indoor unit side, use the table below as a standard and tighten the 

fl

 are nut with two wrenches. Excessive tightening damages the 

fl

 ared section.

Pipe diameter

Tightening torque

N·m

kgf·cm

ø6.35 mm

13.7 to 17.7

140 to 180

ø9.52 mm

34.3 to 41.2

350 to 420

2.  Outdoor unit connection

 

  Connect pipes to the pipe joint part of the stop valve in the same method as the indoor unit.

 

  - For tightening, use the same tightening torque applied for indoor unit and tighten the 

fl

 are  nut  with 

torque wrench or spanner.

INSULATION AND TAPING

1

 Cover piping joints with pipe cover.

2

 For outdoor unit side, surely insulate every piping including valves.

3

 Using piping tape 

E

, apply taping starting from the entry of outdoor unit.

   Fix the end of piping tape 

E

 with adhesive tape.

   When piping has to be arranged through above ceiling, closet or area where the temperature and humidity 

are high, wind additional commercially sold insulation for prevention of condensation.

A

Die

Copper pipe

Flare nut

Die

Copper pipe

Smooth all around

Even length
all around

Inside is shining without any scratches

Yo rk

Flaring tool

Wing nut type

Clutch type

5-4 PURGING PROCEDURES • LEAK TEST

 

 Perform the manifold valve work securely according to the installation manual of the manifold valve.

PURGING PROCEDURES

Connect the refrigerant pipes (both liquid pipe and gas pipe) between the indoor and the outdoor 
unit.

Remove the service port cap of the stop valve on the gas pipe side of the outdoor unit. (The stop 
valve will not work in it initial state fresh out of the factory [totally closed with cap on].)

Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the 
gas pipe side of the outdoor unit.

Run the vacuum pump. (Vacuumize for more than 15 minutes.)

Check the vacuum with the gauge manifold valve, then close the gauge manifold valve and stop 
the vacuum pump.

Leave it as is for one or two minutes. Make sure the pointer of the gauge manifold valve remains in 
the same position. Con

fi

 rm that the pressure gauge shows –0.101 MPa [Gauge] (–760 mmHg).

(or the vacuum
pump with the
function to prevent
the back flow)

Gauge manifold
valve (for R410A)

Pressure gauge
    (for R410A)

Compound pressure
gauge (for R410A)

-0.101MPa
(-760 mmHg)

Handle
Low

Handle High

Window

Charge hose (for R410A)

Vacuum

pump

Adapter for
preventing
the back flow

Charge hose
(for R410A)

Stop valve
(gas side)

Service port

* Perform the purging procedures

on both 

 unit and 

 unit sides.

A

B

Remove the gauge manifold valve quickly from the service port of the stop valve.

After refrigerant pipes are connected and evacuated, fully open all stop valves on both sides of gas 
pipe and liquid pipe.
Operating without fully opening lowers the performance and this causes trouble.

Pipe length up to 20 m 

No gas charge is needed.

Pipe length exceeding 20 m

Charge the prescribed
amount of gas. (refer to 5-1)

Tighten the cap to the service port to obtain the initial status.

Retighten the cap.

Leak test

SG79Y644H01.indd   6

SG79Y644H01.indd   6

29.11.2005   17:04:14 Uhr

29.11.2005   17:04:14 Uhr

Содержание MXZ-2A52VA

Страница 1: ...LLATION DIAGRAM ACCESSORIES 2 3 SELECTING THE INSTALLATION LOCATION 3 4 OUTDOOR UNIT INSTALLATION 4 5 INDOOR OUTDOOR UNITS CONNECTION FINISHING AND TEST RUN 5 IMPORTANT NOTES TO COMPLY WITH THE REQUIREMENTS OF AUSTRALIAN STANDARD AS 3000 S A A WIRING RULES THE ELECTRICAL WIRING REQUIRED BETWEEN THE INDOOR AND OUTDOOR UNITS MUST BE INSTALLED BY A LICENCED ELECTRICAL CONTRACTOR SG79Y644H01 indd 1 SG...

Страница 2: ...tdoor unit are not attached se curely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or specified parts for the installation work The use of defective parts could cause an injury due to a fire an electric shock the unit falling leakage of water etc Be sure to cut off the main power in case of set ting up the indoor electronic control P C board...

Страница 3: ...upport is available to prevent the increase of operation sound or vibration Where there is no risk of combustible gas leakage When installing the unit at a high level be sure to fix the unit legs Where it is at least 3 m away from the antenna of TV set or radio Operation of the air conditioner may interfere with radio or TV reception in areas where reception is weak An amplifier may be required fo...

Страница 4: ...t Take enough care to connect the indoor outdoor unit connecting wire correctly between the respective indoor units and the outdoor unit Make earth wire a little longer than the others more than 35 mm 35 mm 15 mm POWER SUPPLY LY L N 230 V 50 Hz UNIT UNIT For the power supply cord and the indoor outdoor unit connecting wires be sure to use the ones in compli ance with the standards Be sure to push ...

Страница 5: ...A52VA Outdoor unit Indoor unit UNIT Indoor unit UNIT PIPING PREPARATION 1 If you use commercially available copper pipes use the following table for pipe specifications Outside diameter Wall thickness Liquid pipe ø6 35 mm 0 8 mm Gas pipe ø9 52 mm 0 8 mm 2 For insulation material use 8 mm thick heat insulating expended polyethylene with a specific gravity of 0 045 3 Ensure that the 2 refrigerant pi...

Страница 6: ...n for prevention of condensation A Die Copper pipe Flare nut Die Copper pipe Smooth all around Even length all around Inside is shining without any scratches Y ork Flaring tool Wing nut type Clutch type 5 4 PURGING PROCEDURES LEAK TEST Perform the manifold valve work securely according to the installation manual of the manifold valve PURGING PROCEDURES Connect the refrigerant pipes both liquid pip...

Страница 7: ... can lower the operating noise of the outdoor unit when the operation load is small for example during nighttime in COOL mode However please note that the cooling and heating capacity can also be lowered if this function is acti vated Initial setting is required to activate this function Please explain about this function to your custom ers and ask them whether they want to use it How to lower the...

Страница 8: ... cannot detect any erroneous connection if any of the refrigerant pipes and the indoor outdoor unit connecting wires About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner 5 11 EXPLANATION TO THE CUSTOMER Recommend the customer to read the OPERATING INSTRUCTIONS carefull...

Страница 9: ......

Страница 10: ...HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN SG79Y644H01 SG79Y644H01 indd 9 SG79Y644H01 indd 9 29 11 2005 17 04 16 Uhr 29 11 2005 17 04 16 Uhr ...

Отзывы: