3) HEATING CAPACITY
Model
Indoor air
Outdoor intake air WB temperature (˚F)
IDB (˚F)
5
15
25
35
43
45
55
TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
MUZ-HM09NA
MUZ-HM09NA2
75
4.8
0.53
6.3
0.67
7.9
0.79
9.4
0.88
10.6
0.92
11.0
0.94
12.4
0.97
70
5.2
0.51
6.7
0.65
8.2
0.77
9.6
0.86
10.9
0.90
11.2
0.92
12.7
0.95
65
5.5
0.49
6.9
0.62
8.6
0.74
10.0
0.83
11.2
0.88
11.6
0.89
13.0
0.94
MUZ-HM12NA
MUZ-HM12NA2
75
5.4
0.58
7.1
0.74
8.8
0.87
10.6
0.97
11.9
1.01
12.3
1.03
13.9
1.07
70
5.8
0.56
7.5
0.71
9.2
0.85
10.8
0.94
12.2
0.99
12.6
1.01
14.2
1.05
65
6.1
0.53
7.7
0.68
9.6
0.82
11.2
0.92
12.6
0.97
12.9
0.98
14.5
1.03
MUZ-HM15NA
MUZ-HM15NA2
75
7.9
0.94
10.4
1.19
13.1
1.40
15.6
1.56
17.6
1.64
18.1
1.66
20.5
1.73
70
8.6
0.90
11.1
1.15
13.5
1.37
15.9
1.52
18.0
1.60
18.5
1.63
21.0
1.70
65
9.0
0.86
11.3
1.10
14.1
1.32
16.5
1.48
18.5
1.56
19.1
1.58
21.4
1.66
MUZ-HM18NA
MUZ-HM18NA2
75
7.9
0.94
10.4
1.18
13.1
1.39
15.6
1.55
17.6
1.63
18.1
1.65
20.5
1.72
70
8.6
0.90
11.1
1.14
13.5
1.36
15.9
1.51
18.0
1.59
18.5
1.62
21.0
1.69
65
9.0
0.86
11.3
1.10
14.1
1.31
16.5
1.47
18.5
1.55
19.1
1.57
21.4
1.65
MUZ-HM24NA
MUZ-HM24NA2
75
11.4
1.48
15.1
1.86
18.9
2.19
22.5
2.44
25.4
2.56
26.1
2.60
29.6
2.70
70
12.4
1.41
16.0
1.80
19.5
2.14
23.0
2.38
26.0
2.50
26.8
2.55
30.3
2.65
65
13.0
1.35
16.4
1.73
20.4
2.06
23.8
2.31
26.8
2.44
27.6
2.48
30.9
2.60
NOTE
: 1. IDB : Intake air dry-bulb temperature
TC : Total Capacity (x10
3
Btu/h)
TPC : Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL
mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch or press any button on the remote con-
troller.
OBH747C