10-1. CHANGE IN DEFROST SETTING
<JS> When the JS wire of the inverter P.C. board is cut/ soldered, the defrost finish temperature is changed. (Refer to
11-6-1.)
MUZ-HJ25VA MUZ-HJ35VA MUZ-HJ50VA
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after
confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
MUZ-HJ25VA MUZ-HJ35VA MUZ-HJ50VA
10-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low discharge tempera-
ture. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature is
20°C or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W)
<JK> When the JK wire of the inverter P.C. board is cut, pre-heat control is activated. (Refer to 11-6.1)
NOTE :
When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
Jumper wire
Defrost fi nish temperature (
°C
)
MUZ-HJ25/35VA
MUZ-HJ50VA
JS
Soldered
(Initial setting)
8
None (Cut)
11
15
10
SERVICE FUNCTIONS
11
TROUBLESHOOTING
3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To
make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service
work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 11-2 and 11-3.
Lead wiring
Housing point
<Incorrect>
<Correct>
OBH648A