13
DATA
7
MUZ-FH09NA MUZ-FH09NAH MUZ-FH12NA MUZ-FH12NAH MUZ-FH15NA MUZ-FH15NAH
7-1. PERFORMANCE DATA
1) COOLING CAPACITY
Model
Indoor air
Outdoor intake air DB temperature (˚F)
IWB (˚F)
75
85
95
105
115
TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC
MUZ-FH09NA
MUZ-FH09NAH
71
11.0
8.7
0.50
10.3
8.1
0.55
9.7
7.6
0.59
9.0
7.1
0.62
8.3
6.5
0.64
67
10.4
9.6
0.47
9.7
8.9
0.52
9.0
8.3
0.56
8.4
7.7
0.59
7.7
7.1
0.62
63
9.8
10.3
0.45
9.1
9.6
0.50
8.5
8.9
0.53
7.7
8.1
0.57
7.0
7.4
0.59
MUZ-FH12NA
MUZ-FH12NAH
71
14.7
10.2
0.77
13.7
9.6
0.85
12.9
9.0
0.91
12.0
8.4
0.96
11.0
7.7
1.00
67
13.9
11.6
0.73
13.0
10.8
0.80
12.0
10.0
0.87
11.2
9.3
0.92
10.3
8.5
0.97
63
13.1
12.6
0.70
12.1
11.7
0.77
11.3
10.9
0.83
10.3
9.9
0.89
9.4
9.0
0.92
MUZ-FH15NA
MUZ-FH15NAH
71
18.4
10.4
1.07
17.2
9.7
1.17
16.1
9.1
1.26
15.0
8.5
1.33
13.8
7.8
1.38
67
17.4
12.2
1.01
16.2
11.3
1.11
15.0
10.5
1.20
14.0
9.8
1.27
12.8
9.0
1.33
63
16.4
13.6
0.96
15.2
12.6
1.06
14.1
11.8
1.15
12.8
10.7
1.22
11.7
9.8
1.27
NOTE
: 1. IWB : Intake air wet-bulb temperature
TC
: Total Capacity (x10
3
Btu/h)
SHC : Sensible Heat Capacity (x10
3
Btu/h) TPC : Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor Intake air DB temperature.
2) COOLING CAPACITY CORRECTIONS
Refrigerant piping length (one way: ft.)
25 (std.)
40
65
100
MUZ-FH09NA
MUZ-FH09NAH
MUZ-FH12NA
MUZ-FH12NAH
1.0
0.954
0.878
-
MUZ-FH15NA
MUZ-FH15NAH
1.0
0.954
0.878
0.771
OBH584A
Содержание MUZ-FH09NA
Страница 8: ...8 5 WIRING DIAGRAM MUZ FH09NA MUZ FH12NA MUZ FH09NAH MUZ FH12NAH OBH584A ...
Страница 9: ...9 MUZ FH15NA OBH584A ...
Страница 10: ...10 MUZ FH15NAH OBH584A ...
Страница 51: ...51 OBH584A ...