34
Check the resistance of fan motor. (Refer to
11-4.)
Is the resistance of
fan motor normal?
Replace the outdoor
fan motor.
Disconnect the connector CN771 on the
inverter P.C. board.
Disconnect the connector (CN61) between
compressor and power transistor module.
Turn ON the power supply and press the
EMERGENCY OPERATION switch.
Does the upper lamp of
OPERATION
INDICATOR lamp on
the indoor unit light up?
After 3 minutes, is
there voltage 230 VAC
between CN771 and
on the inverter P.C.
board?
Replace the outdoor
fan motor.
Replace the inverter
P.C. board.
Yes
No
Yes
No
I Check of outdoor fan motor
OBH751